FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
5
Without a drain pump
Model
FXDQ20PDVET
FXDQ25PDVET
Power supply
1 phase, 220-240/220 V, 50/60 Hz
1 phase, 220-240/220 V, 50/60 Hz
1
3 Cooling capacity
kcal/h
1,900
2,400
Btu/h
7,500
9,600
kW
2.2
2.8
2
3 Heating capacity
kcal/h
2,200
2,800
Btu/h
8,500
10,900
kW
2.5
3.2
Power input
Cooling
50 Hz
kW
0.067
0.067
60 Hz
kW
0.073
0.073
Heating
50 Hz
kW
0.067
0.067
60 Hz
kW
0.073
0.073
Casing / Colour
Galvanized steel plate
Galvanized steel plate
Dimensions: (H×W×D)
mm
200×700×620
200×700×620
Fan
Model
—
—
Type
Sirocco fan
Sirocco fan
Motor output ×
Number of units
W
62×1
62×1
Airflow rate
(HH/H/L)
m³/min
8.0/7.2/6.4
8.0/7.2/6.4
l/s
133/120/106
133/120/106
cfm
282/254/226
282/254/226
4 External static pressure
Pa
30-10
30-10
Drive
Direct drive
Direct drive
Temperature control
Microprocessor thermostat for cooling and
heating
Microprocessor thermostat for cooling and
heating
Sound absorbing thermal insulation material
Foamed polyethylene
Foamed polyethylene
Air filter
Removal / Washable / Mildew proof
Removal / Washable / Mildew proof
Piping
connections
Liquid pipes
mm
φ
6.4 (Flare connection)
φ
6.4 (Flare connection)
Gas pipes
mm
φ
12.7 (Flare connection)
φ
12.7 (Flare connection)
Drain pipe
mm
VP20 (External dia. 26, Internal dia. 20)
VP20 (External dia. 26, Internal dia. 20)
Mass
kg
23
23
5 Sound pressure level (HH/H/L) dB(A)
28/26/23
28/26/23
Sound power level (HH/H/L)
dB(A)
56/54/51
56/54/51
Safety devices
Fuse, Thermal protector for fan motor
Fuse, Thermal protector for fan motor
Refrigerant control
Electronic expansion valve
Electronic expansion valve
Standard accessories
Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers,
Insulation for fitting, Clamp metal, Washer
fixing plate, Screws for duct flanges, Air filter
Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers,
Insulation for fitting, Clamp metal, Washer
fixing plate, Screws for duct flanges, Air filter
Drawing No.
Specifications
C: 3D109082B
C: 3D109082B
Sound level
C: 4D112287
C: 4D112290
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. External static pressure is changeable to set by the remote controller. This pressure means “High static
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND
models.)
5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.
Conversion formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
l/s=m³/min×1000/60
Summary of Contents for VRV FXDQ-PDVE
Page 1: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 201710 Engineering Data 50 60 Hz...
Page 2: ......
Page 16: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 14 FXDQ63NDVE with a drain pump 3D045496F Unit mm...
Page 18: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 16 FXDQ63NDVET without a drain pump 3D049702D Unit mm...
Page 26: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 24 FXDQ32PDVE FXDQ32PDVET 3D052157E...
Page 27: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 25 9 2 FXDQ NDVE T FXDQ40NDVE FXDQ40NDVET 3D046299G...
Page 28: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 26 FXDQ50NDVE FXDQ50NDVET 3D046300G...
Page 29: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 27 FXDQ63NDVE FXDQ63NDVET 3D046301G...
Page 31: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 29 FXDQ32PDVE FXDQ32PDVET 4D112291...
Page 33: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 31 FXDQ63NDVE FXDQ63NDVET 4D112295...
Page 36: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 34 FXDQ63NDVE FXDQ63NDVET 4D043887Q Unit mm...
Page 53: ......
Page 54: ......
Page 55: ......