FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
21
8. Capacity Tables
8.1 Cooling Capacity for Te: Auto
Model
Capacity
indication
Indoor air temp.
14°CWB
16°CWB
18°CWB
19°CWB
20°CWB
22°CWB
24°CWB
20°CDB
23°CDB
26°CDB
27°CDB
28°CDB
30°CDB
32°CDB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
FXDQ20PDVE
FXDQ20PDVET
20
1.9
1.8
2.1
1.9
2.2
1.9
2.2
1.9
2.2
1.8
2.3
1.6
2.3
1.7
FXDQ25PDVE
FXDQ25PDVET
25
2.5
2.1
2.6
2.2
2.8
2.3
2.8
2.1
2.8
2.1
2.9
2.0
3.0
1.9
FXDQ32PDVE
FXDQ32PDVET
32
3.2
2.4
3.4
2.6
3.5
2.6
3.6
2.6
3.6
2.4
3.7
2.4
3.8
2.4
FXDQ40NDVE
FXDQ40NDVET
40
4.0
3.0
4.2
3.3
4.4
3.4
4.5
3.3
4.6
3.1
4.7
3.0
4.8
3.1
FXDQ50NDVE
FXDQ50NDVET
50
4.9
3.7
5.3
4.0
5.5
4.2
5.6
4.0
5.7
3.9
5.8
3.8
5.9
3.5
FXDQ63NDVE
FXDQ63NDVET
63
6.3
4.8
6.7
5.1
7.0
5.3
7.1
4.9
7.2
4.6
7.3
4.6
7.5
4.6
TC: Total capacity: kW
SHC: Sensible heat capacity: kW
Notes:
1. These capacity tables are for use when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system
satisfies the required heat load.
2.
shows rated condition.
8.2 Cooling Capacity for Te: 6°C
Model
Capacity
indication
Indoor air temp.
14°CWB
16°CWB
18°CWB
19°CWB
20°CWB
22°CWB
24°CWB
20°CDB
23°CDB
26°CDB
27°CDB
28°CDB
30°CDB
32°CDB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
FXDQ20PDVE
FXDQ20PDVET
20
1.5
1.4
1.8
1.6
2.1
1.8
2.2
1.9
2.2
1.8
2.3
1.6
2.3
1.7
FXDQ25PDVE
FXDQ25PDVET
25
1.9
1.6
2.3
1.9
2.6
2.1
2.8
2.1
2.8
2.1
2.9
2.0
3.0
1.9
FXDQ32PDVE
FXDQ32PDVET
32
2.4
1.9
2.9
2.2
3.4
2.4
3.6
2.6
3.6
2.4
3.7
2.4
3.8
2.4
FXDQ40NDVE
FXDQ40NDVET
40
3.0
2.5
3.6
2.8
4.2
3.2
4.5
3.3
4.6
3.1
4.7
3.0
4.8
3.1
FXDQ50NDVE
FXDQ50NDVET
50
3.8
3.1
4.5
3.5
5.2
3.9
5.6
4.0
5.7
3.9
5.8
3.8
5.9
3.5
FXDQ63NDVE
FXDQ63NDVET
63
4.8
3.8
5.7
4.3
6.6
4.8
7.1
4.9
7.2
4.6
7.4
4.6
7.5
4.6
TC: Total capacity: kW
SHC: Sensible heat capacity: kW
Notes:
1. These capacity tables are for use when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system
satisfies the required heat load.
2.
shows rated condition.
Summary of Contents for VRV FXDQ-PDVE
Page 1: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 201710 Engineering Data 50 60 Hz...
Page 2: ......
Page 16: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 14 FXDQ63NDVE with a drain pump 3D045496F Unit mm...
Page 18: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 16 FXDQ63NDVET without a drain pump 3D049702D Unit mm...
Page 26: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 24 FXDQ32PDVE FXDQ32PDVET 3D052157E...
Page 27: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 25 9 2 FXDQ NDVE T FXDQ40NDVE FXDQ40NDVET 3D046299G...
Page 28: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 26 FXDQ50NDVE FXDQ50NDVET 3D046300G...
Page 29: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 27 FXDQ63NDVE FXDQ63NDVET 3D046301G...
Page 31: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 29 FXDQ32PDVE FXDQ32PDVET 4D112291...
Page 33: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 31 FXDQ63NDVE FXDQ63NDVET 4D112295...
Page 36: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 34 FXDQ63NDVE FXDQ63NDVET 4D043887Q Unit mm...
Page 53: ......
Page 54: ......
Page 55: ......