19
|
Charging refrigerant
Installer and user reference guide
95
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1 – 2020.01
NOTICE
▪
Ensure that contamination of different refrigerants does not occur when using
charging equipment.
▪
Charging hoses or lines shall be as short as possible to minimise the amount of
refrigerant contained in them.
▪
Cylinders shall be kept in an appropriate position according to the instructions.
▪
Ensure that the refrigerating system is earthed prior to charging the system with
refrigerant. See
"20.2 To connect the electrical wiring to the outdoor
107].
▪
Label the system when charging is complete.
▪
Extreme care shall be taken not to overfill the refrigerating system.
NOTICE
Prior to charging the system, it shall be pressure tested with the appropriate purging
gas. The system shall be leak tested on completion of charging but prior to
commissioning. A follow up leak test shall be carried out prior to leaving the site.