21
|
Finishing the outdoor unit installation
Installer and user reference guide
113
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1 – 2020.01
b
a
c
d
f
e
a
Liquid piping
b
Gas piping
c
Vinyl tape around curves
d
Sealant
e
Vinyl tape against sharp edges
f
Stop valves
3
Insulate the liquid piping (a, see above) and the gas piping (b, see above).
4
Wind heat insulation around the curves, and then cover it with vinyl tape (c,
see above).
5
Make sure the field piping does not touch any compressor components.
6
Seal the insulation ends (sealant etc.) (d, see above).
7
Wrap the field piping with vinyl tape (e, see above) to protect it against sharp
edges
8
If the outdoor unit is installed above the indoor unit, cover the stop valves (f,
see above) with sealing material to prevent condensed water on the stop
valves from moving to the indoor unit.
NOTICE
Any exposed piping might cause condensation.
9
Reattach the service cover and the piping intake plate.
10
Seal all gaps to prevent snow and small animals from entering the system.
a
a
Seal
NOTICE
Do not block the air vents. This could affect air circulation inside the unit.