22
|
Configuration
Installer and user reference guide
127
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1 – 2020.01
[2‑31]
Power consumption limitation level (step 2) via the external control adaptor
(DTA104A61/62).
If the system needs to be running under power consumption limitation conditions
when an external signal is sent to the unit, this setting defines the level power
consumption limitation that will be applied for step 2. The level is according to the
table.
[2‑31]
Power consumption limitation (approximately)
1 (default)
40%
2
50%
3
55%
[2‑32]
Forced, all time, power consumption limitation operation (no external control
adaptor is required to perform power consumption limitation).
If the system always needs to be running under power consumption limitation
conditions, this setting activates and defines the level power consumption
limitation that will be applied continuously. The level is according to the table.
[2‑32]
Restriction reference
0 (default)
Function not active.
1
Follows [2‑30] setting.
2
Follows [2‑31] setting.
[2‑60]
Supervisor remote controller setting.
For details about the supervisor remote controller, see
19] or refer to the remote controller installation and user
reference guide.
[2‑60]
Description
0 (default)
No supervisor remote controller connected to the
system
1
Supervisor remote controller connected to system
[2‑81]
Cooling comfort setting.
This setting is used in conjunction with setting [2‑8].
[2‑81]
Cooling comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
For more information and advice about the impact of these settings, see
"22.3 Energy saving and optimum operation"
[2‑82]
Heating comfort setting.