22
|
Configuration
Installer and user reference guide
122
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1 – 2020.01
4
Push BS3 1 time; the value which is returned (depending on the actual field
situation), is the status of the setting. In the case of [2‑18], default value is "0",
which means the function is not active.
Result:
Mode 2 setting 18 is addressed and selected, return value is the
current setting situation.
5
To change the value of the setting, push BS2 till the required value appears on
the 7‑segment display indication. When achieved, define the setting value by
pushing BS3 1 time. To start operation according to the chosen setting,
confirm again by pushing BS3.
6
To quit mode 2, push BS1 2 times.
22.2.7 Mode 1: Monitoring settings
[1‑1]
Shows the status of low noise operation.
Low noise operation reduces the sound generated by the unit compared to
nominal operating conditions.
[1‑1]
Description
0
Unit is currently not operating under low noise
restrictions.
1
Unit is currently operating under low noise restrictions.
Low noise operation can be set in mode 2. There are two methods to activate low
noise operation of the outdoor unit system.
▪
The first method is to enable an automatic low noise operation during night time
by field setting. The unit will operate at the selected low noise level during the
selected time frames.
▪
The second method is to enable low noise operation based on an external input.
For this operation an optional accessory is required.
[1‑2]
Shows the status of power consumption limitation operation.
Power consumption limitation reduces the power consumption of the unit
compared to nominal operating conditions.
[1‑2]
Description
0
Unit is currently not operating under power
consumption limitations.
1
Unit is currently operating under power consumption
limitation.
Power consumption limitation can be set in mode 2. There are two methods to
activate power consumption limitation of the outdoor unit system.
▪
The first method is to enable a forced power consumption limitation by field
setting. The unit will always operate at the selected power consumption
limitation.
▪
The second method is to enable power consumption limitation based on an
external input. For this operation an optional accessory is required.
[1‑5] [1‑6]
Shows: