www.DaikinApplied.com 23
Vertical Stack WSHP • IM 986-11
Environment
This equipment is designed for indoor installation only. Shel-
tered locations such as attics, garages, etc., generally will not
provide sufficient protection against extremes in temperature
and/or humidity, and equipment performance, reliability, and
service life may be adversely affected.
CAUTION
Units must be checked for water leaks upon initial
water system start-up. Water leaks may be a result of
mishandling or damage during shipping. Failure by the
installing contractor to check for leaks upon start-up of the
water system could result in property damage.
Operating Limits
Table 10: Air limits in °F (°C)
Air Limits
Standard Range Units
Geothermal Range Units
Cooling (DB/WB)
Heating
Cooling (DB/WB)
Heating
Minimum Ambient Air
1
50°F/40°F (10°C/4°C)
50°F (10°C)
40°F/30°F (4°C/-1°C)
40°F (4°C)
Maximum Ambient Air
2
100°F/85°F (38°C/29°C)
85°F (29°C)
100°F/85°F (38°C/29°C)
85°F (29°C)
Minimum Entering Air
1
65°F/55°F (18°C/13°C)
50°F (10°C)
65°F/55°F (18°C/13°C)
50°F (10°C)
Common Design Entering Air
75°F/63°F (24°C/17°C)
70°F (21°C)
75°F/63°F (24°C/17°C)
70°F (21°C)
Maximum Entering Air
2
85°F/71°F (29°C/22°C)
80°F (27°C)
85°F/71°F (29°C/22°C)
80°F (27°C)
Minimum CFM/Ton
300
Maximum CFM/Ton
450
Table 11: Fluid limits
Fluid Limits
Standard Range Units
Geothermal Range Units
Cooling
Heating
Cooling
Heating
Minimum Entering Fluid
55°F (13°C)
55°F (13°C)
30°F (-1°C)
20°F (-6°C)
Common Design Entering Fluid
85-90°F (29-32°C)
70°F (21°C)
90°F (32°C)
35-60°F (1.5-16°C)
Maximum Entering Fluid
120°F (49°C)
90°F (32°C)
120°F (49°C)
90°F (32°C)
Minimum GPM/Ton
1.5
Nominal GPM/Ton
3.0
Maximum GPM/Ton
4.0
Notes:
1. Maximum and minimum values may not be combined.If one value is at maximum or minimum, the other two conditions may not exceed
the normal condition for standard units. Geothermal range units may combine any two maximum conditions, but not more than two, with
all other conditions being normal conditions.
2. This is not a normal or continuous operating condition. It is assumed that such a start-up is for the purpose of bringing the building space
up to occupancy temperature.
Antifreeze Correction Factors
Antifreeze % by weight
15%
25%
35%
45%
Ethanol
Cooling Capacity
0.985
–
–
–
Heating Capacity
0.9825
–
–
–
Pressure Drop
1.04
Ethylene Glycol
Cooling Capacity
0.9935
0.9895
0.985
0.981
Heating Capacity
0.9865
0.9795
0.973
0.965
Pressure Drop
1.10
1.16
1.22
1.27
Methanol
Cooling Capacity
0.985
–
–
–
Heating Capacity
0.9825
–
–
–
Pressure Drop
1.04
–
–
–
Propylene Glycol
Cooling Capacity
0.985
0.975
0.965
0.955
Heating Capacity
0.981
0.9685
0.952
0.936
Pressure Drop
1.11
1.20
1.31
1.40