P
erforManCe
Fan Speed Selector Switch
A 4-position fan speed selector switch located in the control
box allows CFM settings to be field adjustable. Fan speed
control optimizes unit fan speed based on thermostat/room
sensor inputs. The fan speed switch allows for manually setting
an optimal fan speed specific to the application requirements.
Refer to
Table 4
Figure 55: 4-position fan speed selector switch
Fan Performance for Constant Torque EC Motor (Sizes 009-012)
Table 20: Constant torque EC motor CFM values
Unit Size
Setting
Function
External Static Pressure (in-H
2
O) [Dry Coil and STD Filter) (inches of water column)
0 .00
0 .05
0 .10
0 .15
0 .20
0 .25
0 .30
0 .35
0 .40
009
4 (High)
Stage 1
430
410
390
370
350
340
320
300
280
3 (Standard)
420
400
380
360
340
320
300
270
250
2 (Medium)
350
330
310
290
270
250
230
210
190
1 (Low)
350
330
310
290
270
250
230
210
190
4 (High)
Stage 2
450
430
410
400
380
360
340
320
300
3 (Standard)
430
410
390
370
350
340
320
300
280
2 (Medium)
420
400
380
360
340
320
300
270
250
1 (Low)
350
330
310
290
270
250
230
210
190
4 (High)
Fan Only
350
330
310
290
270
250
230
210
190
3 (Standard)
350
330
310
290
270
250
230
210
190
2 (Medium)
370
340
310
280
250
220
190
160
130
1 (Low)
370
340
310
280
250
220
190
160
130
4 (High)
Hydronic
Heat
430
410
390
370
350
340
320
300
280
3 (Standard)
420
400
380
360
340
320
300
270
250
2 (Medium)
350
330
310
290
270
250
230
210
190
1 (Low)
370
340
310
280
250
220
190
160
130
012
4 (High)
Stage 1
450
430
410
390
370
340
320
300
280
3 (Standard)
420
400
380
360
340
310
290
270
250
2 (Medium)
400
370
350
330
310
290
260
240
220
1 (Low)
400
370
350
330
310
290
260
240
220
4 (High)
Stage 2
470
450
430
410
390
370
350
330
310
3 (Standard)
450
430
410
390
370
340
320
300
280
2 (Medium)
420
400
380
360
340
310
290
270
250
1 (Low)
400
370
350
330
310
290
260
240
220
4 (High)
Fan Only
400
370
350
330
310
290
260
240
220
3 (Standard)
400
370
350
330
310
290
260
240
220
2 (Medium)
360
330
300
270
240
210
180
150
120
1 (Low)
360
330
300
270
240
210
180
150
120
4 (High)
Hydronic
Heat
450
430
410
390
370
340
320
300
280
3 (Standard)
420
400
380
360
340
310
290
270
250
2 (Medium)
400
370
350
330
310
290
260
240
220
1 (Low)
360
330
300
270
240
210
180
150
120
Note:
1. EC motor is programmed to make soft starts and stops to reduce stress transmitted to the fan housing. They adjust their speed and torque to deliver constant
airflow over a wide range of external static pressure.
2. Units are shipped at setting 3 (standard). Speed adjustment is done by 4-position switch in the control box.
3. The unit is capable of high-low fan performance through the use of a 2-stage thermostat wired to specific terminals for
High-Low CFM fan performance. Standard operation with a 1-stage thermostat is indicated as stage 2 fan performance.