![Daikin UAL-A Series Engineering Data Download Page 42](http://html.mh-extra.com/html/daikin/ual-a-series/ual-a-series_engineering-data_501734042.webp)
41
Error Code
S/N
Code
Symptoms
S/N
Code
Symptoms
1
0
0#-slave communication failure
26
43
TH4 temperature sensor malfunction
2
01~14
1# ~14# slave communication failure
27
44
Header pipe water outlet temperature sensor
failure
3
16
Overload of compressor/fan in #1
28
45
TH6 temperature sensor malfunction
4
17
Overload of compressor/fan in #2
29
46
TH7 temperature sensor malfunction
5
18
Pump overload
30
47
TH8 temperature sensor malfunction
6
19
Water fl ow is too small
31
48
TH9 temperature sensor malfunction
7
20
High pressure of #1
32
49
TH10 temperature sensor malfunction
8
21
Low pressure of #1
33
50
TH11 temperature sensor malfunction
9
24
High pressure of #2
34
51
TH12 temperature sensor malfunction
10
25
Temperature of inlet/outlet water is too low
35
52
Low pressure sensor malfunction of #2
11
26
Overload of electric heater in water system
36
53
Low pressure sensor malfunction of #1
12
27
Ambient temperature is too high/low
37
54
Memory failure
13
29
Superheat of #1 is too low
38
60
No system can be started
14
31
and master machine communication failure
39
63
Fan overload failure of System 1
15
32
suction temperature #1 is too high
40
64
Fan overload failure of System 2
16
33
discharge temperature #1 is too high
41
65
Too large water inlet and outlet water
temperature difference failure
17
34
suction temperature #2 is too high
42
66
Reverse connection of water inlet and outlet
water temperature sensors
18
35
discharge temperature #2 is too high
43
67
Failure of water inlet temperature sensor of the
master machine
19
36
Low pressure of #2
44
68
Overload failure of Compressor 2 of System 1
20
37
Superheat of #2 is too low
45
69
Overload failure of Compressor 2 of System 2
21
38
Refrigerant leakage in #1
46
70
Abnormal exhaust temperature of System 1
22
39
Refrigerant leakage in #2
47
71
Abnormal exhaust temperature of System 2
23
40
TH1 temperature sensor malfunction
48
78
Communication failure of all the slave
machines
24
41
TH2 temperature sensor malfunction
49
F6
Communication failure between wired
controller and master unit
25
42
TH3 temperature sensor malfunction
50
ERRO
Dialing setting error
Error Code and Running Status
■ Characters displayed by the LED indicator are explained in the following table.
Character
Content
Character
Content
Character
Content
Character
Content
Character
Content
Character
Content
0/O
2
4
6
8
A
1
3
5
7
9
B
Character Content
Character Content
Character Content
Character Content
Character Content
Character Content
C
E
H
N
R
U
D
F
L
P
T
Y
Summary of Contents for UAL-A Series
Page 8: ...7 Dimensions Unit mm WATER IN WATER OUT UAL WATER IN WATER OUT UAL UAL ...
Page 14: ...13 Wiring Diagrams 208 230V 3Ph 60Hz ...
Page 15: ...14 ...
Page 16: ...15 ...
Page 17: ...16 460V 3Ph 60Hz ...
Page 18: ...17 ...
Page 19: ...18 380V 3Ph 60Hz ...
Page 20: ...19 ...
Page 21: ...20 ...
Page 38: ...37 220V 1Ph 60Hz Wired Controller Instruction Dimensions Controller Installation ...