![Daikin UAL-A Series Engineering Data Download Page 33](http://html.mh-extra.com/html/daikin/ual-a-series/ual-a-series_engineering-data_501734033.webp)
32
Maintenance
The unit must be checked on a routine basis to ensure performance. Routine check is the best way to reduce
downtime and waste. The following needs to be checked on a routine basis:
Items
Monthly
Quarterly
Once half a
year
Once a year
If necessary
1. Compressor
Performance appraisal; whether there is
abnormal sound
●
Whether wires are securely connected
●
Whether the working current is abnormal
(fluctuation: 10%)
▲
Discharge air temperature of the compressor
▲
Check the oil level
▲
Check the color of the lubricant
▲
2. Controller
Check parameter settings
▲
Check protective device
▲
Delay protector
▲
Phase order protector
▲
High/low pressure switch
▲
Differential water pressure switch/water flow
switch
▲
Overload protector
▲
Protector against extreme temperature of
discharged air
▲
3. Plate heat exchanger
Check the water quality
●
Clean the plate heat exchanger
▲
Seasonal protection measures
▲
(anti-freeze in winter)
4. Fin heat exchanger
Clean the fin heat exchanger
▲
5. Others
Whether the Y-shaped filter needs to be cleaned
or replaced
●
Whether bolts have loosened
●
NOTE: THE PRECEDING MAINTENANCE PLAN IS FOR REFERENCE ONLY. THE MAINTENANCE PLAN MAY VARY BASED ON REGION.
● INDICATES ITEMS TO BE CHECKED BY CUSTOMERS; ▲ INDICATES ITEMS TO BE CHECKED BY SERVICE PERSONNEL.
Summary of Contents for UAL-A Series
Page 8: ...7 Dimensions Unit mm WATER IN WATER OUT UAL WATER IN WATER OUT UAL UAL ...
Page 14: ...13 Wiring Diagrams 208 230V 3Ph 60Hz ...
Page 15: ...14 ...
Page 16: ...15 ...
Page 17: ...16 460V 3Ph 60Hz ...
Page 18: ...17 ...
Page 19: ...18 380V 3Ph 60Hz ...
Page 20: ...19 ...
Page 21: ...20 ...
Page 38: ...37 220V 1Ph 60Hz Wired Controller Instruction Dimensions Controller Installation ...