![Daikin UAL-A Series Engineering Data Download Page 22](http://html.mh-extra.com/html/daikin/ual-a-series/ual-a-series_engineering-data_501734022.webp)
21
Installation
Working Condition
Item
Contents
Power supply voltage
Rated voltage ±10%
Power supply frequency
Rated frequency ±1%
Variations between phases
Rated voltage ±2%
Air quality
Must not contain solute that can corrode copper, aluminum or iron.
Flow rate of chilled water
0.5 - 2.0m/s
Pressure of chilled water
< 0.7Mpa
Quality of chilled water
Must not contain solute that can corrode copper, iron, or welding material.
For details on the water quality requirements, see: Water Quality Requirements (page 24).
Installation site
Take anti-snow and ventilation measures as required.
Ambient temp.
Refer to the figure above.
Relative humidity
<90%
NOTES:
1. THE UNIT IS STRICTLY TESTED BEFORE DELIVERY AND CAN WORK SAFELY IN THE RATED WORKING CONDITIONS.
2. FOR THE PERFORMANCE OF THE UNIT IN DIFFERENT WORKING CONDITIONS, PLEASE REFER TO PERFORMENC CURVE.
3. THIS IS THE NORMAL OPERATING TEMPERATURE RANGE FOR THE UNIT. BEYOND THIS TEMPERATURE RANGE, THE UNIT CAN
ONLY OPERATE FOR A SHORT MOMENT BEFORE A FAILURE ALARM IS TRIGGERED.
Installation Dimensions and Environment Limits
Machine Installation Space
Units must be installed by DAIKIN service staff or by specially trained personnel.
Units must installed by following relevant national and local electric, building and environment protection standards as
well as the installation manual.
Unit: mm
Assembling Unit Modules
NOTES:
1. FOUNDATION IS CONCRETE CONSTRUCTION OR CHANNEL STRUCTURE, FOUNDATION MUST BE SMOOTH.
Summary of Contents for UAL-A Series
Page 8: ...7 Dimensions Unit mm WATER IN WATER OUT UAL WATER IN WATER OUT UAL UAL ...
Page 14: ...13 Wiring Diagrams 208 230V 3Ph 60Hz ...
Page 15: ...14 ...
Page 16: ...15 ...
Page 17: ...16 460V 3Ph 60Hz ...
Page 18: ...17 ...
Page 19: ...18 380V 3Ph 60Hz ...
Page 20: ...19 ...
Page 21: ...20 ...
Page 38: ...37 220V 1Ph 60Hz Wired Controller Instruction Dimensions Controller Installation ...