44 |
P a g e
No.
Menu
Property
21
C1/2 OffNoPressAtStartOffNormal
Check whether there is refrigerant leakage.
Check the suction and discharge pressure
sensors and its wiring.
Check the fan speed regulating governor.
22
C1/2 OffCmpCtrlrComFailOffNormal
Check whether compressor control panel and
the main controller are properly connected.
Remarks:
•
Ensure that unit is working in the designated envelope
•
Ensure water flow is the rated water flow
•
Ensure relative humidity if the unit operating environment should be 90% or
less