Alarm
Evap entering water temp sensor
and evap leaving water temp sensor
inverted
Code: UnitOffEvpWTempInvr
tdOffNormal
Category:
Critical
Trigger
Action
Unit pump down shutdown
Reset method
Manual reset
Reset
Condition
Evap Entering water temp
≥
Evap Leaving water temp
Solution
Check whether both temperature sensor condition are good
Check whether both sensors are inverted.
No
No
Yes
Yes
No
Evap LWT -Evap EWT > 1.5
o
C?
Alarm
Evap entering/leaving water
temp sensor = Alarm?
No. of running compressor ≥ 1?
Alarm:
UnitOffEvpEntWTempOffNormal /
UnitOffEvpLvgWTempFault
Yes
Confirm time = 30 sec?
Yes
No