52 |
P a g e
Event Alarm
Alarm
Evap entering water temp sensor
Faulty
Code: UnitOffEvpEntWTempO
ffNormal
Category:
Critical
Trigger
Action
Unit pump down shutdown
Reset method
Manual reset
Reset
Condition
Evap entering water temperature in operating range
Solution
Check sensor condition, wiring and connector condition.
Alarm
Unit Power Restore
Code: UnitPowerRestore
Category:
Critical
Trigger
Action
No action
Reset method
Auto reset
Reset
Condition
Evap entering water temperature in operating range
Solution
Check sensor condition, wiring and connector condition.