background image

7

(5) When hanging the indoor unit main body, be sure to 

use a level or a plastic tube with water in it to make sure 
the drain piping is set either level or slightly tilted, in 
order to ensure proper drainage.

 

(Refer to Fig. 12)

A.When the drain piping is tilted to the right, or to the right 

and back.

Place it level, or tilt it slightly to the right or the back. (1° or less.)

B.When the drain piping is tilted to the left, or to the left and 

back.

Place it level, or tilt it slightly to the left or the back. (1° or less.)

CAUTION

• Setting the unit at an angle opposite to the drain piping might 

cause a water leakage.

6.

REFRIGERANT PIPING WORK

DANGER

• Refrigerant gas may produce toxic gas if it comes in contact 

with fire such as from a fan heater, stove or cooking device. 
Exposure to this gas could cause severe injury or death.

CAUTION

• Use a pipe cutter and flare suitable for the type of refrig-

erant.

• To prevent dust, moisture or other foreign matter from infil-

trating the tube, either pinch the end or cover it with tape.

• Do not allow anything other than the designated refrig-

erant to get mixed into the refrigerant circuit, such as air, 
etc. If any refrigerant gas leaks while working on the 
unit, ventilate the room thoroughly right away.

6-1 GENERAL INSTRUCTIONS

• For refrigerant pipe of outdoor units, see the installation 

manual attached to the outdoor unit.

• Execute thermal insulation work completely on both 

sides of the gas pipe and the liquid pipe.

Otherwise, a water leakage can result sometimes.
(The temperature of the gas pipe can reach up to 
approximately 250°F, so use insulation pipe cover 
which is sufficiently resistant.)

• Also, in cases where the temperature and humidity of 

the refrigerant pipe sections might exceed 86°F or RH 
80%, reinforce the thermal insulation. (3/4 in. or thicker)

Condensate may form on the surface of the insulation 
pipe cover.

• Before refrigerant pipe work, check which type of refrig-

erant is used.

Proper operation is not possible if the types of refriger-
ant are not the same.

6-2 CONNECTING THE REFRIGERANT PIPE

• The outdoor unit is charged with refrigerant.
• Use copper alloy seamless pipes.
• Be sure to use both a spanner and torque wrench together, 

as shown in the drawing, when connecting or disconnecting 
pipes to/from the unit.

 (Refer to Fig. 13)

• Refer to “Table 2” to determine the proper tightening torque.
• Refer to “Table 2” for the dimensions of flare shape.
• When connecting the flare nut, coat the flare section (both 

inside and outside) with ester oil or ether oil, rotate three or 
four times first, then screw in.

 (Refer to Fig. 14)

CAUTION

• Be careful for oil not to adhere to any portions other than a 

flare part. If oil adhere to resin parts etc., there is a possibility 
of damaging by deterioration.

NOTE

• Use the flare nut included with the unit main body.

Table 2

CAUTION

• Overtightening may damage the flare and cause a refrigerant 

leakage.

Not recommended but in case of emergency

You must use a torque wrench, but if you are obliged to install 
the unit without a torque wrench, you may follow the installa-
tion method mentioned below.

When you keep on tightening the flare nut with a spanner, 
there is a point where the tightening torque suddenly 
increases. From that position, further tighten the flare nut 
the angle shown below :

1˚ or less

1˚ or less

1˚ or less

A

A.B

B

Fig. 12

Pipe size

(in.)

Tightening torque 

(ft. lbf)

Flare dimensions A

(in.)

Flare shape (in.)

φ

3/8

24.1–29.4

0.504–0.520

φ

5/8

45.6–55.6

0.760–0.776

Torque wrench

Flare nut

Pipe union

Spanner

Fig. 13

Fig. 14

Ester oil or ether oil.

R0.016-0.031

A

90˚± 2˚ 

45˚±2˚

Summary of Contents for SkyAir SkyAir FHQ42MVJU

Page 1: ...HQ30MVJU FHQ36MVJU FHQ42MVJU INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with the equipm...

Page 2: ...ely Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could result in severe injury or death After completin...

Page 3: ...transmitting distance can result shorter than expected in rooms with elec tronic fluorescent lamps inverter or rapid start types Install the indoor unit as far away from fluorescent lamps as possible...

Page 4: ...ammable materials are present due to the risk explosion resulting in serious injury or death WARNING If the supporting structural members are not strong enough to take the unit s weight the unit could...

Page 5: ...oles in the ceiling 3 Remove the parts from the indoor unit 3 1 Detach the suction grille Slide the locking knobs 2 on the suction grille inward direction of arrows and lift upwards Refer to Fig 1 Wit...

Page 6: ...the provided accessories and specified parts designated by our company 1 Secure the hanger brackets to the suspension bolts Refer to Fig 10 NOTE To ensure they are safely secured use the included wash...

Page 7: ...humidity of the refrigerant pipe sections might exceed 86 F or RH 80 reinforce the thermal insulation 3 4 in or thicker Condensate may form on the surface of the insulation pipe cover Before refrigera...

Page 8: ...6 1 For piping facing back Remove the rear metal plate for pipe Refer to Fig 17 The figure of the direction of back shows when both the pip ing and drain pipe are set backward When setting the piping...

Page 9: ...ly attach the metal clamp bracket inside the gray tape area on the inserted tip of the drain pipe Refer to Fig 22 Screw the screws on the metal clamp bracket until there is 5 32 in left Pay attention...

Page 10: ...upply wire To avoid short circuits in the electric parts box be sure to apply the sealing material or putty not included to the wiring hole to prevent the infiltration of water insects or other small...

Page 11: ...e to the same ground terminal Looseness in the connection may deteriorate pro tection 4 Outside of the unit keep transmission wire at least 5 in away from power supply wire The equipment may malfunc t...

Page 12: ...n manual Setting can be made by changing the Mode No FIRST CODE NO and SECOND CODE NO For setting and operation refer to the FIELD SETTING in the installation manual of the remote controller 11 1 Sett...

Page 13: ...nduct the check operation referring to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the li...

Page 14: ...s the INSPECTION TEST OPERATION button on remote controller starts flashing 2 Keep down the ON OFF button for 5 seconds or longer in the inspection mode and the above trouble history disap pears after...

Page 15: ...uction pipe temperature abnormal U2 Power source voltage malfunction Includes the defect in K1M U3 The check operation has not performed U4 UF Transmission error indoor unit outdoor unit Miswiring bet...

Page 16: ...0510 3PN06240 2E EM04A051B FS...

Reviews: