11-2 2 remote controllers control

(Controlling 1 indoor unit by 2 remote controllers)

• When using 2 remote controllers, one must be set to “MAIN” 

and the other to “SUB”.

MAIN/SUB CHANGEOVER

(1) Insert a 

 screw driver into the recess between the upper 

and lower part of remote controller and, working from the 2 
positions, pry off the upper part.
The remote controller PC board is attached to the upper 
part of remote controller.

 (Refer to Fig. 30)

(2) Turn the MAIN/SUB changeover switch on one of the 2 

remote controllers PC boards to “S”. (Leave the switch of 
the other remote controllers set to “M”.) 

(Refer to Fig. 31)

Wiring Method

(See “8. ELECTRIC WIRING WORK” and “9. WIRING EXAM-
PLE AND HOW TO SET THE REMOTE CONTROLLER” on 
page from 10 to 12.)

(3) Remove the control box lid.

(4) Add 2nd remote controller to the transmission terminal 

block (P1, P2) in the control box. (There is no polarity.) 
(Refer to Fig. 28 on page 11 and Table 4 on page 11)

11-3 COMPUTERISED CONTROL

(FORCED OFF AND ON/OFF OPERATION) 

See “FIELD SETTING” on page 12 for local settings.

(1) Wire specifications and how to perform wiring

• Connect the input from outside to terminals T1 and T2 of 

the transmission terminal block.

(2) Actuation

• The following table explains FORCED OFF and ON/OFF 

OPERATIONS in response to Input A. 

(3) How to select FORCED OFF and ON/OFF OPERATION

• Turn the power on and then use the remote controller to 

select operation.

11-4 CENTRALIZED CONTROL

• For centralized control, it is necessary to designate the group 

No. For details, refer to the manual of each optional control-
lers for centralized control.

12. TEST OPERATION 

Refer to the section of “FOR THE FOLLOWING ITEMS, 
TAKE SPECIAL CARE DURING CONSTRUCTION AND 
CHECK AFTER INSTALLATION IS FINISHED.” on page 4.

• Make sure if the service lids are closed on the indoor and out-

door units.

• After finishing the construction of refrigerant pipe, drain pipe 

and electric wire, conduct the check operation referring to the 
installation manual of the outdoor unit.

• The operation lamp of the remote controller will flash when a 

malfunction occurs. Check the malfunction code on the liquid 
crystal display to identify the point of trouble. An explanation 
of malfunction codes and the corresponding trouble is pro-
vided in the installation manual of the outdoor unit.
It any of the items in Table 6 are displayed, there may be a 
problem with the wiring or power, so check the wiring again.

Table 6

• If “U3” is lit up, the malfunction code shows the check opera-

tion has not been performed yet.

12-1 HOW TO DIAGNOSE FOR MALFUNCTION

With the power on, it is possible to monitor the type of mal-
function by looking at the malfunction code displayed in 
the remote controller.

Upper part of 
remote controller

Lower part of 
remote controller

Insert the screw driver 
here and gently work 
off the upper part of 
remote controller.

Fig. 30

S

M

S

S

M

Remote controller 
PC board

(Factory setting)

Only 1 remote 
controller needs 
to be changed if 
factory settings 
have remained 
untouched.

Fig. 31

F2

T1

T2

FORCED
OFF

Input A

Wire specification

Sheathed vinyl wire or cable (2 wires)

Gauge

AWG 18-16

Length

Max. 328 ft.

External terminal

Contact that can ensure the minimum appli-
cable load of 15 V DC, 10 mA.

FORCED OFF

ON/OFF OPERATION

Input “ON” stops operation (impossible by 
remote controllers.)

Input OFF 

→ 

ON turns 

ON unit.

Input OFF enables control by remote con-
troller.

Input ON 

→ 

OFF turns 

OFF unit.

Remote control display

Content

“ 

 ” (under 

centralized control) is lit up

• There is a short circuit at the 

FORCED OFF terminals (T

1

, T

2

)

“U4” is lit up
“UF” is lit up

• The power on the outdoor unit is off.
• The outdoor unit has not been wired 

for power supply.

• Incorrect wiring for the transmission 

wiring and / or FORCED OFF wiring.

• The transmission wiring is cut.

No display

• The power on the indoor unit is off.
• The indoor unit has not been wired 

for power supply.

• Incorrect wiring for the remote con-

troller wiring, the transmission wiring 
and / or the FORCED OFF wiring.

• The remote controller wiring is cut.

Summary of Contents for SkyAir SkyAir FHQ42MVJU

Page 1: ...HQ30MVJU FHQ36MVJU FHQ42MVJU INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with the equipm...

Page 2: ...ely Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could result in severe injury or death After completin...

Page 3: ...transmitting distance can result shorter than expected in rooms with elec tronic fluorescent lamps inverter or rapid start types Install the indoor unit as far away from fluorescent lamps as possible...

Page 4: ...ammable materials are present due to the risk explosion resulting in serious injury or death WARNING If the supporting structural members are not strong enough to take the unit s weight the unit could...

Page 5: ...oles in the ceiling 3 Remove the parts from the indoor unit 3 1 Detach the suction grille Slide the locking knobs 2 on the suction grille inward direction of arrows and lift upwards Refer to Fig 1 Wit...

Page 6: ...the provided accessories and specified parts designated by our company 1 Secure the hanger brackets to the suspension bolts Refer to Fig 10 NOTE To ensure they are safely secured use the included wash...

Page 7: ...humidity of the refrigerant pipe sections might exceed 86 F or RH 80 reinforce the thermal insulation 3 4 in or thicker Condensate may form on the surface of the insulation pipe cover Before refrigera...

Page 8: ...6 1 For piping facing back Remove the rear metal plate for pipe Refer to Fig 17 The figure of the direction of back shows when both the pip ing and drain pipe are set backward When setting the piping...

Page 9: ...ly attach the metal clamp bracket inside the gray tape area on the inserted tip of the drain pipe Refer to Fig 22 Screw the screws on the metal clamp bracket until there is 5 32 in left Pay attention...

Page 10: ...upply wire To avoid short circuits in the electric parts box be sure to apply the sealing material or putty not included to the wiring hole to prevent the infiltration of water insects or other small...

Page 11: ...e to the same ground terminal Looseness in the connection may deteriorate pro tection 4 Outside of the unit keep transmission wire at least 5 in away from power supply wire The equipment may malfunc t...

Page 12: ...n manual Setting can be made by changing the Mode No FIRST CODE NO and SECOND CODE NO For setting and operation refer to the FIELD SETTING in the installation manual of the remote controller 11 1 Sett...

Page 13: ...nduct the check operation referring to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the li...

Page 14: ...s the INSPECTION TEST OPERATION button on remote controller starts flashing 2 Keep down the ON OFF button for 5 seconds or longer in the inspection mode and the above trouble history disap pears after...

Page 15: ...uction pipe temperature abnormal U2 Power source voltage malfunction Includes the defect in K1M U3 The check operation has not performed U4 UF Transmission error indoor unit outdoor unit Miswiring bet...

Page 16: ...0510 3PN06240 2E EM04A051B FS...

Reviews: