background image

8

Table 3

After the work is finished, make sure to check that there 
is no gas leak.

6-3 BRAZING REFRIGERANT PIPING

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT 
PIPING

“Do not use flux when brazing refrigerant pipe. Therefore, use 
the phosphor copper brazing filler metal (BCuP) which does not 
require flux.”
(Flux has an extremely negative effect on refrigerant piping sys-
tems. For instance, if chlorine based flux is used, it will cause 
pipe corrosion. If the flux contains fluorine, it will damage the 
refrigerant oil.)

• Before brazing local refrigerant pipe, nitrogen gas shall be 

blown through the pipe to expel air from the pipe.
If you brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the pipe, and could 
cause system malfunction.

• When brazing the refrigerant pipe, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant pipe. Once this is done, connect 
the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 2.9 psi with a pressure-reducing 

valve if brazing while inserting nitrogen into the pipe.

(Refer to Fig. 15)

DANGER

• Use of oxygen may cause an explosion resulting in serious 

injury or death. Only use nitrogen gas.

CAUTION

• Be sure to insulate any field piping all the way to the piping 

connection inside the unit. Any exposed piping may cause 
condensate or a burn if touched.

6-4 PIPING INSULATION

• Make absolutely sure to execute thermal insulation works on 

the pipe-connecting section after checking gas leakage by 
thoroughly studying the following figure and using the insula-
tion pipe cover (6) and (7). (Fasten both ends with the clamps 
(4).) 

(Refer to Fig. 16)

• Wrap the small sealing pad (9) only around the insulation for 

the joints on the gas piping side.

 (Refer to Fig. 16)

(1) For piping facing back.

• Remove the rear metal plate for pipe.

 (Refer to Fig. 17)

• The figure of the direction of back shows when both the pip-

ing and drain pipe are set backward.
When setting the piping to face up or right, attach the rear 
metal plate for refrigerant pipe and plug a hole for drain pipe. 
(See “4 PREPARATIONS BEFORE INSTALLATION” (3-3) on 
page 6)

(2) For piping facing up.

• When setting the piping to face up, the L-shaped branch pipe 

kit sold separately is required.

• Removing the top penetration lid and use the L-shaped branch 

pipe kit sold separately to set the pipe. 

(Refer to Fig. 18, 19)

(3) For piping facing right.

• Cut out a slit hole on the decoration panel (right) and set the 

pipe.

 (Refer to Fig. 17)

Pipe size 

(in.)

Further tightening angle

Recommended arm length of tool 

(in.)

φ

3/8

60 to 90 degrees

Approx. 7 7/8

φ

5/8

30 to 60 degrees

Approx. 11 13/16

Refrigerant pipe

Part to be 
brazed

Taping

Pressure-reducing
valve

hands valve

Nitrogen

Nitrogen

Fig. 15

Insulation pipe cover for gas pipe (6)

Gas pipe

Liquid pipe

Insulation pipe cover for liquid pipe (7)

Clamp (4) (× 4)

Attach to the bottom 
(For both gas pipe and liquid pipe)

Procedure for thermal insulation of liquid-side pipe

Insulation pipe cover for 
liquid pipe (7)

Orient so that the end of 
the wrapped insulation 
material is facing up

Flare nut connection

Insulation pipe cover (main unit)

Attach to base

Main unit

Main unit

Clamp (4)

Clamp (4)

Insulation pipe cover
(Locally procured)

Procedure for thermal insulation of gas-side pipe

Insulation pipe cover
for gas pipe (6) 

Insulation pipe
cover (main unit)

Attach to base

Orient so that the end of 
the wrapped insulation 
pipe cover is facing up

Flare nut connection

Insulation pipe cover
(Locally procured)

Wind around the 
pipe, beginning at 
the base.

Small sealing
pad (9)

Fig. 16

Right-facing drain pipe

Right-facing 
refrigerant 
piping

Decoration panel (right) removable part

If only setting the drain pipe to 
face right, cut this section only.

Fig. 17

Rear-facing 
refrigerant pipe

Rear right-facing 
drain pipe

Summary of Contents for SkyAir SkyAir FHQ42MVJU

Page 1: ...HQ30MVJU FHQ36MVJU FHQ42MVJU INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with the equipm...

Page 2: ...ely Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could result in severe injury or death After completin...

Page 3: ...transmitting distance can result shorter than expected in rooms with elec tronic fluorescent lamps inverter or rapid start types Install the indoor unit as far away from fluorescent lamps as possible...

Page 4: ...ammable materials are present due to the risk explosion resulting in serious injury or death WARNING If the supporting structural members are not strong enough to take the unit s weight the unit could...

Page 5: ...oles in the ceiling 3 Remove the parts from the indoor unit 3 1 Detach the suction grille Slide the locking knobs 2 on the suction grille inward direction of arrows and lift upwards Refer to Fig 1 Wit...

Page 6: ...the provided accessories and specified parts designated by our company 1 Secure the hanger brackets to the suspension bolts Refer to Fig 10 NOTE To ensure they are safely secured use the included wash...

Page 7: ...humidity of the refrigerant pipe sections might exceed 86 F or RH 80 reinforce the thermal insulation 3 4 in or thicker Condensate may form on the surface of the insulation pipe cover Before refrigera...

Page 8: ...6 1 For piping facing back Remove the rear metal plate for pipe Refer to Fig 17 The figure of the direction of back shows when both the pip ing and drain pipe are set backward When setting the piping...

Page 9: ...ly attach the metal clamp bracket inside the gray tape area on the inserted tip of the drain pipe Refer to Fig 22 Screw the screws on the metal clamp bracket until there is 5 32 in left Pay attention...

Page 10: ...upply wire To avoid short circuits in the electric parts box be sure to apply the sealing material or putty not included to the wiring hole to prevent the infiltration of water insects or other small...

Page 11: ...e to the same ground terminal Looseness in the connection may deteriorate pro tection 4 Outside of the unit keep transmission wire at least 5 in away from power supply wire The equipment may malfunc t...

Page 12: ...n manual Setting can be made by changing the Mode No FIRST CODE NO and SECOND CODE NO For setting and operation refer to the FIELD SETTING in the installation manual of the remote controller 11 1 Sett...

Page 13: ...nduct the check operation referring to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the li...

Page 14: ...s the INSPECTION TEST OPERATION button on remote controller starts flashing 2 Keep down the ON OFF button for 5 seconds or longer in the inspection mode and the above trouble history disap pears after...

Page 15: ...uction pipe temperature abnormal U2 Power source voltage malfunction Includes the defect in K1M U3 The check operation has not performed U4 UF Transmission error indoor unit outdoor unit Miswiring bet...

Page 16: ...0510 3PN06240 2E EM04A051B FS...

Reviews: