4 Installation

Installation manual

7

RZAG71~Y1
Sky Air Alpha-series
4P485927-1C – 2019.04

1

Remove  the  knockout  hole  (a)  by  tapping  on  the  attachment
points with a flat head screwdriver and a hammer.

a

2

Remove  the  burrs,  and  paint  the  edges  and  areas  around  the
edges using repair paint to prevent rusting.

4.1.4

To prevent the outdoor unit from falling
over

In  case  the  unit  is  installed  in  places  where  strong  wind  can  tilt  the
unit, take following measure:

1

Prepare  2  cables  as  indicated  in  the  following  illustration  (field
supply).

2

Place the 2 cables over the outdoor unit.

3

Insert  a  rubber  sheet  between  the  cables  and  the  outdoor  unit
to prevent the cables from scratching the paint (field supply).

4

Attach the ends of the cables and tighten them.

4.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING

4.2.1

To connect the refrigerant piping to the
outdoor unit

Piping length.

 Keep field piping as short as possible.

Piping  protection.

  Protect  the  field  piping  against  physical

damage.

1

Do the following:

▪ Remove the service cover (a) with screw (b).
▪ Remove the piping intake plate (c) with screw (d).

c

a

b

d

2

Choose a piping route (a, b, c or d).

a

b

c

d

INFORMATION

b

b

b

b

a

a

▪ Remove  the  knockout  hole  (a)  in  the  bottom  plate  or

cover plate by tapping on the attachment points with a
flat head screwdriver and a hammer.

▪ Optionally, cut out the slits (b) with a metal saw.

NOTICE

Precautions when making knockout holes:

▪ Avoid damaging the casing and underlying piping.

▪ After  making  the  knockout  holes,  we  recommend  to

remove  the  burrs  and  paint  the  edges  and  areas
around the edges using repair paint to prevent rusting.

▪ When  passing  electrical  wiring  through  the  knockout

holes,  wrap  the  wiring  with  protective  tape  to  prevent
damage.

3

Do the following:

▪ Connect the liquid pipe (a) to the liquid stop valve.
▪ Connect the gas pipe (b) to the gas stop valve.

a

b

4

Do the following:

▪ Insulate the liquid piping (a) and the gas piping (b).
▪ Wind  heat  insulation  around  the  curves,  and  then  cover  it

with vinyl tape (c).

▪ Make  sure  the  field  piping  does  not  touch  any  compressor

components (d).

▪ Seal the insulation ends (sealant etc.) (e).

d

e

f

b

a

c

5

If  the  outdoor  unit  is  installed  above  the  indoor  unit,  cover  the
stop  valves  (f,  see  above)  with  sealing  material  to  prevent
condensed water on the stop valves from moving to the indoor
unit.

NOTICE

Any exposed piping might cause condensation.

6

Reattach the service cover and the piping intake plate.

7

Seal  all  gaps  (example:  a)  to  prevent  snow  and  small  animals
from entering the system.

Summary of Contents for SkyAir RZAG125M7V1B

Page 1: ...Installation manual Sky Air Alpha series English Installation manual Sky Air Alpha series RZAG71M7V1B RZAG100M7V1B RZAG125M7V1B RZAG140M7V1B RZAG71M7Y1B RZAG100M7Y1B RZAG125M7Y1B RZAG140M7Y1B...

Page 2: ...1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB H...

Page 3: ...onforme altera o em 10 11 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m...

Page 4: ...PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplo...

Page 5: ...2 To check the insulation resistance of the compressor 14 5 Commissioning 14 5 1 Checklist before commissioning 14 5 2 To perform a test run 14 5 3 Error codes when performing a test run 15 5 4 Dedica...

Page 6: ...d supply as follows mm 150 6 2 0 350 3 4 5 3 5 5 4 M12 a a Make sure not to cover the drain holes of the bottom plate of the unit INFORMATION The recommended height of the upper protruding part of the...

Page 7: ...b c d INFORMATION b b b b a a Remove the knockout hole a in the bottom plate or cover plate by tapping on the attachment points with a flat head screwdriver and a hammer Optionally cut out the slits...

Page 8: ...flare nut and the copper flare 1 Charge the system with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks...

Page 9: ...efrigerant circuit so the vacuuming process or recharge of refrigerant can be done properly Before vacuum drying or recharging activate field setting vacuum mode After finishing vacuum drying or recha...

Page 10: ...of twin triple and double twin 1 Determine G1 and G2 G1 m Total length of x liquid piping x 9 5 mm standard x 12 7 mm size up G2 m Total length of 6 4 mm liquid piping 2 Determine R1 and R2 If Then G...

Page 11: ...When 2 28 is reached press the BS3 button once 4 Change the setting to 1 by pressing the BS2 button once 5 Push the BS3 button once 6 When the display is not blinking anymore press the BS3 button aga...

Page 12: ...onnected to public low voltage systems with input current 16 A and 75 A per phase RZAG71 140M7Y1B Equipment complying with EN IEC 61000 3 2 European International Technical Standard setting the limits...

Page 13: ...e of the 3 possibilities a b a b a b 2 3 1 a Power supply cable b Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduits PG insertions...

Page 14: ...g field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between the outdoor unit and the indoor unit master Be...

Page 15: ...oor unit and user interface The fuse on the outdoor unit PCB has blown out E3 E4 or L8 The stop valves are closed The air inlet or air outlet is blocked E7 There is a missing phase in case of three ph...

Page 16: ...nimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of obstacle B eD Maximum distance between the unit and...

Page 17: ...e Outdoor Outdoor Indoor Indoor Upper Upper Lower Lower Fan Fan ON ON OFF OFF 2 Layout English Translation Layout Layout Front Front Back Back Position of compressor terminal Position of compressor te...

Page 18: ...t breaker 30 mA Q1E Overload protection R1 R8 A1P Y1 only Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger R5T Thermistor heat exchanger middle...

Page 19: ......

Page 20: ...4P485927 1C 2019 04 Copyright 2017 Daikin 4P485927 1 C 00000007...

Reviews: