4 Installation

Installation manual

13

RZAG71~Y1
Sky Air Alpha-series
4P485927-1C – 2019.04

c

a

d

e

1~ 50 Hz

220-240 V

3N~ 50 Hz

380-415 V

V1

Y1

L1 L2 L3

L1 L2 L3

N

b

b

a

a

a

I, II, III, IV

Pair, twin, triple, double twin

M, S

Master, slave

a

Interconnection cables

b

Power supply cable

c

Earth leakage circuit breaker

d

Fuse

e

User interface

a

71

d

c

e

100~140

d

e

c

d

f

d

c

c

f

b

a

Switch box

b

Stop valve attachment plate

c

Earth

d

Cable tie

e

Interconnection cable

f

Power supply cable

3

Fix the cables (power supply and interconnection cable) with a
cable tie to the stop valve attachment plate and route the wiring
according to the illustration above.

4

Choose  a  knockout  hole  and  remove  the  knockout  hole  by
tapping  on  the  attachment  points  with  a  flat  head  screwdriver
and a hammer.

5

Route  the  wiring  through  the  frame  and  connect  the  wiring  to
the frame at the knockout hole.

Routing through
the frame

Choose one of the 3 possibilities:

a

b

a

b

a

b

2

3

1

a

 Power supply cable

b

 Interconnection cable

Connecting to the
frame

When cables are routed from the unit, a
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.

When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.

a b c

d

e

A B

A

 Inside of the outdoor unit

B

 Outside of the outdoor unit

a

 Wire

b

 Bush

c

 Nut

d

 Frame

e

 Hose

NOTICE

Precautions when making knockout holes:

▪ Avoid damaging the casing and underlying piping.

▪ After  making  the  knockout  holes,  we  recommend  to

remove  the  burrs  and  paint  the  edges  and  areas
around the edges using repair paint to prevent rusting.

▪ When  passing  electrical  wiring  through  the  knockout

holes,  wrap  the  wiring  with  protective  tape  to  prevent
damage.

6

Reattach the service cover.

7

Connect an earth leakage circuit breaker and fuse to the power
supply line.

4.6

Finishing the outdoor unit
installation

4.6.1

To finish the outdoor unit installation

1

Insulate and fix the refrigerant piping and interconnection cable
as follows:

Summary of Contents for SkyAir RZAG125M7V1B

Page 1: ...Installation manual Sky Air Alpha series English Installation manual Sky Air Alpha series RZAG71M7V1B RZAG100M7V1B RZAG125M7V1B RZAG140M7V1B RZAG71M7Y1B RZAG100M7Y1B RZAG125M7Y1B RZAG140M7Y1B...

Page 2: ...1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB H...

Page 3: ...onforme altera o em 10 11 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m...

Page 4: ...PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplo...

Page 5: ...2 To check the insulation resistance of the compressor 14 5 Commissioning 14 5 1 Checklist before commissioning 14 5 2 To perform a test run 14 5 3 Error codes when performing a test run 15 5 4 Dedica...

Page 6: ...d supply as follows mm 150 6 2 0 350 3 4 5 3 5 5 4 M12 a a Make sure not to cover the drain holes of the bottom plate of the unit INFORMATION The recommended height of the upper protruding part of the...

Page 7: ...b c d INFORMATION b b b b a a Remove the knockout hole a in the bottom plate or cover plate by tapping on the attachment points with a flat head screwdriver and a hammer Optionally cut out the slits...

Page 8: ...flare nut and the copper flare 1 Charge the system with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks...

Page 9: ...efrigerant circuit so the vacuuming process or recharge of refrigerant can be done properly Before vacuum drying or recharging activate field setting vacuum mode After finishing vacuum drying or recha...

Page 10: ...of twin triple and double twin 1 Determine G1 and G2 G1 m Total length of x liquid piping x 9 5 mm standard x 12 7 mm size up G2 m Total length of 6 4 mm liquid piping 2 Determine R1 and R2 If Then G...

Page 11: ...When 2 28 is reached press the BS3 button once 4 Change the setting to 1 by pressing the BS2 button once 5 Push the BS3 button once 6 When the display is not blinking anymore press the BS3 button aga...

Page 12: ...onnected to public low voltage systems with input current 16 A and 75 A per phase RZAG71 140M7Y1B Equipment complying with EN IEC 61000 3 2 European International Technical Standard setting the limits...

Page 13: ...e of the 3 possibilities a b a b a b 2 3 1 a Power supply cable b Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduits PG insertions...

Page 14: ...g field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between the outdoor unit and the indoor unit master Be...

Page 15: ...oor unit and user interface The fuse on the outdoor unit PCB has blown out E3 E4 or L8 The stop valves are closed The air inlet or air outlet is blocked E7 There is a missing phase in case of three ph...

Page 16: ...nimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of obstacle B eD Maximum distance between the unit and...

Page 17: ...e Outdoor Outdoor Indoor Indoor Upper Upper Lower Lower Fan Fan ON ON OFF OFF 2 Layout English Translation Layout Layout Front Front Back Back Position of compressor terminal Position of compressor te...

Page 18: ...t breaker 30 mA Q1E Overload protection R1 R8 A1P Y1 only Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger R5T Thermistor heat exchanger middle...

Page 19: ......

Page 20: ...4P485927 1C 2019 04 Copyright 2017 Daikin 4P485927 1 C 00000007...

Reviews: