4 Installation

Installation manual

12

RZAG71~Y1

Sky Air Alpha-series

4P485927-1C – 2019.04

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

Use  the  GWP  value  mentioned  on  the  refrigerant  charge
label.  That  GWP  is  based  on  the  current  legislation  on
fluorinated greenhouse gases. The GWP mentioned in the
manual might be outdated.

2

Fix  the  label  on  the  inside  of  the  outdoor  unit.  There  is  a
dedicated place for it on the wiring diagram label.

4.5

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

CAUTION

For  use  of  units  in  applications  with  temperature  alarm
settings  it  is  recommended  to  foresee  a  delay  of  10
minutes  for  signalling  the  alarm  in  case  the  alarm
temperature  is  exceeded.  The  unit  may  stop  for  several
minutes during normal operation for "defrosting the unit", or
when in "thermostat stop" operation.

4.5.1

About electrical compliance

RZAG71~140M7V1B

Equipment  complying  with  EN/IEC  61000‑3‑12  (European/
International  Technical  Standard  setting  the  limits  for  harmonic
currents  produced  by  equipment  connected  to  public  low-voltage
systems with input current >16 A and ≤75 A per phase.).

RZAG71~140M7Y1B

Equipment 

complying 

with 

EN/IEC 

61000‑3‑2 

(European/

International  Technical  Standard  setting  the  limits  for  harmonic
currents  produced  by  equipment  connected  to  public  low-voltage
systems with input current ≤16 A per phase.).

4.5.2

Guidelines when connecting the electrical
wiring

Tightening torques

Item

Tightening torque (N•m)

M4 (X1M)

1.2~1.8

M4 (earth)

1.2~1.4

M5 (X1M)

2.0~3.0

M5 (earth)

2.4~2.9

NOTICE

If  limited  space  is  available  at  the  wire  terminal,  use
bended crimp-style ring terminals.

4.5.3

Specifications of standard wiring components

Component

V1

Y1

71

100~140

71

100

125

140

Power supply cable MCA

(a)

18.8 A

28.5 A

12.3 A

15.9 A

15.7 A

15.4  A

Voltage range

220~240 V

380~415 V

Phase

1~

3N~

Frequency

50 Hz

Wire sizes

Must comply with applicable legislation

Interconnection cables

Minimum cable section of 2.5 mm² and applicable for 230 V

Recommended field fuse

20 A

32 A

16 A

Earth leakage circuit breaker

Must comply with applicable legislation

(a)

MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of combination with indoor units for exact values).

4.5.4

To connect the electrical wiring on the
outdoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

1

Remove the service cover.

2

Connect  the  interconnection  cables  and  power  supply  as
follows:

Summary of Contents for SkyAir RZAG125M7V1B

Page 1: ...Installation manual Sky Air Alpha series English Installation manual Sky Air Alpha series RZAG71M7V1B RZAG100M7V1B RZAG125M7V1B RZAG140M7V1B RZAG71M7Y1B RZAG100M7Y1B RZAG125M7Y1B RZAG140M7Y1B...

Page 2: ...1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB H...

Page 3: ...onforme altera o em 10 11 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m...

Page 4: ...PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplo...

Page 5: ...2 To check the insulation resistance of the compressor 14 5 Commissioning 14 5 1 Checklist before commissioning 14 5 2 To perform a test run 14 5 3 Error codes when performing a test run 15 5 4 Dedica...

Page 6: ...d supply as follows mm 150 6 2 0 350 3 4 5 3 5 5 4 M12 a a Make sure not to cover the drain holes of the bottom plate of the unit INFORMATION The recommended height of the upper protruding part of the...

Page 7: ...b c d INFORMATION b b b b a a Remove the knockout hole a in the bottom plate or cover plate by tapping on the attachment points with a flat head screwdriver and a hammer Optionally cut out the slits...

Page 8: ...flare nut and the copper flare 1 Charge the system with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks...

Page 9: ...efrigerant circuit so the vacuuming process or recharge of refrigerant can be done properly Before vacuum drying or recharging activate field setting vacuum mode After finishing vacuum drying or recha...

Page 10: ...of twin triple and double twin 1 Determine G1 and G2 G1 m Total length of x liquid piping x 9 5 mm standard x 12 7 mm size up G2 m Total length of 6 4 mm liquid piping 2 Determine R1 and R2 If Then G...

Page 11: ...When 2 28 is reached press the BS3 button once 4 Change the setting to 1 by pressing the BS2 button once 5 Push the BS3 button once 6 When the display is not blinking anymore press the BS3 button aga...

Page 12: ...onnected to public low voltage systems with input current 16 A and 75 A per phase RZAG71 140M7Y1B Equipment complying with EN IEC 61000 3 2 European International Technical Standard setting the limits...

Page 13: ...e of the 3 possibilities a b a b a b 2 3 1 a Power supply cable b Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduits PG insertions...

Page 14: ...g field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between the outdoor unit and the indoor unit master Be...

Page 15: ...oor unit and user interface The fuse on the outdoor unit PCB has blown out E3 E4 or L8 The stop valves are closed The air inlet or air outlet is blocked E7 There is a missing phase in case of three ph...

Page 16: ...nimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of obstacle B eD Maximum distance between the unit and...

Page 17: ...e Outdoor Outdoor Indoor Indoor Upper Upper Lower Lower Fan Fan ON ON OFF OFF 2 Layout English Translation Layout Layout Front Front Back Back Position of compressor terminal Position of compressor te...

Page 18: ...t breaker 30 mA Q1E Overload protection R1 R8 A1P Y1 only Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger R5T Thermistor heat exchanger middle...

Page 19: ......

Page 20: ...4P485927 1C 2019 04 Copyright 2017 Daikin 4P485927 1 C 00000007...

Reviews: