Daikin SkyAir FTQ18TAVJUA Installation Manual Download Page 4

4

English

(d)

Where  flammable  gas  may  leak,  where  there  is

carbon fiber, or ignitable dust suspension in the
air, or where volatile flammables such as thinner
or gasoline are handled. Operating the unit in such
conditions can cause a fire.

Take adequate measures to prevent the outside unit from
being used as a shelter by small animals. Small animals
making  contact  with  electrical  parts  can  cause
malfunctions,  smoke,  or  fire.  Instruct  the  customer  to
keep the area around the unit clean.

Install the power supply and control wires for the indoor
and outdoor units at least 3.5 feet away from televisions
or  radios  to  prevent  image  interference  or  noise.
Depending  on  the  radio  waves,  a  distance  of  3.5  feet
may not be sufficient to eliminate the noise.

Dismantling the unit, treatment of the refrigerant, oil and
additional  parts  must  be  done  in  accordance  with  the
relevant local, state, and national regulations.

Do  not  use  the  following  tools  that  are  used  with
conventional refrigerants: gauge manifold, charge hose,
gas leak detector, reverse flow check valve, refrigerant
charge  base,  vacuum  gauge,  or  refrigerant  recovery
equipment.

If  the  conventional  refrigerant  and  refrigerator  oil  are
mixed in R-410A, the refrigerant may deteriorate.

This air conditioner or heat pump is an appliance that
should not be accessible to the general public.

As design pressure is 450 psi, the wall thickness of field-
installed pipes should be selected in accordance with
the relevant local, state, and national regulations.

2.

 BEFORE INSTALLATION

Entrust  installation  to  the  place  of  purchase  or  a  qualified
serviceman. Improper installation could lead to leaks and, in
worse cases, electric shock or fire.

Use of unspecified parts could lead to the unit failing, leaks
and, in worse cases, electric shock or fire.

Be sure to read this manual before installing the indoor unit.

Be sure to mount an air filter (part to be procured in the field)
in the suction air passage in order to prevent water leaking,
etc.

The accessories needed for installation must be retained in
your  custody  until  the  installation  work  is  completed.  Do
not discard them.

1.

Decide upon a line of transport.

2.

Leave  the  unit  inside  its  packaging  while  moving,  until
reaching  the  installation  site.  Where  unpacking  is
unavoidable, use a sling of soft material or protective plates
together  with  a  rope  when  lifting,  to  avoid  damage  or
scratches to the unit.

Be sure to check the type of R-410A refrigerant to be used
before installing the unit.

(Using an incorrect refrigerant will prevent normal operation
of the unit.)

For  the  installation  of  an  outdoor  unit,  refer  to  the  installation
manual attached to the outdoor unit.

2.1

 PRECAUTIONS

Be sure to instruct customers how to properly operate the
unit  (operating  different  functions,  and  adjusting  the
temperature) by having them carry out operations themselves
while looking at the operation manual.

Do not install in locations where the air contains high levels
of  salt  such  as  that  near  the  ocean  and  where  voltage
fluctuates greatly such as that in factories, or in vehicles or
vessels.

2.2

 OPTIONAL ACCESSORIES

This indoor unit requires one of the operation remote controls
listed below.

Wired type

BRC1E73, BRC2A71

Remote Controller

FOR  THE  FOLLOWING  ITEMS,  TAKE  SPECIAL  CARE
DURING  CONSTRUCTION  AND  CHECK  AFTER
INSTALLATION IS FINISHED.

ITEMS TO BE CHECKED AFTER COMPLETION OF WORK

Summary of Contents for SkyAir FTQ18TAVJUA

Page 1: ...English Fran ais Espa ol ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTU...

Page 2: ...llation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation...

Page 3: ...mmediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise water leakage may occur Do not touch the refrigerant pipes during and immediately after op...

Page 4: ...serviceman Improper installation could lead to leaks and in worse cases electric shock or fire Use of unspecified parts could lead to the unit failing leaks and in worse cases electric shock or fire B...

Page 5: ...tion site where the following conditions are fulfilled and meets with your customer s approval Where optimum air distribution can be ensured Where nothing blocks air passage Where condensate can be pr...

Page 6: ...L LEFT INSTALLATION No field modifications are permissible for this application Refer to Figure 7 and 8 for the location of the components referenced in the following steps Drain port labeled B in Fig...

Page 7: ...ew Side view Screw Front view Side view mount mount NOTE DO NOT USE MANIFOLDS OR FLOWRATOR TO PULL THE COIL ASSEMBLY OUT FAILURE TO DO SO MAY RESULT IN BRAZE JOINT DAMAGE AND LEAKS 3 Slide the coil as...

Page 8: ...ure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Blower Access Panel Coil Access Panel Tubing Panel UV Knockout Filter Access Panel NOTE If removing only the coil acce...

Page 9: ...nt piping according to the installation environment If the temperature or humidity in the product installation location might reach 86 F or 80 respectively Condensation may form on the surface of the...

Page 10: ...g connections referring to Fig 13 Do not leave a gap Gas piping Piping heat insulation material Liquid piping Air handler Figure 13 Be sure to insulate any field piping all the way to the piping conne...

Page 11: ...roper drainage Some installation may require a field fabricated or field supplied secondary drain pan under the coil cabinet enclosure The installation must include a P style trap that is located as c...

Page 12: ...rmed by an authorized electrician Install a wiring interrupter or ground fault circuit interrupter for the power wiring To avoid short circuiting the power supply wire be sure to use insulated termina...

Page 13: ...r wire connection from the 240V terminal to the 208V terminal on both transformers 8 4 ELECTRICAL CHARACTERISTICS Hz Volts MCA MOP HP FLA Cooling Heating 60 208 230V 4 9 15 1 2 3 9 215 215 60 208 230V...

Page 14: ...fore installing the Heat Kit uninstall the transformer sub assembly Figure 19 Make sure to unplug 12 pin connector before uninstalling the transformer sub assembly Follow the Heat Kit Installation Man...

Page 15: ...RECAUTIONS Daisy chain wiring is needed when using group control and 2 remote controllers at the same time Connect the indoor unit at the end of the crossover wire P1 P2 to remote controller 2 SUB Fig...

Page 16: ...settings may have to be performed using the remote controller depending on the type of installation 1 Make sure the electric component box covers are closed on the indoor and outdoor units 2 Dependin...

Page 17: ...gging and also the time that is set 01 02 0 low high 10000 5000 ON OFF Mode No 10 20 FIRST CODE NO SECOND CODE NO Filter dirt 1 low high 3 Displayed time units hours Filter sign display 2500 1250 9 4...

Page 18: ...CFM can be estimated from the TR formula above See Specification Sheet and or Service Manual for more information 11 21 3 XX XX 01 02 07 08 Heater Operation Electric Heater with Heat Pump not allowed...

Page 19: ...XX Choose dry mode settings as per following table XX 01 02 DRY mode Set Point Room Temperature Set Point became same as cooling mode set point Mode No 14 24 First Code No 5 Second Code No XX 10 ACCES...

Page 20: ...gs 11 TEST RUN Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the...

Page 21: ...R GREEN WH WHITE PU PURPLE LOW VOLTAGE LOW VOLTAGE FIELD HIGH VOLTAGE HIGH VOLTAGE FIELD JUNCTION TERMINAL PLUG CONNECTION EQUIPMENT GND FIELD GROUND 0140A00500 A X1A X3A X38A BS1 X12A X13A HAP X8A TH...

Page 22: ...22 English THIS PAGE LEFT INTENTIONALLY BLANK...

Page 23: ...23 English THIS PAGE LEFT INTENTIONALLY BLANK...

Page 24: ...perly maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in you...

Reviews: