Daikin SkyAir FTQ18TAVJUA Installation Manual Download Page 18

18

English

For installations not indicated above the following formula

is to be used:

TR = (kW x 3412) x (Voltage Correction) / (1.08 x CFM)

Where:

TR

= Temperature Rise

kW

= Heater Kit Actual kW

3412

= Btu per kW

VC*

= .96 (230 Supply Volts)

= .92 (220 Supply Volts)

= .87 (208 Supply Volts)

1.08

= Constant

CFM

= Measured Airflow

*VC (Voltage Correction)

NOTE: 

The Temperature Rise Calculations can also be used

to estimate the air handler airflow delivery. When using these
tables for this purpose set the room thermostat to maximum
heat and allow the system to reach steady state conditions.
Insert two thermometers, one in the return air and one in the
supply air. The temperature rise is the supply air temperature
minus the return air temperature. Using the temperature rise

calculated, CFM can be estimated from the TR formula above.

See  Specification  Sheet  and/or  Service  Manual  for  more

information.

11(21)-3-XX

XX

01 (*)

02

07

08

Heater Operation

Electric 

Heater 

with Heat 
Pump not 

allowed

Electric 

Heater 

with Heat 

Pump 

allowed

Electric 

Heater 

with Heat 
Pump not 

allowed

Electric 

Heater 

with Heat 

Pump 

allowed

Electric Heater run 
for Defrost/oil 
return operation

Not 

Allowed

Not 

allowed

Allowed

Allowed

*Factory Set

Electric Heater Setting

Mode No. 11(21)

First Code No. 3

Second Code No. XX

No Heat Kit

3

5

6

8

10

15

19

01*

02

03

04

05

06

07

08

FTQ18TAVJUA

X

X

X

X

X

X

FTQ18TAVJUD

X

X

X

X

X

X

FTQ24TAVJUA

X

X

X

X

X

X

FTQ24TAVJUD

X

X

X

X

X

X

FTQ30TAVJUA

X

X

X

X

X

X

FTQ30TAVJUD

X

X

X

X

X

X

FTQ36TAVJUA

X

X

X

X

X

X

FTQ36TAVJUD

X

X

X

X

X

X

FTQ42TAVJUA

X

X

X

X

X

X

X

FTQ42TAVJUD

X

X

X

X

X

X

X

FTQ48TAVJUA

X

X

X

X

X

X

X

FTQ48TAVJUD

X

X

X

X

X

X

X

*

Factory Set

X

Available

Not Available

HEATER (kW)

Second Code No.

Model

Mode No.

First Code No.

11(21)

5

Summary of Contents for SkyAir FTQ18TAVJUA

Page 1: ...English Fran ais Espa ol ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTU...

Page 2: ...llation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation...

Page 3: ...mmediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise water leakage may occur Do not touch the refrigerant pipes during and immediately after op...

Page 4: ...serviceman Improper installation could lead to leaks and in worse cases electric shock or fire Use of unspecified parts could lead to the unit failing leaks and in worse cases electric shock or fire B...

Page 5: ...tion site where the following conditions are fulfilled and meets with your customer s approval Where optimum air distribution can be ensured Where nothing blocks air passage Where condensate can be pr...

Page 6: ...L LEFT INSTALLATION No field modifications are permissible for this application Refer to Figure 7 and 8 for the location of the components referenced in the following steps Drain port labeled B in Fig...

Page 7: ...ew Side view Screw Front view Side view mount mount NOTE DO NOT USE MANIFOLDS OR FLOWRATOR TO PULL THE COIL ASSEMBLY OUT FAILURE TO DO SO MAY RESULT IN BRAZE JOINT DAMAGE AND LEAKS 3 Slide the coil as...

Page 8: ...ure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Blower Access Panel Coil Access Panel Tubing Panel UV Knockout Filter Access Panel NOTE If removing only the coil acce...

Page 9: ...nt piping according to the installation environment If the temperature or humidity in the product installation location might reach 86 F or 80 respectively Condensation may form on the surface of the...

Page 10: ...g connections referring to Fig 13 Do not leave a gap Gas piping Piping heat insulation material Liquid piping Air handler Figure 13 Be sure to insulate any field piping all the way to the piping conne...

Page 11: ...roper drainage Some installation may require a field fabricated or field supplied secondary drain pan under the coil cabinet enclosure The installation must include a P style trap that is located as c...

Page 12: ...rmed by an authorized electrician Install a wiring interrupter or ground fault circuit interrupter for the power wiring To avoid short circuiting the power supply wire be sure to use insulated termina...

Page 13: ...r wire connection from the 240V terminal to the 208V terminal on both transformers 8 4 ELECTRICAL CHARACTERISTICS Hz Volts MCA MOP HP FLA Cooling Heating 60 208 230V 4 9 15 1 2 3 9 215 215 60 208 230V...

Page 14: ...fore installing the Heat Kit uninstall the transformer sub assembly Figure 19 Make sure to unplug 12 pin connector before uninstalling the transformer sub assembly Follow the Heat Kit Installation Man...

Page 15: ...RECAUTIONS Daisy chain wiring is needed when using group control and 2 remote controllers at the same time Connect the indoor unit at the end of the crossover wire P1 P2 to remote controller 2 SUB Fig...

Page 16: ...settings may have to be performed using the remote controller depending on the type of installation 1 Make sure the electric component box covers are closed on the indoor and outdoor units 2 Dependin...

Page 17: ...gging and also the time that is set 01 02 0 low high 10000 5000 ON OFF Mode No 10 20 FIRST CODE NO SECOND CODE NO Filter dirt 1 low high 3 Displayed time units hours Filter sign display 2500 1250 9 4...

Page 18: ...CFM can be estimated from the TR formula above See Specification Sheet and or Service Manual for more information 11 21 3 XX XX 01 02 07 08 Heater Operation Electric Heater with Heat Pump not allowed...

Page 19: ...XX Choose dry mode settings as per following table XX 01 02 DRY mode Set Point Room Temperature Set Point became same as cooling mode set point Mode No 14 24 First Code No 5 Second Code No XX 10 ACCES...

Page 20: ...gs 11 TEST RUN Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the...

Page 21: ...R GREEN WH WHITE PU PURPLE LOW VOLTAGE LOW VOLTAGE FIELD HIGH VOLTAGE HIGH VOLTAGE FIELD JUNCTION TERMINAL PLUG CONNECTION EQUIPMENT GND FIELD GROUND 0140A00500 A X1A X3A X38A BS1 X12A X13A HAP X8A TH...

Page 22: ...22 English THIS PAGE LEFT INTENTIONALLY BLANK...

Page 23: ...23 English THIS PAGE LEFT INTENTIONALLY BLANK...

Page 24: ...perly maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in you...

Reviews: