Daikin SkyAir FTQ18TAVJUA Installation Manual Download Page 19

19

English

9.5.1

ELECTRIC HEATER ON/OFF

TEMPERATURE SETTING

When an auxiliary heater is installed and controlled by the indoor unit,
the  heater  ON/OFF  temperatures,  Ton  and  Toff,  can  be  selected
individually by switching the 1st code and 2nd code according 

to 

the

following table.

Heater
2  Stage

nd

Heater
1  Stage

st

Heat Pump

ON

ON

ON

OFF

OFF

OFF

TEMPERATURE

1.8°F

1.8°F

Toff + S*

Ton + S*

SP (Set Point)

*“

S” Value varies automatically based on the room temperature trend

ELECTRIC HEATER & HEAT PUMP OPERATION MODE

Figure 25

ON

OFF

SP (Set Point)

Heater
2

nd

Stage

ON

OFF

1.8

F

1.8

F

Ton + S*

Heater
1

st

Stage

TEMPERATURE

*‘‘S” Value varies automatically based on the room temperature trend

ELECTRIC HEATER OPERATION MODE

Figure 26

Perform on-site setting using the remote controller.

Temperature difference must be 3.6ºF or more between “Ton”
and “Toff” to activate setting(s).

°F (°C)

01*

02

03

04

05

06

Ton

1

-7.2

(-4.0)

-6.3

(-3.5)

-5.4

(-3.0)

-4.5

(-2.5)

-3.6

(-2.0)

-2.7

(-1.5)

Toff

2

-3.6

(-2.0)

-2.7

(-1.5)

-1.8

(-1.0)

-0.9

(-0.5)

0

(0)

0.9

(0.5)

SYMBOL

MODE

NO.

FIRST

CODE

SECONE CODE NO.

11(21)

*Factory Set

9.6

DRY MODE 2.0

14(24)-5-XX

Choose dry mode settings as per following table:

XX

01 (*)

02

DRY

mode

Set Point = 

Room 

Temperature

Set Point 

became same 

as cooling 

mode set point

Mode No. 14(24)

First Code No. 5

Second Code No. XX

10.

 ACCESSORIES

1.

Installation of the humidifier, economizer and air purifier (UV
lamp)

Humidifier,  economizer  (11.5VA  each  terminal)  and  air
purifier  (UV  lamp)  are  sold  separately.  For  the  method  of
installation, refer to the manual provided with each optional
product.

If the unit is installed with an electric heater, install the optional
product at a location where it is not exposed directly to the
heat  from  the  electric  heater.  Direct  exposure  to  heat  can
result in an equipment malfunction or fire.

2.

Connect the wires.

Run the wires through knockout hole.

Connect the wires to the terminal block of the product.  Refer
to wiring diagram inside the unit for wire connections.

3.

On-site setting of air purifier/humidifier.

Terminal Name 

Input/output signal

CONTROL ON/OFF

Outputs: indoor unit ON
 (AC 24V) 11.5VA or less

ECONOMIZER 2

Output: indoor unit cooling 
THERMO ON (AC 24V) 11.5VA or less

ECONOMIZER 1

Receives input: Economizer operation ON (Dry 
contact)

HUMIDIFIER

Receives input: Humidifier operation ON (Dry 
contact)

AIR CLEANER

Receives input: Air purifier operation ON (Dry 
contact)

Summary of Contents for SkyAir FTQ18TAVJUA

Page 1: ...English Fran ais Espa ol ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTU...

Page 2: ...llation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation...

Page 3: ...mmediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise water leakage may occur Do not touch the refrigerant pipes during and immediately after op...

Page 4: ...serviceman Improper installation could lead to leaks and in worse cases electric shock or fire Use of unspecified parts could lead to the unit failing leaks and in worse cases electric shock or fire B...

Page 5: ...tion site where the following conditions are fulfilled and meets with your customer s approval Where optimum air distribution can be ensured Where nothing blocks air passage Where condensate can be pr...

Page 6: ...L LEFT INSTALLATION No field modifications are permissible for this application Refer to Figure 7 and 8 for the location of the components referenced in the following steps Drain port labeled B in Fig...

Page 7: ...ew Side view Screw Front view Side view mount mount NOTE DO NOT USE MANIFOLDS OR FLOWRATOR TO PULL THE COIL ASSEMBLY OUT FAILURE TO DO SO MAY RESULT IN BRAZE JOINT DAMAGE AND LEAKS 3 Slide the coil as...

Page 8: ...ure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Blower Access Panel Coil Access Panel Tubing Panel UV Knockout Filter Access Panel NOTE If removing only the coil acce...

Page 9: ...nt piping according to the installation environment If the temperature or humidity in the product installation location might reach 86 F or 80 respectively Condensation may form on the surface of the...

Page 10: ...g connections referring to Fig 13 Do not leave a gap Gas piping Piping heat insulation material Liquid piping Air handler Figure 13 Be sure to insulate any field piping all the way to the piping conne...

Page 11: ...roper drainage Some installation may require a field fabricated or field supplied secondary drain pan under the coil cabinet enclosure The installation must include a P style trap that is located as c...

Page 12: ...rmed by an authorized electrician Install a wiring interrupter or ground fault circuit interrupter for the power wiring To avoid short circuiting the power supply wire be sure to use insulated termina...

Page 13: ...r wire connection from the 240V terminal to the 208V terminal on both transformers 8 4 ELECTRICAL CHARACTERISTICS Hz Volts MCA MOP HP FLA Cooling Heating 60 208 230V 4 9 15 1 2 3 9 215 215 60 208 230V...

Page 14: ...fore installing the Heat Kit uninstall the transformer sub assembly Figure 19 Make sure to unplug 12 pin connector before uninstalling the transformer sub assembly Follow the Heat Kit Installation Man...

Page 15: ...RECAUTIONS Daisy chain wiring is needed when using group control and 2 remote controllers at the same time Connect the indoor unit at the end of the crossover wire P1 P2 to remote controller 2 SUB Fig...

Page 16: ...settings may have to be performed using the remote controller depending on the type of installation 1 Make sure the electric component box covers are closed on the indoor and outdoor units 2 Dependin...

Page 17: ...gging and also the time that is set 01 02 0 low high 10000 5000 ON OFF Mode No 10 20 FIRST CODE NO SECOND CODE NO Filter dirt 1 low high 3 Displayed time units hours Filter sign display 2500 1250 9 4...

Page 18: ...CFM can be estimated from the TR formula above See Specification Sheet and or Service Manual for more information 11 21 3 XX XX 01 02 07 08 Heater Operation Electric Heater with Heat Pump not allowed...

Page 19: ...XX Choose dry mode settings as per following table XX 01 02 DRY mode Set Point Room Temperature Set Point became same as cooling mode set point Mode No 14 24 First Code No 5 Second Code No XX 10 ACCES...

Page 20: ...gs 11 TEST RUN Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the...

Page 21: ...R GREEN WH WHITE PU PURPLE LOW VOLTAGE LOW VOLTAGE FIELD HIGH VOLTAGE HIGH VOLTAGE FIELD JUNCTION TERMINAL PLUG CONNECTION EQUIPMENT GND FIELD GROUND 0140A00500 A X1A X3A X38A BS1 X12A X13A HAP X8A TH...

Page 22: ...22 English THIS PAGE LEFT INTENTIONALLY BLANK...

Page 23: ...23 English THIS PAGE LEFT INTENTIONALLY BLANK...

Page 24: ...perly maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in you...

Reviews: