Installation

Installer reference guide

22

RZAG71~Y1

Sky Air Alpha-series

4P573381-1 – 2019.04

If  pump  down  is  needed  in  case  of  dismantling  or  relocating  the
system, see 

"11.3 To pump down" on page 29

 for more details.

6.6.6

Completely recharging refrigerant

To determine the complete recharge amount

To determine the complete recharge amount (kg) (in case of
standard liquid pipe size)

Model

Length (m)

(a)

3~40 40~50 50~55 55~60 60~70 70~80 80~85

RZAG71

3.2

3.55

3.75

RZAG100

3.2

3.55

3.9

4.25

4.6

4.75

RZAG125-140

3.7

4.05

4.4

4.75

5.1

5.25

(a)

Length=L1 (pair); L1+L2 (twin, triple); L1+L2+L4 (double
twin)

To determine the complete recharge amount (kg) (in case of
size‑up liquid pipe size)

Model

Length (m)

(a)

3~15

15~20

20~25

25~30

30~35

RZAG71

3.2

3.55

3.9

RZAG100

3.2

3.55

3.9

4.25

4.6

140

3.7

4.05

4.4

4.75

5.1

(a)

Length=L1 (pair); L1+L2 (twin, triple); L1+L2+L4 (double
twin)

To determine the complete recharge amount (kg) (in case of
size‑down liquid pipe size)

Model

Length (m)

(a)

3~10

100

3.2

140

3.7

(a)

Length=L1 (pair); L1+L2 (twin, triple); L1+L2+L4 (double
twin)

To activate/deactivate the vacuum mode field
setting

Description

To  perform  vacuum  drying  or  a  complete  recharge  of  the  outdoor
unit’s  internal  refrigerant  piping  it  is  necessary  to  activate  the
vacuum  mode  which  will  open  required  valves  in  the  refrigerant
circuit  so  the  vacuuming  process  or  recharge  of  refrigerant  can  be
done properly.

To activate vacuum mode:

Activating  the  vacuum  mode  is  done  by  operating  the  push  buttons
BS* on the PCB (A1P) and reading the feedback from the 7‑segment
displays.

Operate the switches and push buttons with an insulated stick (such
as a closed ball-point pen) to avoid touching of live parts.

1

When  the  unit  is  powered  on  and  not  running,  hold  down  the
BS1 pushbutton for 5 seconds.

Result: 

You will reach the setting mode, the 7 segment display

will show '2 0 0'.

2

Press the BS2 button until you reach page 

2–17

.

3

When 

2–17

 is reached, press the BS3 button once.

4

Change the setting to '

2

' by pressing the BS2 button once .

5

Push the BS3 button once.

6

When the display is not blinking anymore, press the BS3 button
again to activate vacuum mode.

To deactivate vacuum mode:

After charging or vacuuming the unit, please deactivate the vacuum
mode:

7

Press the BS2 button until you reach page 

2–17

.

8

When 

2–17

 is reached, press the BS3 button once.

9

Change the setting to '

1

' by pressing the BS2 button once.

10

Push the BS3 button once.

11

When the display is not blinking anymore, press the BS3 button
again to deactivate vacuum mode.

12

Press the BS1 button to leave the setting mode.

Make  sure  to  reattach  the  electronic  component  box  cover  and  to
install the front cover after the job is finished.

NOTICE

Make  sure  that  all  outside  panels,  except  for  the  service
cover  on  the  electrical  component  box,  are  closed  while
working.

Close the lid of the electrical component box firmly before
turning on the power.

Charging refrigerant: Setup

See 

"6.5.3 Checking refrigerant piping: Setup" on page 19

.

To completely recharge refrigerant

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  ALWAYS  use  protective

gloves and safety glasses.

CAUTION

To  avoid  compressor  breakdown,  do  NOT  charge  more
than the specified amount of refrigerant.

Prerequisite: 

Before  completely  recharging  refrigerant,  make  sure

the  system  is  pumped  down,  the  outdoor  unit's 

external

  refrigerant

piping  is  checked  (leak  test,  vacuum  drying)  and  vacuum  drying  on
the outdoor unit's 

internal

 refrigerant piping is performed.

1

If not already done (for vacuum drying of the unit), activate the
vacuum  mode  (see 

"To  activate/deactivate  the  vacuum  mode

field setting" on page 22

)

2

Connect the refrigerant cylinder to the service port of the liquid
stop valve.

3

Open the liquid stop valve.

4

Charge the complete refrigerant amount.

5

Deactivate  the  vacuum  mode  (see 

"To  activate/deactivate  the

vacuum mode field setting" on page 22

).

6

Open the gas stop valve.

6.6.7

To fix the fluorinated greenhouse gases
label

1

Fill in the label as follows:

Summary of Contents for Sky Air Alpha RZAG100N7V1B

Page 1: ...staller reference guide Sky Air Alpha series English Installer reference guide Sky Air Alpha series RZAG71N7V1B RZAG100N7V1B RZAG125N7V1B RZAG140N7V1B RZAG71N7Y1B RZAG100N7Y1B RZAG125N7Y1B RZAG140N7Y1...

Page 2: ...6 5 1 About checking the refrigerant piping 18 6 5 2 Precautions when checking the refrigerant piping 18 6 5 3 Checking refrigerant piping Setup 19 6 5 4 To check for leaks 19 6 5 5 To perform vacuum...

Page 3: ...uch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it wear...

Page 4: ...operated and stored MUST be larger than the minimum floor area defined in table below A m2 This applies to Indoor units without a refrigerant leakage sensor in case of indoor units with refrigerant l...

Page 5: ...ate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refrigerant gas comes into contact with fire DA...

Page 6: ...NG ONLY use copper wires Make sure the field wiring complies with the applicable legislation All field wiring MUST be performed in accordance with the wiring diagram supplied with the product NEVER sq...

Page 7: ...data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication required 2 2 Installer reference gu...

Page 8: ...tion R Air cooled split outdoor unit Z Inverter A Refrigerant R32 G High end series 71 140 Capacity class N7 Model series V1 Power supply 1 220 240 V 50 Hz Y1 Power supply 3N 380 415 V 50 Hz B Europea...

Page 9: ...quipment and electric wires keeping proper distances away from stereo equipment personal computers etc b a c d f e mm 1500 1500 1000 1000 1000 1000 a Earth leakage protector b Fuse c Outdoor unit d In...

Page 10: ...hat the outdoor unit is NEVER snowed up a b c c d a Snow cover or shed b Pedestal minimum height 150 mm c Prevailing wind direction d Air outlet Snow might build up and freeze between the heat exchang...

Page 11: ...s L2 L3 double twin Liquid piping 9 5 mm Gas piping 15 9 mm L1 pair twin triple double twin Model New a Existing b L1 liquid piping L1 gas piping RZAG71 Size down 6 4 mm 12 7 mm Standard 9 5 mm 15 9 m...

Page 12: ...out preparing electrical wiring INFORMATION Also read the precautions and requirements in the General safety precautions chapter INFORMATION Also read 6 7 5 Specifications of standard wiring component...

Page 13: ...e service cover is removed 6 2 2 To open the outdoor unit DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING 1 3 2 4 1 6 3 Mounting the outdoor unit 6 3 1 About mounting the outdoor unit Typical work...

Page 14: ...ollowing figure INFORMATION If necessary you can use a drain pan field supply to prevent drain water from dripping NOTICE If the unit CANNOT be installed fully level always make sure that the inclinat...

Page 15: ...Using the stop valves 6 4 2 Precautions when connecting the refrigerant piping INFORMATION Also read the precautions and requirements in the following chapters General safety precautions Preparation...

Page 16: ...ly flared in a perfect circle c Make sure the flare nut is fitted 6 4 6 To braze the pipe end The indoor unit and outdoor unit have flare connections Connect both ends without brazing If brazing shoul...

Page 17: ...5 16 5 Stem cap gas side 22 5 27 5 To handle the service cap ALWAYS use a charge hose equipped with a valve depressor pin since the service port is a Schrader type valve After handling the service po...

Page 18: ...he refrigerant piping The outdoor unit s internal refrigerant piping has been factory tested for leaks You only have to check the outdoor unit s external refrigerant piping Before checking the refrige...

Page 19: ...a manifold pressure of 0 1 MPa 1 bar 4 After turning the pump OFF check the pressure for at least 1 hour 5 If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour do the follow...

Page 20: ...el and fixing it to the inside of the outdoor unit 6 6 2 About the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gases into the atmosphere Refrigerant type R32 Global warm...

Page 21: ...m 20 30 m 30 40 m 40 45 m R1 0 35 kg 0 7 kg a 0 55 kg b 0 7 kg a 1 05 kg a 1 4 kg a 1 55 kg a R2 0 2 kg 0 4 kg 0 4 kg 0 6 kg 0 8 kg a 1 kg a a Only for RZAG100 140 b Only for RZAG71 In case of size up...

Page 22: ...by pressing the BS2 button once 5 Push the BS3 button once 6 When the display is not blinking anymore press the BS3 button again to activate vacuum mode To deactivate vacuum mode After charging or va...

Page 23: ...wer supply 6 7 2 About electrical compliance RZAG71 140N7V1B Equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by e...

Page 24: ...cover 1 Remove the service cover See 6 2 2 To open the outdoor unit on page 13 2 Strip insulation 20 mm from the wires a b a Strip wire end to this point b Excessive strip length may cause electrical...

Page 25: ...er See 6 8 2 To close the outdoor unit on page 25 8 Connect an earth leakage circuit breaker and fuse to the power supply line 6 8 Finishing the outdoor unit installation 6 8 1 To finish the outdoor u...

Page 26: ...illed the unit must be closed Power up the unit after it is closed You read the complete installation instructions as described in the installer reference guide The indoor units are properly mounted I...

Page 27: ...g displayed the currently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between ind...

Page 28: ...a fan rotates due to strong wind it may store electricity in the capacitor or in the main circuit and cause electric shock 5 After the service is finished plug the junction connector back in Otherwise...

Page 29: ...low pressure sensor to protect the compressor by turning it OFF NEVER short circuit the low pressure switch during pump down operation 11 3 To pump down DANGER RISK OF EXPLOSION Pump down Refrigerant...

Page 30: ...row of units A E a b c d e eB eD a b c d e eB eD A B C D E B HU HD H B 100 A B C 100 1 100 100 B E 100 1000 500 A B C E 150 1 150 150 1000 500 D 500 D E 500 1000 500 B D 100 100 500 500 B D E 1 2 1 HD...

Page 31: ...tween the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lower unit to prevent ice buildup at the upper unit s bottom plate...

Page 32: ...6A X28A and X77A 4 Colours BLK black RED red BLU blue WHT white GRN green 4 Legend English Translation Legend Legend Field supply Field supply Optional Optional Part n Part n Description Description A...

Page 33: ...sed installer Technical skilled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All international European nat...

Page 34: ......

Page 35: ......

Page 36: ...4P573381 1 2019 04 Copyright 2019 Daikin...

Reviews: