Installation

Installer reference guide

20

RZAG71~Y1

Sky Air Alpha-series

4P573381-1 – 2019.04

NOTICE

Before  completely  recharging,  perform  vacuum  drying  on
the outdoor unit's 

internal

 refrigerant piping as well.

NOTICE

To  perform  vacuum  drying  or  a  complete  recharge  of  the
outdoor  unit’s  internal  refrigerant  piping  it  is  necessary  to
activate the vacuum mode (see 

"To activate/deactivate the

vacuum  mode  field  setting"  on  page  22

)  which  will  open

required  valves  in  the  refrigerant  circuit  so  the  vacuuming
process or recharge of refrigerant can be done properly.

▪ Before  vacuum  drying  or  recharging,  activate  field

setting "vacuum mode".

▪ After finishing vacuum drying or recharging, deactivate

field setting "vacuum mode".

WARNING

Some  sections  of  the  refrigerant  circuit  may  be  isolated
from  other  sections  caused  by  components  with  specific
functions  (e.g.  valves).  The  refrigerant  circuit  therefore
features  additional  service  ports  for  vacuuming,  pressure
relief or pressurizing the circuit.

In case it is required to perform 

brazing

 on the unit, ensure

that there is no pressure remaining inside the unit. Internal
pressures  need  to  be  released  with  ALL  the  service  ports
indicated  on  the  figures  below  opened.  The  location  is
depending on model type.

Location of service ports:

b

c

a

a

Internal service port

b

Stop valve with service port (liquid)

c

Stop valve with service port (gas)

Typical  workflow  –  Completely  recharging  refrigerant  typically
consists of the following stages:

1 Determining how much refrigerant to charge.

2 Charging refrigerant.

3 Filling in the fluorinated greenhouse gases label, and fixing it to

the inside of the outdoor unit.

6.6.2

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R32

Global warming potential (GWP) value: 675

WARNING: FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

The  refrigerant  inside  the  unit  is  mildly  flammable,  but
normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater, or a cooker, this may result in fire, or the formation
of a harmful gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room,  and  contact  the  dealer  where  you  purchased  the
unit.

Do  NOT  use  the  unit  until  a  service  person  confirms  that
the  part  from  which  the  refrigerant  leaked  has  been
repaired.

6.6.3

Precautions when charging refrigerant

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

6.6.4

Definitions: L1~L7, H1, H2

Pair

(a)

H1

L1

Twin

(a)

H1

H2

L1

L2

L3

Triple

(a)

L2

L3

L4

H1

H2

L1

Double twin

(a)

H1

H2

L1

L2

L3

L4

L5

L6

L7

(a)

Assume that the longest line in the illustration corresponds
with the actual longest pipe, and the highest unit in the
illustration corresponds with the actual highest unit.

L1

Main piping

L2~L7

Branch piping

H1

Height difference between the highest indoor unit and the
outdoor unit

Summary of Contents for Sky Air Alpha RZAG100N7V1B

Page 1: ...staller reference guide Sky Air Alpha series English Installer reference guide Sky Air Alpha series RZAG71N7V1B RZAG100N7V1B RZAG125N7V1B RZAG140N7V1B RZAG71N7Y1B RZAG100N7Y1B RZAG125N7Y1B RZAG140N7Y1...

Page 2: ...6 5 1 About checking the refrigerant piping 18 6 5 2 Precautions when checking the refrigerant piping 18 6 5 3 Checking refrigerant piping Setup 19 6 5 4 To check for leaks 19 6 5 5 To perform vacuum...

Page 3: ...uch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it wear...

Page 4: ...operated and stored MUST be larger than the minimum floor area defined in table below A m2 This applies to Indoor units without a refrigerant leakage sensor in case of indoor units with refrigerant l...

Page 5: ...ate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refrigerant gas comes into contact with fire DA...

Page 6: ...NG ONLY use copper wires Make sure the field wiring complies with the applicable legislation All field wiring MUST be performed in accordance with the wiring diagram supplied with the product NEVER sq...

Page 7: ...data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication required 2 2 Installer reference gu...

Page 8: ...tion R Air cooled split outdoor unit Z Inverter A Refrigerant R32 G High end series 71 140 Capacity class N7 Model series V1 Power supply 1 220 240 V 50 Hz Y1 Power supply 3N 380 415 V 50 Hz B Europea...

Page 9: ...quipment and electric wires keeping proper distances away from stereo equipment personal computers etc b a c d f e mm 1500 1500 1000 1000 1000 1000 a Earth leakage protector b Fuse c Outdoor unit d In...

Page 10: ...hat the outdoor unit is NEVER snowed up a b c c d a Snow cover or shed b Pedestal minimum height 150 mm c Prevailing wind direction d Air outlet Snow might build up and freeze between the heat exchang...

Page 11: ...s L2 L3 double twin Liquid piping 9 5 mm Gas piping 15 9 mm L1 pair twin triple double twin Model New a Existing b L1 liquid piping L1 gas piping RZAG71 Size down 6 4 mm 12 7 mm Standard 9 5 mm 15 9 m...

Page 12: ...out preparing electrical wiring INFORMATION Also read the precautions and requirements in the General safety precautions chapter INFORMATION Also read 6 7 5 Specifications of standard wiring component...

Page 13: ...e service cover is removed 6 2 2 To open the outdoor unit DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING 1 3 2 4 1 6 3 Mounting the outdoor unit 6 3 1 About mounting the outdoor unit Typical work...

Page 14: ...ollowing figure INFORMATION If necessary you can use a drain pan field supply to prevent drain water from dripping NOTICE If the unit CANNOT be installed fully level always make sure that the inclinat...

Page 15: ...Using the stop valves 6 4 2 Precautions when connecting the refrigerant piping INFORMATION Also read the precautions and requirements in the following chapters General safety precautions Preparation...

Page 16: ...ly flared in a perfect circle c Make sure the flare nut is fitted 6 4 6 To braze the pipe end The indoor unit and outdoor unit have flare connections Connect both ends without brazing If brazing shoul...

Page 17: ...5 16 5 Stem cap gas side 22 5 27 5 To handle the service cap ALWAYS use a charge hose equipped with a valve depressor pin since the service port is a Schrader type valve After handling the service po...

Page 18: ...he refrigerant piping The outdoor unit s internal refrigerant piping has been factory tested for leaks You only have to check the outdoor unit s external refrigerant piping Before checking the refrige...

Page 19: ...a manifold pressure of 0 1 MPa 1 bar 4 After turning the pump OFF check the pressure for at least 1 hour 5 If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour do the follow...

Page 20: ...el and fixing it to the inside of the outdoor unit 6 6 2 About the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gases into the atmosphere Refrigerant type R32 Global warm...

Page 21: ...m 20 30 m 30 40 m 40 45 m R1 0 35 kg 0 7 kg a 0 55 kg b 0 7 kg a 1 05 kg a 1 4 kg a 1 55 kg a R2 0 2 kg 0 4 kg 0 4 kg 0 6 kg 0 8 kg a 1 kg a a Only for RZAG100 140 b Only for RZAG71 In case of size up...

Page 22: ...by pressing the BS2 button once 5 Push the BS3 button once 6 When the display is not blinking anymore press the BS3 button again to activate vacuum mode To deactivate vacuum mode After charging or va...

Page 23: ...wer supply 6 7 2 About electrical compliance RZAG71 140N7V1B Equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by e...

Page 24: ...cover 1 Remove the service cover See 6 2 2 To open the outdoor unit on page 13 2 Strip insulation 20 mm from the wires a b a Strip wire end to this point b Excessive strip length may cause electrical...

Page 25: ...er See 6 8 2 To close the outdoor unit on page 25 8 Connect an earth leakage circuit breaker and fuse to the power supply line 6 8 Finishing the outdoor unit installation 6 8 1 To finish the outdoor u...

Page 26: ...illed the unit must be closed Power up the unit after it is closed You read the complete installation instructions as described in the installer reference guide The indoor units are properly mounted I...

Page 27: ...g displayed the currently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between ind...

Page 28: ...a fan rotates due to strong wind it may store electricity in the capacitor or in the main circuit and cause electric shock 5 After the service is finished plug the junction connector back in Otherwise...

Page 29: ...low pressure sensor to protect the compressor by turning it OFF NEVER short circuit the low pressure switch during pump down operation 11 3 To pump down DANGER RISK OF EXPLOSION Pump down Refrigerant...

Page 30: ...row of units A E a b c d e eB eD a b c d e eB eD A B C D E B HU HD H B 100 A B C 100 1 100 100 B E 100 1000 500 A B C E 150 1 150 150 1000 500 D 500 D E 500 1000 500 B D 100 100 500 500 B D E 1 2 1 HD...

Page 31: ...tween the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lower unit to prevent ice buildup at the upper unit s bottom plate...

Page 32: ...6A X28A and X77A 4 Colours BLK black RED red BLU blue WHT white GRN green 4 Legend English Translation Legend Legend Field supply Field supply Optional Optional Part n Part n Description Description A...

Page 33: ...sed installer Technical skilled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All international European nat...

Page 34: ......

Page 35: ......

Page 36: ...4P573381 1 2019 04 Copyright 2019 Daikin...

Reviews: