6.6.5
Charging additional refrigerant
To determine the additional refrigerant amount
To determine if adding additional refrigerant is necessary
If
Then
(L1+L2+L3+L4+L5+L6+L7)≤
chargeless length
Chargeless length=
▪ 10 m (size‑down)
▪ 40 m (standard)
▪ 15 m (size‑up)
You do not have to add
additional refrigerant.
(L1+L2+L3+L4+L5+L6+L7)>
chargeless length
You must add additional
refrigerant.
For future servicing, encircle the
selected amount in the tables
below.
INFORMATION
Piping length is the largest one-way length of liquid piping.
To determine the additional refrigerant amount (R in kg) (in
case of pair)
Standard piping size
L1 (m)
L1: 40~50 m 50~55 m 55~60 m 60~70 m 70~80 m 80~85 m
R:
0.35 kg
0.7 kg
(a)
0.55 kg
(b)
0.7 kg
(a)
1.05 kg
(a)
1.4 kg
(a)
1.55 kg
(a)
(a)
Only for RZAG100~140.
(b)
Only for RZAG71.
Size-up piping size
L1 (m)
L1:
15~20 m
20~25 m
25~30 m
30~35 m
R:
0.35 kg
0.7 kg
1.05 kg
(a)
1.4 kg
(a)
(a)
Only for RZAG100~140.
To determine the additional refrigerant amount (R in kg) (in
case of twin, triple and double twin)
1
Determine G1 and G2.
G1 (m)
Total length of <x> liquid piping
x=
Ø9.5 mm
(standard)
x=
Ø12.7 mm
(size‑up)
G2 (m)
Total length of
Ø6.4
mm liquid piping
2
Determine R1 and R2.
If
Then
G1>40 m
(a)
Use the table below to determine
R1 (length=
G1−40 m
)
(a)
and R2
(length=
G2
).
G1≤40 m
(a)
(and G1+G2>40 m)
(a)
R1=0.0 kg.
Use the table below to determine
R2 (length=
G1+G2−40 m
)
(a)
.
(a)
In case of size‑up: Replace 40 m by 15 m.
In case of
standard
liquid pipe size:
Length
0~10 m
10~15 m 15~20 m 20~30 m 30~40 m 40~45 m
R1:
0.35 kg
0.7 kg
(a)
0.55 kg
(b)
0.7 kg
(a)
1.05 kg
(a)
1.4 kg
(a)
1.55 kg
(a)
R2:
0.2 kg
0.4 kg
0.4 kg
0.6 kg
0.8 kg
(a)
1 kg
(a)
(a)
Only for RZAG100~140.
(b)
Only for RZAG71.
In case of
size‑up
liquid pipe size:
Length
0~5
m
5~10
m
10~15
m
15~20
m
20~30
m
30~40
m
40~45
m
R1:
0.35 kg 0.7 kg 1.05 kg
(a)
1.4 kg
(a)
—
—
—
R2:
0.35 kg
0.7 kg
(a)
1.05 kg
(a)
1.4 kg
(a)
—
(a)
Only for RZAG100~140.
3
Determine the additional refrigerant amount: R=R1+R2.
Examples
Layout
Additional refrigerant amount (R)
L2=7 m
(Ø6.4 mm)
L3=5 m
(Ø6.4 mm)
L1=45 m (Ø9.5 mm)
RZAG100
Case: Twin, standard liquid pipe size
1 G1 Total Ø9.5
=> G1=45 m
G2 Total Ø6.4 => G2=7+5=12 m
2 Case: G1>40 m
R1 Length=G1−40 m=5 m
=> R1=0.35 kg
R2 Length=G2=12 m
=> R2=0.4 kg
3 R
R=R1+R2=0.35+0.4=0.75 kg
L2=20 m
(Ø6.4 mm)
L3=17 m
(Ø6.4 mm)
L4=17 m
(Ø6.4 mm)
L1=15 m (Ø9.5 mm)
RZAG125
Case: Triple, standard liquid pipe size
1 G1 Total Ø9.5 => G1=15 m
G2 Total Ø6.4 => G2=20+17+17=54 m
2 Case: G1≤40 m (and G1+G2>40 m)
R1 R1=0.0 kg
R2 Length=G1+G2−40 m=15+54−40=2
9 m
=> R2=0.6 kg
3 R
R=R1+R2=0.0+0.6=0.6 kg
Charging refrigerant: Setup
See
"6.5.3 Checking refrigerant piping: Setup" on page 19
.
To charge additional refrigerant
WARNING
▪ Only use R32 as refrigerant. Other substances may
cause explosions and accidents.
▪ R32 contains fluorinated greenhouse gases. Its global
warming potential (GWP) value is 675. Do NOT vent
these gases into the atmosphere.
▪ When charging refrigerant, ALWAYS use protective
gloves and safety glasses.
CAUTION
To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
Prerequisite:
Before charging refrigerant, make sure the refrigerant
piping is connected and checked (leak test and vacuum drying).
1
Connect the refrigerant cylinder to both the service port of the
gas stop valve and the service port of the liquid stop valve.
2
Charge the additional refrigerant amount.
3
Open the stop valves.