Installation

Installer reference guide

15

RZAG71~Y1
Sky Air Alpha-series
4P573381-1 – 2019.04

NOTICE

Precautions when making knockout holes:

▪ Avoid damaging the casing and underlying piping.

▪ After  making  the  knockout  holes,  we  recommend  to

remove  the  burrs  and  paint  the  edges  and  areas
around the edges using repair paint to prevent rusting.

▪ When  passing  electrical  wiring  through  the  knockout

holes,  wrap  the  wiring  with  protective  tape  to  prevent
damage.

INFORMATION

We  suggest  to  install  the  optional  bottom  plate  heater
(EKBPH140N7) when the unit is installed in cold climates.

6.3.6

To prevent the outdoor unit from falling
over

In  case  the  unit  is  installed  in  places  where  strong  wind  can  tilt  the
unit, take following measure:

1

Prepare  2  cables  as  indicated  in  the  following  illustration  (field
supply).

2

Place the 2 cables over the outdoor unit.

3

Insert  a  rubber  sheet  between  the  cables  and  the  outdoor  unit
to prevent the cables from scratching the paint (field supply).

4

Attach the ends of the cables and tighten them.

6.4

Connecting the refrigerant piping

6.4.1

About connecting the refrigerant piping

Before connecting the refrigerant piping

Make sure the outdoor and indoor unit are mounted.

Typical workflow

Connecting the refrigerant piping involves:

▪ Connecting the refrigerant piping to the outdoor unit

▪ Connecting the refrigerant piping to the indoor unit

▪ Insulating the refrigerant piping

▪ Keeping in mind the guidelines for:

▪ Pipe bending

▪ Flaring pipe ends

▪ Brazing

▪ Using the stop valves

6.4.2

Precautions when connecting the
refrigerant piping

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

DANGER: RISK OF BURNING

CAUTION

▪ Do NOT use mineral oil on flared part.

▪ NEVER  install  a  drier  to  this  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

NOTICE

Take  the  following  precautions  on  refrigerant  piping  into
account:

▪ Avoid  anything  but  the  designated  refrigerant  to  get

mixed into the refrigerant cycle (e.g. air).

▪ Only use R32 when adding refrigerant.

▪ Only use installation tools (e.g. manifold gauge set) that

are  exclusively  used  for  R32  installations  to  withstand
the  pressure  and  to  prevent  foreign  materials  (e.g.
mineral oils and moisture) from mixing into the system.

▪ Install  the  piping  so  that  the  flare  is  NOT  subjected  to

mechanical stress.

▪ Protect the piping as described in the following table to

prevent dirt, liquid or dust from entering the piping.

▪ Use  caution  when  passing  copper  tubes  through  walls

(see figure below).

Unit

Installation period

Protection method

Outdoor unit

>1 month

Pinch the pipe

<1 month

Pinch or tape the pipe

Indoor unit

Regardless of the
period

INFORMATION

Do  NOT  open  the  refrigerant  stop  valve  before  checking
the refrigerant piping. When you need to charge additional
refrigerant  it  is  recommended  to  open  the  refrigerant  stop
valve after charging.

6.4.3

Guidelines when connecting the
refrigerant piping

Take the following guidelines into account when connecting pipes:

▪ Coat  the  flare  inner  surface  with  ether  oil  or  ester  oil  when

connecting  a  flare  nut.  Tighten  3  or  4  turns  by  hand,  before
tightening firmly.

Summary of Contents for Sky Air Alpha RZAG100N7V1B

Page 1: ...staller reference guide Sky Air Alpha series English Installer reference guide Sky Air Alpha series RZAG71N7V1B RZAG100N7V1B RZAG125N7V1B RZAG140N7V1B RZAG71N7Y1B RZAG100N7Y1B RZAG125N7Y1B RZAG140N7Y1...

Page 2: ...6 5 1 About checking the refrigerant piping 18 6 5 2 Precautions when checking the refrigerant piping 18 6 5 3 Checking refrigerant piping Setup 19 6 5 4 To check for leaks 19 6 5 5 To perform vacuum...

Page 3: ...uch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it wear...

Page 4: ...operated and stored MUST be larger than the minimum floor area defined in table below A m2 This applies to Indoor units without a refrigerant leakage sensor in case of indoor units with refrigerant l...

Page 5: ...ate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refrigerant gas comes into contact with fire DA...

Page 6: ...NG ONLY use copper wires Make sure the field wiring complies with the applicable legislation All field wiring MUST be performed in accordance with the wiring diagram supplied with the product NEVER sq...

Page 7: ...data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication required 2 2 Installer reference gu...

Page 8: ...tion R Air cooled split outdoor unit Z Inverter A Refrigerant R32 G High end series 71 140 Capacity class N7 Model series V1 Power supply 1 220 240 V 50 Hz Y1 Power supply 3N 380 415 V 50 Hz B Europea...

Page 9: ...quipment and electric wires keeping proper distances away from stereo equipment personal computers etc b a c d f e mm 1500 1500 1000 1000 1000 1000 a Earth leakage protector b Fuse c Outdoor unit d In...

Page 10: ...hat the outdoor unit is NEVER snowed up a b c c d a Snow cover or shed b Pedestal minimum height 150 mm c Prevailing wind direction d Air outlet Snow might build up and freeze between the heat exchang...

Page 11: ...s L2 L3 double twin Liquid piping 9 5 mm Gas piping 15 9 mm L1 pair twin triple double twin Model New a Existing b L1 liquid piping L1 gas piping RZAG71 Size down 6 4 mm 12 7 mm Standard 9 5 mm 15 9 m...

Page 12: ...out preparing electrical wiring INFORMATION Also read the precautions and requirements in the General safety precautions chapter INFORMATION Also read 6 7 5 Specifications of standard wiring component...

Page 13: ...e service cover is removed 6 2 2 To open the outdoor unit DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING 1 3 2 4 1 6 3 Mounting the outdoor unit 6 3 1 About mounting the outdoor unit Typical work...

Page 14: ...ollowing figure INFORMATION If necessary you can use a drain pan field supply to prevent drain water from dripping NOTICE If the unit CANNOT be installed fully level always make sure that the inclinat...

Page 15: ...Using the stop valves 6 4 2 Precautions when connecting the refrigerant piping INFORMATION Also read the precautions and requirements in the following chapters General safety precautions Preparation...

Page 16: ...ly flared in a perfect circle c Make sure the flare nut is fitted 6 4 6 To braze the pipe end The indoor unit and outdoor unit have flare connections Connect both ends without brazing If brazing shoul...

Page 17: ...5 16 5 Stem cap gas side 22 5 27 5 To handle the service cap ALWAYS use a charge hose equipped with a valve depressor pin since the service port is a Schrader type valve After handling the service po...

Page 18: ...he refrigerant piping The outdoor unit s internal refrigerant piping has been factory tested for leaks You only have to check the outdoor unit s external refrigerant piping Before checking the refrige...

Page 19: ...a manifold pressure of 0 1 MPa 1 bar 4 After turning the pump OFF check the pressure for at least 1 hour 5 If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour do the follow...

Page 20: ...el and fixing it to the inside of the outdoor unit 6 6 2 About the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gases into the atmosphere Refrigerant type R32 Global warm...

Page 21: ...m 20 30 m 30 40 m 40 45 m R1 0 35 kg 0 7 kg a 0 55 kg b 0 7 kg a 1 05 kg a 1 4 kg a 1 55 kg a R2 0 2 kg 0 4 kg 0 4 kg 0 6 kg 0 8 kg a 1 kg a a Only for RZAG100 140 b Only for RZAG71 In case of size up...

Page 22: ...by pressing the BS2 button once 5 Push the BS3 button once 6 When the display is not blinking anymore press the BS3 button again to activate vacuum mode To deactivate vacuum mode After charging or va...

Page 23: ...wer supply 6 7 2 About electrical compliance RZAG71 140N7V1B Equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by e...

Page 24: ...cover 1 Remove the service cover See 6 2 2 To open the outdoor unit on page 13 2 Strip insulation 20 mm from the wires a b a Strip wire end to this point b Excessive strip length may cause electrical...

Page 25: ...er See 6 8 2 To close the outdoor unit on page 25 8 Connect an earth leakage circuit breaker and fuse to the power supply line 6 8 Finishing the outdoor unit installation 6 8 1 To finish the outdoor u...

Page 26: ...illed the unit must be closed Power up the unit after it is closed You read the complete installation instructions as described in the installer reference guide The indoor units are properly mounted I...

Page 27: ...g displayed the currently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between ind...

Page 28: ...a fan rotates due to strong wind it may store electricity in the capacitor or in the main circuit and cause electric shock 5 After the service is finished plug the junction connector back in Otherwise...

Page 29: ...low pressure sensor to protect the compressor by turning it OFF NEVER short circuit the low pressure switch during pump down operation 11 3 To pump down DANGER RISK OF EXPLOSION Pump down Refrigerant...

Page 30: ...row of units A E a b c d e eB eD a b c d e eB eD A B C D E B HU HD H B 100 A B C 100 1 100 100 B E 100 1000 500 A B C E 150 1 150 150 1000 500 D 500 D E 500 1000 500 B D 100 100 500 500 B D E 1 2 1 HD...

Page 31: ...tween the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lower unit to prevent ice buildup at the upper unit s bottom plate...

Page 32: ...6A X28A and X77A 4 Colours BLK black RED red BLU blue WHT white GRN green 4 Legend English Translation Legend Legend Field supply Field supply Optional Optional Part n Part n Description Description A...

Page 33: ...sed installer Technical skilled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All international European nat...

Page 34: ......

Page 35: ......

Page 36: ...4P573381 1 2019 04 Copyright 2019 Daikin...

Reviews: