background image

6 Installation

Installer reference guide

9

ATXM20~50+FTXM20~71N2V1B
Daikin room air conditioner
4P518023-4C – 2018.09

▪ In  places  where  a  mineral  oil  mist,  spray  or  vapour  may  be

present  in  the  atmosphere.  Plastic  parts  may  deteriorate  and  fall
off or cause water leakage.

▪ In places where the unit would be in the path of direct sunlight.

▪ In bathrooms.

▪ Sound  sensitive  areas  (e.g.  near  a  bedroom),  so  that  the

operation noise will cause no trouble.

WARNING

Do NOT place objects below the indoor and/or outdoor unit
that may get wet. Otherwise condensation on the main unit
or  refrigerant  pipes,  air  filter  dirt  or  drain  blockage  may
cause dripping, and objects under the unit may get dirty or
damaged.

Spacing. 

Install the unit at least 1.8 m from the floor and keep the

following  requirements  in  mind  for  distances  from  the  walls  and
the ceiling:

≥50

≥50

≥30

(mm)

5.3

Preparing refrigerant piping

5.3.1

Refrigerant piping requirements

INFORMATION

Also  read  the  precautions  and  requirements  in  the
"General safety precautions" chapter.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Class

L1 liquid piping

L1 gas piping

15~35

Ø6.4

Ø9.5

42~60

Ø6.4

Ø12.7

71

Ø6.4

Ø15.9

Refrigerant piping material

Piping material:

 Phosphoric acid deoxidised seamless copper.

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

12.7 mm (1/2")

15.9 mm (5/8")

(a)

Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.

5.3.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

10~14 mm

12.7 mm (1/2")

14~16 mm

15.9 mm (5/8")

16~20 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

5.4

Preparing electrical wiring

5.4.1

About preparing electrical wiring

INFORMATION

Also  read  the  precautions  and  requirements  in  the
"General safety precautions" chapter.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

ALWAYS use multicore cable for power supply cables.

6

Installation

6.1

Overview: Installation

This  chapter  describes  what  you  have  to  do  and  know  on-site  to
install the system.

Summary of Contents for Siesta ATXM25N2V1B

Page 1: ...in room air conditioner English Installer reference guide Daikin room air conditioner CTXM15N2V1B ATXM20N2V1B ATXM25N2V1B ATXM35N2V1B ATXM50N2V1B FTXM20N2V1B FTXM25N2V1B FTXM35N2V1B FTXM42N2V1B FTXM50...

Page 2: ...cting the electrical wiring 15 6 5 2 Precautions when connecting the electrical wiring 15 6 5 3 Guidelines when connecting the electrical wiring 15 6 5 4 Specifications of standard wiring components 1...

Page 3: ...ide a logbook with the product containing at least information on maintenance repair work results of tests stand by periods Also at least following information MUST be provided at an accessible place...

Page 4: ...or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 340 350 360 370 380 390 400 41...

Page 5: ...licable legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the n...

Page 6: ...When disconnecting the power supply the current carrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the termi...

Page 7: ...r What to give and explain to the user Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms 3 About the box 3 1 Overview About the box This ch...

Page 8: ...ite Do NOT install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created the unit MUST be covered Choose an installation location...

Page 9: ...terial with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resistance of at least 120 C Insulation thickness Pipe outer diameter p Insulation inner diameter i...

Page 10: ...panel shaft 6 2 2 To re install the front panel 1 Attach the front panel Align the shafts with the slots and push them all the way in 2 Close the front panel slowly press at both sides and at the cen...

Page 11: ...on the wall using M4 25L screws field supply Class 15 42 Class 50 71 INFORMATION The removed pipe port cover can be kept in the mounting plate pocket Class 15 42 337 810 A 294 44 5 170 68 68 44 5 137...

Page 12: ...This involves General guidelines Connecting the drain piping to the indoor unit Checking for water leaks General guidelines Pipe length Keep drain piping as short as possible Pipe size If drain hose...

Page 13: ...wise water leakage may occur a b a b a Insulation fixing screw b Drain hose 4 Attach the drain hose to the refrigerant pipes bottom side using adhesive vinyl tape A B C b a A Left side piping B Left b...

Page 14: ...ther to tighten the flare nut when connecting the piping This to prevent nut cracking and leaks a b c d a Torque wrench b Spanner c Piping union d Flare nut Piping size mm Tightening torque N m Flare...

Page 15: ...fied persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical parts i...

Page 16: ...animals that make contact with electrical parts can cause malfunctions smoke or fire a b c a Terminal block b Electrical component block c Wire retainer 5 Strip the wire ends approximately 15 mm 6 Mat...

Page 17: ...to the definition of Directive 2014 53 EU INFORMATION Install the wireless LAN adapter after finishing the indoor unit installation Refer to 6 7 2 To install the wireless LAN adapter on page 17 Basic...

Page 18: ...ccessory 2 To place the wireless LAN adapter into the unit For class 15 42 1 Place the wireless LAN adapter against the hooks 2 Lock the adapter by pressing it down 3 To remove the adapter perform the...

Page 19: ...or at least 5 seconds Result The user interface will return to the previous screen 8 Commissioning 8 1 Overview Commissioning Typical workflow Commissioning typically consists of the following stages...

Page 20: ...ormal level In cooling mode 26 28 C in heating mode 20 24 C 3 The system stops operating 3 minutes after the unit is turned OFF 8 3 1 To perform a test run using the user interface 1 Press to switch t...

Page 21: ...SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR...

Page 22: ...oduct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance ins...

Page 23: ......

Page 24: ...4P518023 4C 2018 09 Copyright 2018 Daikin...

Reviews: