background image

7 Configuration

Installer reference guide

19

ATXM20~50+FTXM20~71N2V1B
Daikin room air conditioner
4P518023-4C – 2018.09

6.7.3

To install the Daikin Online Controller
application

1

Open:

▪ Google Play for appliances using Android.
▪ App Store for appliances using iOS.

2

Search for 

Daikin Online Controller

.

3

Follow the directions on the screen to install.

7

Configuration

7.1

To set a different address

In case 2 indoor units are installed in 1 room, different addresses for
2 user interfaces can be set.

1

Remove the cover and the batteries from the user interface.

2

Cut the address jumper J4.

a

a

Address jumper J4

NOTICE

Be  careful  NOT  to  damage  any  of  the  surrounding  parts
when cutting the address jumper.

3

Turn the power supply on.

4

Press 

 and 

 simultaneously.

5

Press 

, select   and press 

.

Result: 

The operation lamp will start to blink.

a

b

a

Operation lamp

b

Indoor unit ON/OFF switch

6

Press  the  indoor  unit  ON/OFF  switch  while  the  operation  lamp
is blinking.

Address jumper

Address

Factory setting

1

After cutting with nippers

2

INFORMATION

If the setting could NOT be completed while the operation
lamp  was  blinking,  repeat  the  setting  process  from  the
beginning.

7

When the setting is complete, keep 

 pressed for at least

5 seconds.

Result: 

 The user interface will return to the previous screen.

8

Commissioning

8.1

Overview: Commissioning

Typical workflow

Commissioning typically consists of the following stages:

1

Checking the "Checklist before commissioning".

2

Performing a test run for the system.

8.2

Checklist before commissioning

Do NOT operate the system before the following checks are OK:

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor units

 are properly mounted.

The 

outdoor unit

 is properly mounted.

Air inlet/outlet

Check  that  the  air  inlet  and  outlet  of  the  unit  is  NOT
obstructed  by  paper  sheets,  cardboard,  or  any  other
material.

There are NO 

missing phases

 or 

reversed phases

.

The 

refrigerant  pipes

  (gas  and  liquid)  are  thermally

insulated.

Drainage

Make sure drainage flows smoothly.

Possible consequence: 

Condensate water might drip.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

The  specified  wires  are  used  for  the 

interconnection

cable

.

The indoor unit receives the signals of the 

user interface

.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

The 

insulation resistance

 of the compressor is OK.

Summary of Contents for Siesta ATXM25N2V1B

Page 1: ...in room air conditioner English Installer reference guide Daikin room air conditioner CTXM15N2V1B ATXM20N2V1B ATXM25N2V1B ATXM35N2V1B ATXM50N2V1B FTXM20N2V1B FTXM25N2V1B FTXM35N2V1B FTXM42N2V1B FTXM50...

Page 2: ...cting the electrical wiring 15 6 5 2 Precautions when connecting the electrical wiring 15 6 5 3 Guidelines when connecting the electrical wiring 15 6 5 4 Specifications of standard wiring components 1...

Page 3: ...ide a logbook with the product containing at least information on maintenance repair work results of tests stand by periods Also at least following information MUST be provided at an accessible place...

Page 4: ...or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 340 350 360 370 380 390 400 41...

Page 5: ...licable legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the n...

Page 6: ...When disconnecting the power supply the current carrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the termi...

Page 7: ...r What to give and explain to the user Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms 3 About the box 3 1 Overview About the box This ch...

Page 8: ...ite Do NOT install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created the unit MUST be covered Choose an installation location...

Page 9: ...terial with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resistance of at least 120 C Insulation thickness Pipe outer diameter p Insulation inner diameter i...

Page 10: ...panel shaft 6 2 2 To re install the front panel 1 Attach the front panel Align the shafts with the slots and push them all the way in 2 Close the front panel slowly press at both sides and at the cen...

Page 11: ...on the wall using M4 25L screws field supply Class 15 42 Class 50 71 INFORMATION The removed pipe port cover can be kept in the mounting plate pocket Class 15 42 337 810 A 294 44 5 170 68 68 44 5 137...

Page 12: ...This involves General guidelines Connecting the drain piping to the indoor unit Checking for water leaks General guidelines Pipe length Keep drain piping as short as possible Pipe size If drain hose...

Page 13: ...wise water leakage may occur a b a b a Insulation fixing screw b Drain hose 4 Attach the drain hose to the refrigerant pipes bottom side using adhesive vinyl tape A B C b a A Left side piping B Left b...

Page 14: ...ther to tighten the flare nut when connecting the piping This to prevent nut cracking and leaks a b c d a Torque wrench b Spanner c Piping union d Flare nut Piping size mm Tightening torque N m Flare...

Page 15: ...fied persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical parts i...

Page 16: ...animals that make contact with electrical parts can cause malfunctions smoke or fire a b c a Terminal block b Electrical component block c Wire retainer 5 Strip the wire ends approximately 15 mm 6 Mat...

Page 17: ...to the definition of Directive 2014 53 EU INFORMATION Install the wireless LAN adapter after finishing the indoor unit installation Refer to 6 7 2 To install the wireless LAN adapter on page 17 Basic...

Page 18: ...ccessory 2 To place the wireless LAN adapter into the unit For class 15 42 1 Place the wireless LAN adapter against the hooks 2 Lock the adapter by pressing it down 3 To remove the adapter perform the...

Page 19: ...or at least 5 seconds Result The user interface will return to the previous screen 8 Commissioning 8 1 Overview Commissioning Typical workflow Commissioning typically consists of the following stages...

Page 20: ...ormal level In cooling mode 26 28 C in heating mode 20 24 C 3 The system stops operating 3 minutes after the unit is turned OFF 8 3 1 To perform a test run using the user interface 1 Press to switch t...

Page 21: ...SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR...

Page 22: ...oduct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance ins...

Page 23: ......

Page 24: ...4P518023 4C 2018 09 Copyright 2018 Daikin...

Reviews: