background image

6 Installation

Installer reference guide

12

ATXM20~50+FTXM20~71N2V1B

Daikin room air conditioner

4P518023-4C – 2018.09

6.3.3

To drill a wall hole

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

NOTICE

Be  sure  to  seal  the  gaps  around  the  pipes  with  sealing
material (field supply), in order to prevent water leakage.

1

Bore  a  65  mm  (class  15~42)  or  80  mm  (class  50~71)  large
feed-through  hole  in  the  wall  with  a  downward  slope  towards
the outside.

2

Insert a wall embedded pipe into the hole.

3

Insert a wall cover into the wall pipe.

Ø65/80

a b

c

a

Wall embedded pipe

b

Putty

c

Wall hole cover

4

After  completing  wiring,  refrigerant  piping  and  drain  piping,  do
NOT forget to seal the gap with putty.

6.3.4

To remove the pipe port cover

To  connect  the  piping  on  right-side,  right-bottom,  left-side  or  left-
bottom, the pipe port cover MUST be removed.

1

Cut  off  the  pipe  port  cover  from  inside  the  front  grille  using  a
coping saw.

2

Remove  any  burrs  along  the  cut  section  using  a  half  round
needle file.

NOTICE

Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.

6.3.5

To provide drainage

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe  size.

  If  drain  hose  extension  or  embedded  drain  piping  is

required, use appropriate parts that match the hose front end.

Ø16

Ø18

NOTICE

▪ Install the drain hose with a downward slope.

▪ Traps are NOT permitted.

▪ Do NOT put the end of the hose in water.

Drain  hose  extension.

  To  extend  the  drain  hose,  use  a  field

supplied  hose  with  inner  Ø16  mm.  Do  NOT  forget  to  use  a  heat
insulation tube on the indoor section of the extension hose.

a

a

b

c

Ø16

Ø16

a

Drain hose supplied with the indoor unit

b

Heat insulation tube (field supply)

c

Extension drain hose

Rigid polyvinyl chloride pipe.

 When connecting a rigid polyvinyl

chloride pipe (nominal Ø13 mm) directly to the drain hose as with
embedded piping work, use a field supplied drain socket (nominal
Ø13 mm).

a

b

c

Ø18

a

Drain hose supplied with the indoor unit

b

Drain socket with nominal Ø13 mm (field supply)

c

Rigid polyvinyl chloride pipe (field supply)

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

1

Insert the drain hose in the drain pipe as shown in the following
figure, so it will NOT be pulled out of the drain pipe.

≥50

mm

To connect the piping on right side, right-back, or
right-bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

Summary of Contents for Siesta ATXM25N2V1B

Page 1: ...in room air conditioner English Installer reference guide Daikin room air conditioner CTXM15N2V1B ATXM20N2V1B ATXM25N2V1B ATXM35N2V1B ATXM50N2V1B FTXM20N2V1B FTXM25N2V1B FTXM35N2V1B FTXM42N2V1B FTXM50...

Page 2: ...cting the electrical wiring 15 6 5 2 Precautions when connecting the electrical wiring 15 6 5 3 Guidelines when connecting the electrical wiring 15 6 5 4 Specifications of standard wiring components 1...

Page 3: ...ide a logbook with the product containing at least information on maintenance repair work results of tests stand by periods Also at least following information MUST be provided at an accessible place...

Page 4: ...or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 340 350 360 370 380 390 400 41...

Page 5: ...licable legislation WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the n...

Page 6: ...When disconnecting the power supply the current carrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the termi...

Page 7: ...r What to give and explain to the user Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms 3 About the box 3 1 Overview About the box This ch...

Page 8: ...ite Do NOT install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created the unit MUST be covered Choose an installation location...

Page 9: ...terial with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resistance of at least 120 C Insulation thickness Pipe outer diameter p Insulation inner diameter i...

Page 10: ...panel shaft 6 2 2 To re install the front panel 1 Attach the front panel Align the shafts with the slots and push them all the way in 2 Close the front panel slowly press at both sides and at the cen...

Page 11: ...on the wall using M4 25L screws field supply Class 15 42 Class 50 71 INFORMATION The removed pipe port cover can be kept in the mounting plate pocket Class 15 42 337 810 A 294 44 5 170 68 68 44 5 137...

Page 12: ...This involves General guidelines Connecting the drain piping to the indoor unit Checking for water leaks General guidelines Pipe length Keep drain piping as short as possible Pipe size If drain hose...

Page 13: ...wise water leakage may occur a b a b a Insulation fixing screw b Drain hose 4 Attach the drain hose to the refrigerant pipes bottom side using adhesive vinyl tape A B C b a A Left side piping B Left b...

Page 14: ...ther to tighten the flare nut when connecting the piping This to prevent nut cracking and leaks a b c d a Torque wrench b Spanner c Piping union d Flare nut Piping size mm Tightening torque N m Flare...

Page 15: ...fied persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical parts i...

Page 16: ...animals that make contact with electrical parts can cause malfunctions smoke or fire a b c a Terminal block b Electrical component block c Wire retainer 5 Strip the wire ends approximately 15 mm 6 Mat...

Page 17: ...to the definition of Directive 2014 53 EU INFORMATION Install the wireless LAN adapter after finishing the indoor unit installation Refer to 6 7 2 To install the wireless LAN adapter on page 17 Basic...

Page 18: ...ccessory 2 To place the wireless LAN adapter into the unit For class 15 42 1 Place the wireless LAN adapter against the hooks 2 Lock the adapter by pressing it down 3 To remove the adapter perform the...

Page 19: ...or at least 5 seconds Result The user interface will return to the previous screen 8 Commissioning 8 1 Overview Commissioning Typical workflow Commissioning typically consists of the following stages...

Page 20: ...ormal level In cooling mode 26 28 C in heating mode 20 24 C 3 The system stops operating 3 minutes after the unit is turned OFF 8 3 1 To perform a test run using the user interface 1 Press to switch t...

Page 21: ...SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR...

Page 22: ...oduct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance ins...

Page 23: ......

Page 24: ...4P518023 4C 2018 09 Copyright 2018 Daikin...

Reviews: