7-3 Power supply wiring connection procedure

WARNING

• Never connect power supply wiring to the terminal block for remote 

controller wiring as this could damage the entire system.

Install a ground fault circuit interrupter.

• It is obliged to install a ground fault circuit interrupter to prevent elec-

tric shock and fire accident.

CAUTION

• After finishing the electric wiring work, confirm that all the wirings are 

connected securely.

〈〈

Precautions when laying power wiring

〉〉

• Two electric wires of different thickness cannot be connected to the 

power terminal block.
(Slack in the electric wires may generate abnormal heat.)

• Use round pressure terminals with insulting sleeve for connection to 

the power terminal block.  
If such terminals are not available for unavoidable reasons, connect 
an electric wire of the same thickness to each side as shown in the 
figure.

• For wiring, use the designated power wire and connect firmly, then 

secure to prevent outside pressure being exerted on the terminal 
board.

• Use an appropriate screwdriver for tightening the terminal screws. 

A screwdriver with a small head will strip the head and make proper 
tightening impossible.

• Over-tightening the terminal screws may break them.
• See the table below for tightening torque for the terminal screws.

Model

Phase and 

frequency

Voltage

Max. Overcurrent 

Protective device

Min. Circuit 

Amps.

RZQ30PVJU7

1 ~ 60Hz

208/230V

30A

27A

RZQ36PVJU8
RZR36PVJU8

RZQ42PVJU8
RZR42PVJU8

Screw

Remove it and open 
the cover.

Control box

Terminal block

Stop valve 
mounting plate

Knockout hole

Power supply wiring 
(including ground wire) 
or transmission wiring.

Power supply wiring 
(including ground wire) 
or transmission wiring.

Forward

Sideways

Backward

Knockout hole

Make sure to observe the following items.  If they are not observed, 
abnormal heat may be generated by slack in electric wires, etc. 

Tightening torque (ft·lbf)

M5

(Power supply and ground terminal block)

1.76 ~ 2.15

M4

(Shielded ground)

0.87 ~ 1.06

M3.5

(Transmission wiring terminal block)

0.58 ~ 0.72

L 2

L 1

Cut off the insulation 
tube sticking out of the 
outdoor unit.

Terminal block (X2M)

Transmission wiring

(To X2M [TO IN/ D 
UNIT](F1, F2))

Insulation tube (Small) 
(accessory)

Cut off the insulation 
tube sticking out of the 
outdoor unit.

Insulation tube (Large) 
(accessory)

Clamp (accessory)

Ground wire 
(Yellow/Green)

Stop valve 
mounting plate

Terminal 
block (X1M)

Connecting power 
supply wiring

Power wire

Round pressure terminal

Attach insulation sleeve

Connect same-
thickness wiring 
to both sides.

It is forbidden to 
connect two to 
one side.

It is forbidden to 
connect wiring of 
different thicknesses.

01_EN_3PN07193-9P.fm  Page 12  Tuesday, June 6, 2017  3:56 PM

Summary of Contents for RZR36PVJU8

Page 1: ...avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente estas instrucciones antes de instalar Guarde...

Page 2: ...ult in water leakage elec tric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant l...

Page 3: ...as thinner or gasoline are handled Oper ating the unit in such conditions can cause a fire Take adequate measures to prevent the outdoor unit from being used as a shelter by small animals Small animal...

Page 4: ...whose velocity is 11 mph or more blows to the out door unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following eff...

Page 5: ...conduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open 1 When one outdoor unit is installed individually When an obstruction is pr...

Page 6: ...utdoor unit is installed individually The dimensional relationship between H L and A is as shown in the table below NOTE Close the area under the frame so that the outlet air does not bypass there 2 W...

Page 7: ...2 Only two outdoor units can be installed side by side D When outdoor units are stacked 1 When an obstruction is present on the air outlet side NOTE 1 Only two outdoor units can be stacked 2 About 4 i...

Page 8: ...ng nut 3 Remove the transportation metal and the washer as shown in the above figure 4 Return and tighten the fixing nut again 5 Return the sound proof cover to achieve the former status CAUTION If th...

Page 9: ...than the specified refrigerant enter the refrigerant system Do not let any gas such as air enter the refrigerant system Precautions when connecting the piping See the following table for flare dimens...

Page 10: ...nditioner at 14 6 psi or less for 1 hour or more and confirm that the vacuum pressure indi cated by the vacuum gage does not increase If the vacuum pressure increases the system may contain moisture o...

Page 11: ...counterclockwise 2 When the valve stem cannot be turned any more stop turning Now the valve is open How to close the stop valve 1 Insert a hexagon wrench into the valve stem and turn the valve stem c...

Page 12: ...supply wiring and transmission wiring Let the power supply wiring and transmission wiring with a conduit pass through one of the knockout holes on the front or side piping cover and let the transmiss...

Page 13: ...e below for tightening torque for the terminal screws Model Phase and frequency Voltage Max Overcurrent Protective device Min Circuit Amps RZQ30PVJU7 1 60Hz 208 230V 30A 27A RZQ36PVJU8 RZR36PVJU8 RZQ4...

Page 14: ...ORK 5 Piping size and heat insulation Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping 6 Check of stop valve Confirm that the stop valve is open on both the liquid line and gas...

Page 15: ...outdoor unit may continue to operate for a further 3 minutes If the system has not undergone the check operation by the test run button since it was first installed a malfunction code U3 is dis playe...

Page 16: ...in the outdoor unit remain closed Open the stop valve on both the gas and liquid lines The refrigerant is overcharged Calculate again the required amount of refrigerant to be charged based on the pipi...

Page 17: ...ions in steps 1 and 2 above 4 Deal with the situations where the result exceeds the maximum con centration level Where the installation of a facility results in a concentration in excess of the maximu...

Page 18: ...1707 HT 3PN07193 9P EM17A016 00_CV_3PN07193 9P fm Page 2 Tuesday June 6 2017 3 52 PM...

Reviews: