background image

English

8

NOTE

• Maximum piping length between the outdoor and indoor unit is 230ft.
• Installation tools:

Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to withstand
the pressure and to prevent foreign materials (e.g. mineral oils such
as SUNISO and moisture) from mixing into the system.
(The screw specifications differ for R410A and R407C.)
Vacuum pump (use a 2-stage vacuum pump with a non-return valve):

1.

Make sure the pump oil does not flow oppositely into the system
while the pump is not working.

2.

Use a vacuum pump which can evacuate to –14.6 psi.

6-1 Selection of piping material
1.

Foreign materials inside pipes (including oils for fabrication) must be
0.14gr/10ft. or less.

2.

Use the following material specification for refrigerant piping:

construction material: Phosphoric acid deoxidized seamless cop-
per for refrigerant.

6-2 Protection of piping

• Protect the piping to prevent moisture and dusts from coming into the 

piping.

• Especially, pay attention when passing the piping through a hole or 

connecting the end of piping to the outdoor.

6-3 Piping connection

For handling of stop valves, refer to “Stop valve operation 
method” in “6-7 Additional refrigerant charge”.

Only use the flare nuts attached to the stop valves. 
Using different flare nuts may cause the refrigerant to leak.

Be sure to perform a nitrogen blow when brazing.

(Brazing without performing nitrogen replacement or releasing nitrogen 
into the piping will create large quantities of oxidized film inside the 
pipes, adversely affecting valves and compressor in the refrigerating 
system and preventing normal operation.)

DANGER

• Use of oxygen could cause an explosion resulting in severe injury or 

death.  Only use nitrogen gas.

• Refrigerant gas may produce toxic gas if it comes in contact with fire 

such as from a fan heater, stove or cooking device. Exposure to this 
gas could cause severe injury or death.

NOTE

• When brazing with blowing nitrogen, set the nitrogen pressure to 

2.9 psi or less by using a pressure reducing valve.

CAUTION

• Do not use anti-oxidants when brazing.

Residue can clog pipes and break the unit.

Do not let any refrigerant other than the specified refrigerant enter  
the refrigerant system.
Do not let any gas such as air enter the refrigerant system.

Precautions when connecting the piping

• See the following table for flare dimensions.
• When connecting the flare nuts, apply refrigerant oil to the inside and 

outside of the flares and turn them three or four times at first.
(Use ester oil or ether oil.)

• See the following table for tightening torque. (Applying too much 

torque may cause the flares to crack.)

• After connecting all the piping perform a gas leak check by using 

nitrogen.

• If you are obliged to install the unit without a torque wrench, you may 

follow the installation method mentioned below. 
After the work is finished, make sure to check that there is no gas leak.

• When you keep on tightening the flare nut with a spanner, there is a 

point where the tightening torque suddenly increases. 
From that position, further tighten the flare nut the angle shown below.

Disposal requirements

Dismantling of the unit,  treatment of the refrigerant, oil and eventual
other parts should be comply the relevant local and national regulations.

6-4 Refrigerant piping work procedure

The field piping can be connected in four directions.

When connecting the piping downward, remove the knockout hole by 
making four holes in the middle on the each side of the knockout hole 
with a drill.

Then cut out the corner of the bottom frame along the slits (in two 
positions) by using a hacksaw.

After removing the parts, it is recommended to apply repair paint on 
the edges, to prevent rusting.

Location

Working period

Protection method

Outdoor

1 month or more

Pinch pipes

Less than 1 month

Pinch or tape pipes

Indoor

Regardless of period

Location to 
be brazed

Taping

Refrigerant 
piping

Nitrogen

Regulator

Manual valve

Nitrogen

Pipe size

Tightening

torque (ft·lbf)

Flare dimension A (in.)

Flare shape (in.)

φ

3/8”

26.7±2.6

0.504 - 0.520

φ

5/8”

50.6±5.0

0.760 - 0.776

Pipe size

Tightening angle 

(Guideline)

Recommended arm 

length of tool (in.)

φ

 3/8”

60°~90°

Approx. 7 7/8

φ

 5/8”

30°~60°

Approx. 11 13/16

A

45˚± 2˚

90˚± 2˚

R0.016

~0.031

Apply ester oil or ether oil 
only to inner side of flare.

Piping cover

Screw for 
front panel

Screw for piping 
cover (front)

Front 
panel

Lateral 
direction

Front direction

Rear 
direction

Downward 
direction

Field piping

Bottom frame

Knockout hole

Drill

Slit

Middle on the side

Slit

01_EN_3PN07193-9P.fm  Page 8  Tuesday, June 6, 2017  3:56 PM

Summary of Contents for RZR36PVJU8

Page 1: ...avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente estas instrucciones antes de instalar Guarde...

Page 2: ...ult in water leakage elec tric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant l...

Page 3: ...as thinner or gasoline are handled Oper ating the unit in such conditions can cause a fire Take adequate measures to prevent the outdoor unit from being used as a shelter by small animals Small animal...

Page 4: ...whose velocity is 11 mph or more blows to the out door unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following eff...

Page 5: ...conduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open 1 When one outdoor unit is installed individually When an obstruction is pr...

Page 6: ...utdoor unit is installed individually The dimensional relationship between H L and A is as shown in the table below NOTE Close the area under the frame so that the outlet air does not bypass there 2 W...

Page 7: ...2 Only two outdoor units can be installed side by side D When outdoor units are stacked 1 When an obstruction is present on the air outlet side NOTE 1 Only two outdoor units can be stacked 2 About 4 i...

Page 8: ...ng nut 3 Remove the transportation metal and the washer as shown in the above figure 4 Return and tighten the fixing nut again 5 Return the sound proof cover to achieve the former status CAUTION If th...

Page 9: ...than the specified refrigerant enter the refrigerant system Do not let any gas such as air enter the refrigerant system Precautions when connecting the piping See the following table for flare dimens...

Page 10: ...nditioner at 14 6 psi or less for 1 hour or more and confirm that the vacuum pressure indi cated by the vacuum gage does not increase If the vacuum pressure increases the system may contain moisture o...

Page 11: ...counterclockwise 2 When the valve stem cannot be turned any more stop turning Now the valve is open How to close the stop valve 1 Insert a hexagon wrench into the valve stem and turn the valve stem c...

Page 12: ...supply wiring and transmission wiring Let the power supply wiring and transmission wiring with a conduit pass through one of the knockout holes on the front or side piping cover and let the transmiss...

Page 13: ...e below for tightening torque for the terminal screws Model Phase and frequency Voltage Max Overcurrent Protective device Min Circuit Amps RZQ30PVJU7 1 60Hz 208 230V 30A 27A RZQ36PVJU8 RZR36PVJU8 RZQ4...

Page 14: ...ORK 5 Piping size and heat insulation Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping 6 Check of stop valve Confirm that the stop valve is open on both the liquid line and gas...

Page 15: ...outdoor unit may continue to operate for a further 3 minutes If the system has not undergone the check operation by the test run button since it was first installed a malfunction code U3 is dis playe...

Page 16: ...in the outdoor unit remain closed Open the stop valve on both the gas and liquid lines The refrigerant is overcharged Calculate again the required amount of refrigerant to be charged based on the pipi...

Page 17: ...ions in steps 1 and 2 above 4 Deal with the situations where the result exceeds the maximum con centration level Where the installation of a facility results in a concentration in excess of the maximu...

Page 18: ...1707 HT 3PN07193 9P EM17A016 00_CV_3PN07193 9P fm Page 2 Tuesday June 6 2017 3 52 PM...

Reviews: