background image

English

10

After the vacuum drying is finished, charge the additional refrigerant
in its liquid state through the liquid stop valve service port. 
Taking into account following instructions:

1.

Check that gas and liquid stop valves are closed.

2.

Charge the specified amount of refrigerant.

• If the outdoor unit is not in operation and the total amount cannot be 

charged, follow the procedures for additional refrigerant charge 
shown below.

• Make sure to use installation tools you exclusively use on R410A 

installations to withstand the pressure and to prevent foreign materi-
als from mixing into the system.

Procedures for charging additional refrigerant.

See the “Cautions on service” label on the back of the front panel for the 
settings for operation after replenishing refrigerant.
1. Open the gas line stop valve (leaving the liquid line stop valve, valve

A in the diagram above, close) and perform the operation to add the
refrigerant.

2. Once the appropriate amount of refrigerant is in, press the confirma-

tion button (BS3) on the outdoor unit PC board (A1P), and stop oper-
ation.

3. Open the stop valves quickly (both liquid and gas line valves).

(This must be done quickly to avoid the possibility that the pipe might
burst.)

• The figure below shows the name of each part required in handling the 

stop valve.  At the time of shipment, the stop valve is closed.

• If only a torque wrench is used to loosen or tighten the flare nut, the 

side plate may be distorted.  Make sure to fix the stop valve with a 
spanner, then loosen or tighten the flare nut with a torque wrench.

• When it is expected that the operating pressure will be low (for exam-

ple, when cooling will be performed while the outside air temperature 
is low), seal sufficiently the flare nut in the stop valve on the gas line 
with silicon sealant to prevent freezing.

[Stop valve operation method]

Prepare hexagon wrenches (whose size is 4 mm and 6 mm).

How to open the stop valve

1. Insert a hexagon wrench into the valve stem, and turn the valve

stem counterclockwise.

2. When the valve stem cannot be turned any more, stop turning.

Now, the valve is open.

How to close the stop valve

1. Insert a hexagon wrench into the valve stem, and turn the valve

stem clockwise.

2. When the valve stem cannot be turned any more, stop turning.

Now, the valve is closed.

• The valve is sealed in the arrow area.  Take care not to damage the 

arrow area.

• After handling the valve, make sure to tighten the valve cap securely. 

• Use charge hose equipped with push in the work.
• After the work, make sure to tighten the valve cap securely.

Tightening torque.....8.5~10.3 ft·lbf

7.

ELECTRIC WIRING WORK

DANGER

• Do not ground units to water pipes, telephone wires or lightning rods 

because incomplete grounding could cause a severe shock hazard 
resulting in severe injury or death, and to gas pipes because a gas leak 
could result in an explosion which could lead to severe injury or death.

WARNING

• Disconnect all power to unit to avoid possible electric shock 

during installation.

• Use only specified wire and connect wires to terminals tightly.  Be 

careful that wires do not place external stress on terminals.  Keep 
wires in neat order so as to not to obstruct other equipment.  Incom-
plete connections could result in overheating, and in worse cases, 
electric shock or fire. 
For the details, refer to  

“7-3 Power supply wiring connection pro-

cedure”

.

Stop valve operation method 

Cautions on handling the stop valve 

Nitrogen

Dotted lines 
represent 
field piping

Cylinder

Stop valve service port

Vacuum pump

Weighing 
scale

Charge hose

R410A

Pressure 
reducing 
valve

Outdoor unit

Indoor unit

Liquid line

Gas line

(Siphon system)

Valve A

Valve cap

Service port

Field piping 
connection part

Valve stem

Silicon sealant

(Take care not to generate cavity.)

Stop valve of two 
hangs structure

Stop valve of one 
hang structure

Torque 
wrench

Torque 

wrench

Spanner

Spanner prohibition 
to valve cap and 
body part

Cautions on handling the valve cap

Liquid line

Gas line

10.0~12.2 ft·lbf

16.6~20.3 ft·lbf

Cautions on handling the service port

<Liquid line>

<Gas line>

Opening direction

Opening direction

Valve cap

Stop valve 
(valve cap attachment area)

01_EN_3PN07193-9P.fm  Page 10  Tuesday, June 6, 2017  3:56 PM

Summary of Contents for RZR36PVJU8

Page 1: ...avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente estas instrucciones antes de instalar Guarde...

Page 2: ...ult in water leakage elec tric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant l...

Page 3: ...as thinner or gasoline are handled Oper ating the unit in such conditions can cause a fire Take adequate measures to prevent the outdoor unit from being used as a shelter by small animals Small animal...

Page 4: ...whose velocity is 11 mph or more blows to the out door unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following eff...

Page 5: ...conduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open 1 When one outdoor unit is installed individually When an obstruction is pr...

Page 6: ...utdoor unit is installed individually The dimensional relationship between H L and A is as shown in the table below NOTE Close the area under the frame so that the outlet air does not bypass there 2 W...

Page 7: ...2 Only two outdoor units can be installed side by side D When outdoor units are stacked 1 When an obstruction is present on the air outlet side NOTE 1 Only two outdoor units can be stacked 2 About 4 i...

Page 8: ...ng nut 3 Remove the transportation metal and the washer as shown in the above figure 4 Return and tighten the fixing nut again 5 Return the sound proof cover to achieve the former status CAUTION If th...

Page 9: ...than the specified refrigerant enter the refrigerant system Do not let any gas such as air enter the refrigerant system Precautions when connecting the piping See the following table for flare dimens...

Page 10: ...nditioner at 14 6 psi or less for 1 hour or more and confirm that the vacuum pressure indi cated by the vacuum gage does not increase If the vacuum pressure increases the system may contain moisture o...

Page 11: ...counterclockwise 2 When the valve stem cannot be turned any more stop turning Now the valve is open How to close the stop valve 1 Insert a hexagon wrench into the valve stem and turn the valve stem c...

Page 12: ...supply wiring and transmission wiring Let the power supply wiring and transmission wiring with a conduit pass through one of the knockout holes on the front or side piping cover and let the transmiss...

Page 13: ...e below for tightening torque for the terminal screws Model Phase and frequency Voltage Max Overcurrent Protective device Min Circuit Amps RZQ30PVJU7 1 60Hz 208 230V 30A 27A RZQ36PVJU8 RZR36PVJU8 RZQ4...

Page 14: ...ORK 5 Piping size and heat insulation Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping 6 Check of stop valve Confirm that the stop valve is open on both the liquid line and gas...

Page 15: ...outdoor unit may continue to operate for a further 3 minutes If the system has not undergone the check operation by the test run button since it was first installed a malfunction code U3 is dis playe...

Page 16: ...in the outdoor unit remain closed Open the stop valve on both the gas and liquid lines The refrigerant is overcharged Calculate again the required amount of refrigerant to be charged based on the pipi...

Page 17: ...ions in steps 1 and 2 above 4 Deal with the situations where the result exceeds the maximum con centration level Where the installation of a facility results in a concentration in excess of the maximu...

Page 18: ...1707 HT 3PN07193 9P EM17A016 00_CV_3PN07193 9P fm Page 2 Tuesday June 6 2017 3 52 PM...

Reviews: