background image

9

NOTE

• When brazing with blowing nitrogen, set the nitrogen pressure to 

2.9 psi or less by using a pressure reducing valve.

CAUTION

• Do not use anti-oxidants when brazing.

Residue can clog pipes and break the unit.

Do not let any refrigerant other than the specified refrigerant enter  
the refrigerant system.
Do not let any gas such as air enter the refrigerant system.

〈〈〈〈

Precautions when connecting the pipings

〉〉〉〉

• See the following table for flare dimensions.
• When connecting the flare nuts, apply refrigerant oil to the inside and 

outside of the flares and turn them three or four times at first.
(Use ester oil or ether oil.)

• See the following table for tightening torque. (Applying too much 

torque may cause the flares to crack.)

• After connecting all the pipings perform a gas leak check by using 

nitrogen.

• If you are obliged to install the unit without a torque wrench, you may 

follow the installation method mentioned below. 
After the work is finished, make sure to check that there is no gas leak.

• When you keep on tightening the flare nut with a spanner, there is a 

point where the tightening torque suddenly increases. 
From that position, further tighten the flare nut the angle shown below.

Disposal requirements

Dismantling of the unit,  treatment of the refrigerant, oil and eventual
other parts should be comply the relevant local and national regulations.

6-4 Refrigerant piping work procedure

The field piping can be connected in four directions.

When connecting the piping in the lateral direction (on the rear),    
remove the piping cover (rear) and receiver mounting plate in refer-
ence to the figure below.

When connecting the pipings downward, remove the knockout by 
making four holes in the middle on the each side of the knockout with 
a drill.

Then cut out the corner of the bottom frame along the slits (in two 
positions) by using a hacksaw.

After removing the parts, it is recommended to apply repair paint on 
the edges, to prevent rusting.

• Make sure that the field pipings do 

not touch the terminal cover of the 
compressor.
Especially when the insulation pro-
vided on the liquid piping touches 
the terminal cover, adjust it’s height 
as shown in the  right figure.  Make 
sure also that the piping does not 
touch the bolts of the compressor 
and the outer panels.

• When it is expected that water con-

densed in the stop valve will reach 
the indoor unit through the gap 
between the heat insulating material 
and the piping (for example, when 
the outdoor unit is installed in a 
higher position than the indoor unit), 
take proper action such as caulking 
the connection area.

Pipe size

Tightening

torque (ft·lbf)

Flare dimension A (in.)

Flare shape (in.)

φ

3/8”

24.1 - 29.4

0.504 - 0.520

φ

5/8”

45.6-55.6

0.760 - 0.776

Pipe size

Tightening angle 

(Guideline)

Recommended arm 

length of tool (in.)

φ

 3/8”

60°~90°

Approx. 7 7/8

φ

 5/8”

30°~60°

Approx. 11 13/16

Location to

be brazed

Taping

Refrigerant

piping

Nitrogen

Regulator

Manual valve

Nitrogen

A

45

°

±2

°

90

°

±2

°

R0.016

~0.031

Refrigerant oil

Cautions on connecting the connection piping

Piping cover

Screw for

front panel

Screw for piping

cover (front)

Front

panel

Lateral

direction

Front direction

Rear

direction

Downward

direction

Receiver mounting plate

Piping cover (rear)

Field pipings

Bottom frame

Knockout

Drill

Slit

Middle on the side

Slit

Terminal cover

 Insulation

Bolt

Caulking, etc.

Compressor

Liquid piping

01_EN_3PN05597-5R.fm  Page 9  Wednesday, September 14, 2005  8:35 PM

Summary of Contents for RZQ24MVJU

Page 1: ...instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner SPLIT SYSTEM Air Conditioners INSTALLATION MANUAL 00_CV_3PN05597 5R fm Page 1 Friday September 2 2005 4 06 PM ...

Page 2: ...h by suffocation WARNING Ask your dealer or qualified personnel to carry out installation work Do not try to install the machine by yourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may result in water leakage electric shocks or fire Be sure to use only the specified accesso...

Page 3: ...revent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause mal functions smoke or fire Please instruct the customer to keep the area around the unit clean NOTE Install the indoor and outdoor units power supply wiring and transmission wiring at least 3 5ft away from televisions or radios in order to prevent image interference or n...

Page 4: ... is deteriorated The adhered frost increases during heating operation The operation is stopped by pressure rise If excessive strong wind continuously blows from the air outlet side of the outdoor unit the fan may rotate in the reverse direction at high speed and lead to damage Install the outdoor unit in ref erence to the following figures Position the air outlet side toward the building wall fenc...

Page 5: ...ruction is present on the both sides 2 When two or more outdoor units are installed side by side When an obstruction is present on the both sides When an obstruction is present also in the upward area 1 When one outdoor unit is installed individually When an obstruction is present also on the air inlet side When an obstruction is present also on the air inlet side and both sides 2 When two or more...

Page 6: ... L and A is as shown in the table below NOTE 1 Close the area under the frame so that the outlet air does not bypass there 2 Only two outdoor units can be installed side by side Pattern 2 When an obstruction on the air outlet side is lower than the outdoor unit There is no restriction in the height of obstruction on the air inlet side When the upward area is open 1 When one outdoor unit is install...

Page 7: ...unit so that the outlet air does not bypass there 2 When an obstruction is present on the air inlet side NOTE 1 Only two outdoor units can be stacked 2 About 4 in is required as the drain piping size for the upper out door unit 3 Close the area Z gap between the upper outdoor unit and the lower outdoor unit so that the outlet air does not bypass there E When outdoor units are installed in rows on ...

Page 8: ...ion Flux containing fluorine will damage refrigerant oil NOTE Maximum piping length between the outdoor and indoor unit is 230ft Installation tools Make sure to use installation tools gauge manifold charge hose etc that are exclusively used for R410A installations to withstand the pressure and to prevent foreign materials e g mineral oils such as SUNISO and moisture from mixing into the system The...

Page 9: ...gure below When connecting the pipings downward remove the knockout by making four holes in the middle on the each side of the knockout with a drill Then cut out the corner of the bottom frame along the slits in two positions by using a hacksaw After removing the parts it is recommended to apply repair paint on the edges to prevent rusting Make sure that the field pipings do not touch the terminal...

Page 10: ...ump for 1 hour to achieve 14 6 psi or less vacuum drying If the vacuum pressure does not reach 14 6 psi or less even after evacuation for 2 hours or more repeat vacuum break and vacuum dry ing Leave the air conditioner in the vacuum status for 1 hour or more and confirm that the vacuum pressuree indicated by the vacuum gauge does not increase 6 7 Additional refrigerant charge WARNING To avoid inju...

Page 11: ...g rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death WARNING Disconnect all power to unit to avoid possible electric shock during installation Use only specified wire and connect wires to terminals tightly Be careful that wires do not plac...

Page 12: ...al noise and malfunction or fail Be sure to connect the power supply wiring to the terminal block and secure it as described in 7 3 Power supply wiring connection procedure Fix the wiring between the units in accordance with 7 4 Transmission wiring connection procedure Secure the wirings with the clamps accessory so that do not touch the piping Make sure the wirings will not be pinched by the fron...

Page 13: ...tions below If they are not observed transmission error may occur Maximum wiring length 3280 ft Never connect 208 230V to the terminal block for the transmission wiring Doing so will break the entire system The transmission wiring from the indoor unit must be connected to the F1 F2 TO IN D UNIT terminals on the PC board in the outdoor unit Make sure to use sheathed two core cables of AWG18 16 in t...

Page 14: ...ck operation the status of the outdoor unit is checked and incorrect wiring is checked for Make sure to turn on the power 6 hours before starting operation for supplying the power to the crankcase heater Caution One outdoor unit installed H1P H5P H4P H6P H7P H2P H3P HAP Blinking ON OFF LED display LED display Default status before delivery Donotleaveanyshutoff valveclosed Otherwisethecompressor wi...

Page 15: ...lled a malfunction code U3 is displayed In this case perform the check operation by referring to 9 1 Power on and check operation Check a malfunction code in the remote controller connected to the indoor unit When a malfunction code is displayed in the remote controller Malfunction code Cause Solution E3 The stop valves in the outdoor unit remain closed Open the stop valve on both the gas and liqu...

Page 16: ... lb of the refrigerant gas in 1ft 3 volume of the occupied space Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the maximum concentration level in accor...

Page 17: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 0510 HT 3PN05597 5R EM04A040B 00_CV_3PN05597 5R fm Page 2 Friday September 2 2005 4 06 PM ...

Reviews: