6
(2)When two or more outdoor units are installed side by side
(C) When an obstruction is present on both the air inlet and air out-
let sides
<Pattern 1>
When an obstruction on the air outlet side is higher than the outdoor unit
(There is no restriction in the height of obstruction on the air inlet side.)
•
When the upward area is open
(1)When one outdoor unit is installed individually
(2)When two or more outdoor units are installed side by side
•
When an obstruction is present also in the upward area
(1)When one outdoor unit is installed individually
The dimensional relationship between H, L and A is as shown in the
table below.
NOTE
• Close the area under the frame so that the outlet air does not bypass
there.
(2)When only two outdoor units are installed side by side
The dimensional relationship between H, L and A is as shown in the
table below.
NOTE
1. Close the area under the frame so that the outlet air does not
bypass there.
2. Only two outdoor units can be installed side by side.
<Pattern 2>
When an obstruction on the air outlet side is lower than the outdoor unit
(There is no restriction in the height of obstruction on the air inlet side.)
•
When the upward area is open
(1)When one outdoor unit is installed individually
(2)When two or more outdoor units are installed side by side
The dimensional relationship between H, L and A is as shown in the
table below.
L
A
L
≤
H
0
L
≤
1/2H
30
1/2H
L
≤
H
40
H
L
Install the frame to achieve “L
≤≤≤≤
H”.
40
or
more
40 or
more
20 or
less
L
4 or
more
H
20 or
more
L>H
12 or
more
H
L
40 or
more
L>H
L
A
20 or
less
40
or
more
10 or
more
H
L
A
L
≤
H
0
L
≤
1/2H
40
1/2H
L
≤
H
50
H
L
Install the frame to achieve “L
≤≤≤≤
H”.
L
A
0
L
≤
1/2H
10
1/2H
L
≤
H
12
A
H
L
20 or
less
12 or
more
40
or
more
L
≤
H
4 or
more
20 or
more
H
L
L
60 or
more
H
A