4P485928-1 – 2017.04

7

Technical data

subset

  of  the  latest  technical  data  is  available  on  the  regional  Daikin  website  (publicly  accessible).  The 

full  set

  of  latest  technical  data  is

available on the Daikin extranet (authentication required).

7.1

Overview: Technical data

This chapter contains information about:
• Service space
• Piping diagram
• Wiring diagram

7.2

Service space: Outdoor unit

Suction side

In the illustrations below, the service space at the suction side is based on 35°C DB and cooling operation. Foresee
more space in the following cases:

▪ When the suction side temperature regularly exceeds this temperature.

▪ When the heat load of the outdoor units is expected to regularly exceed the maximum operating capacity.

Discharge side

Take refrigerant piping work into account when positioning the units. If your layout does not match with any of the
layouts below, contact your dealer.

Single unit (

) | Single row of units (

)

See figure 1 on the inside of the front cover.

A,B,C,D

Obstacles (walls/baffle plates)

E

Obstacle (roof)

a,b,c,d,e

Minimum service space between the unit and obstacles A, B, C, D and E

e

B

Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle B

e

D

Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle D

H

U

Height of the unit

H

B

,H

D

Height of obstacles B and D

1

Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit.

2

Maximum two units can be installed.
Not allowed

Multiple rows of units (

)

See figure 2 on the inside of the front cover.

Stacked units (max. 2 levels) (

)

See figure 3 on the inside of the front cover.

A1=>A2

(A1) If there is danger of drainage dripping and freezing between the upper and lower units…
(A2) Then install a 

roof

 between the upper and lower units. Install the upper unit high enough above the lower unit to prevent ice buildup at the

upper unit's bottom plate.

B1=>B2

(B1) If there is no danger of drainage dripping and freezing between the upper and lower units…
(B2) Then it is not required to install a roof, but 

seal the gap

 between the upper and lower units to prevent discharged air from flowing back to the

suction side through the bottom of the unit.

Summary of Contents for RZASG71M2V1B

Page 1: ...Installation manual Sky Air Advance series English Installation manual Sky Air Advance series RZASG71M2V1B RZASG100M7V1B RZASG125M7V1B RZASG140M7V1B RZASG100M7Y1B RZASG125M7Y1B RZASG140M7Y1B...

Page 2: ...A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB H...

Page 3: ...difi es Richtlijnen zoals geamendeerd Directivas seg n lo enmendado Direttive come da modifica Directivas conforme altera o em 10 11 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f ret...

Page 4: ...astaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota T...

Page 5: ...ltera o em 10 11 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smje...

Page 6: ...PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplo...

Page 7: ...To check the insulation resistance of the compressor 15 5 Commissioning 15 5 1 Checklist before commissioning 15 5 2 To perform a test run 16 5 3 Error codes when performing a test run 17 6 Disposal...

Page 8: ...mm 150 6 2 0 350 3 4 5 3 5 5 4 M12 a a Make sure not to cover the drain holes of the bottom plate of the unit INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 N...

Page 9: ...ce cover a with screw b Remove the piping intake plate c with screw d c a b d 2 Choose a piping route a b c or d a b c d 3 If you have chosen the downwards piping route Drill a 4 and remove the knocko...

Page 10: ...at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test solution to all connections 3 Discharge all nitr...

Page 11: ...ying or recharging activate field setting vacuum mode After finishing vacuum drying or recharging deactivate field setting vacuum mode WARNING Some sections of the refrigerant circuit may be isolated...

Page 12: ...140 b Only for RZASG100 125 2 Determine the additional refrigerant amount R R1 R2 Examples Layout Additional refrigerant amount R L2 7 m 6 4 mm L3 5 m 6 4 mm L1 35 m 9 5 mm RZASG100 Case Twin standard...

Page 13: ...deactivate the vacuum mode field setting on page 12 2 Connect the refrigerant cylinder to the service port of the liquid stop valve 3 Open the liquid stop valve 4 Charge the complete refrigerant amou...

Page 14: ...connect the electrical wiring on the outdoor unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover Make sure the electrical wiring does NOT obstruct...

Page 15: ...nsulation resistance of the compressor NOTICE If after installation refrigerant accumulates in the compressor the insulation resistance over the poles can drop but if it is at least 1 M then the unit...

Page 16: ...lit For any other action it needs to be lit first The backlight is lit for 30 seconds when you press a button 1 Perform introductory steps Action 1 Open the liquid stop valve A and gas stop valve B b...

Page 17: ...f the three electrical wires L4 The air inlet or air outlet is blocked U0 The stop valves are closed U2 There is a voltage imbalance There is a missing phase in case of three phase power supply units...

Page 18: ...acles walls baffle plates E Obstacle roof a b c d e Minimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction...

Page 19: ...for See note See note Outdoor Outdoor Indoor Indoor Upper Upper Lower Lower Fan Fan ON ON OFF OFF 2 Layout English Translation Layout Layout Front Front Back Back Position of compressor terminal Posi...

Page 20: ...Earth leakage circuit breaker 30 mA Q1E Overload protection R1 R8 A1P Y1 only Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger R5T Thermistor...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P485928 1 2017 04 Copyright 2017 Daikin 4P485928 1 0000000Y...

Reviews: