9 Technical data
Installation and operation manual
26
RXYTQ8~16T7YF
VRV IV system air conditioner
4P388987-1C – 2016.02
ABCD
Sides along the installation site with obstacles
F
Sides along the installation site with obstacles
Suction side
▪ In case of an installation site where sides A+B+C+D have
obstacles, the wall heights of sides A+C have no impact on
service space dimensions. Refer to the figure above for impact of
wall heights of sides B+D on service space dimensions.
▪ In case of an installation site where only the sides A+B have
obstacles, the wall heights have no influence on any indicated
service space dimensions.
▪ The installation space required on these drawings are for full load
heating operation without considering possible ice accumulation. If
the location of the installation is in a cold climate, then all
dimensions above should be >500 mm to avoid accumulation of
ice in between the outdoor units.
INFORMATION
The service space dimensions in above figure are based
on cooling operation at 46°C ambient temperature
(standard conditions).
INFORMATION
Further specifications can be found in the technical
engineering data.
9.2
Piping diagram: Outdoor unit
Piping diagram: RXYTQ8
R3T
R6T
R5T
R7T
R1T
R4T
R21T
h
g
f
p
d
b
l
e
k
j
i
a
c
o
n
m
INV
M
sv
sv
M1C
M1F
(S1NPL)
(S1NPH)
(S1PH)
HPS
a
Compressor (M1C)
b
Heat exchanger
c
Fan
d
Fan motor (M1F)
e
Accumulator
f
Expansion valve, main (Y1E)
g
Expansion valve, subcool heat exchanger (Y2E)
h
Subcool heat exchanger
i
Oil separator
j
Solenoid valve, oil1 (Y3S)
k
Solenoid valve, oil accumulator (Y2S)
l
4‑way valve, main (Y1S)
m
Service port, refrigerant charge
n
Stop valve (liquid)
o
Stop valve (gas)
p
Service port
Piping diagram: 12
R3T
R6T
R5T
R7T
R4T
R21T
h
g
f
p
l
e
k
j
i
a
o
n
m
INV
sv
sv
M1C
(S1NPL)
(S1NPH)
(S1PH)
HPS
R8T
b
d
c
c
d
M
M1F
M
M2F
R1T
a
Compressor (M1C)
b
Heat exchanger
c
Fan
d
Fan motor (M1F, M2F)
e
Accumulator
f
Expansion valve, main (Y1E)
g
Expansion valve, subcool heat exchanger (Y2E)
h
Subcool heat exchanger
i
Oil separator
j
Solenoid valve, oil1 (Y3S)
k
Solenoid valve, oil accumulator (Y2S)
l
4‑way valve, main (Y1S)
m
Service port, refrigerant charge
n
Stop valve (liquid)
o
Stop valve (gas)
p
Service port
Summary of Contents for RXYTQ8T7YF