background image

5 Installation

Installation and operation manual

15

RXYTQ8~16T7YF
VRV IV system air conditioner
4P388987-1C – 2016.02

5.6.5

To charge refrigerant

Follow the steps as described below.

Pre-charging refrigerant

1

Calculate the additional amount of refrigerant to be added using
the  formula  mentioned  in 

"5.6.3  To  determine  the  additional

refrigerant amount" on page 13

.

2

The  first  10  kg  of  additional  refrigerant  can  be  pre-charged
without outdoor unit operation.

If

Then

The additional refrigerant amount
is smaller than 10 kg

Perform steps 2+3.

The additional refrigerant charge
is larger than 10 kg

Perform steps 2~8.

3

Pre-charging  can  be  done  without  compressor  operation,  by
connecting the refrigerant bottle to the service ports of the liquid
and equalising stop valves (open valve B). Make sure that valve
A and all outdoor unit stop valves are closed.

NOTICE

During pre-charging, the refrigerant is charged through the
liquid line. Close valve A and disconnect the manifold from
the gas line.

p< p>

R410A

N2

C

b

c

e

a

g

f

d

A

B

a

Pressure reducing valve

b

Nitrogen

c

Weighing scales

d

Refrigerant R410A tank (siphon system)

e

Vacuum pump

f

Liquid line stop valve

g

Gas line stop valve

A

Valve A

B

Valve B

C

Valve C

4

Do one of the following:

If

Then

4a

The calculated additional
refrigerant amount is reached
by above pre-charging
procedure

Close valves C and B and
disconnect the manifold
connection to the liquid line.

4b

The total amount of
refrigerant could not be
charged by pre-charging

Close valves C and B,
disconnect the manifold
connection to the liquid line,
and perform steps 4~8.

INFORMATION

If  the  total  additional  refrigerant  amount  was  reached  in
step  3  (by  pre-charging  only),  record  the  amount  of
refrigerant  that  was  added  on  the  additional  refrigerant
charge  label  provided  with  the  unit  and  attach  it  on  the
back side of the front panel.

Perform 

the 

test 

procedure 

as 

described 

in

"7 Commissioning" on page 21

.

Charging refrigerant

5

After  pre-charging,  connect  valve  A  to  the  refrigerant  charge
port and charge the remaining additional refrigerant through this
port.  Open  all  outdoor  unit  stop  valves.  At  this  point,  valve  A
must remain closed!

p< p>

R410A

a

c

d

b

A

a

Weighing scales

b

Refrigerant R410A tank (siphon system)

c

Vacuum pump

d

Refrigerant charge port

A

Valve A

INFORMATION

For  a  multi  outdoor  unit  system,  it  is  not  required  to
connect all charge ports to a refrigerant tank.

The  refrigerant  will  be  charged  with  ±22  kg  in  1  hour  time
at an outdoor temperature of 30°C DB or with ±6 kg at an
outdoor temperature of 0°C DB.

If  you  need  to  speed  up  in  case  of  a  multiple  outdoor
system, connect the refrigerant tanks to each outdoor unit.

NOTICE

▪ The refrigerant charging port is connected to the piping

inside  the  unit.  The  unit's  internal  piping  is  already
factory  charged  with  refrigerant,  so  be  careful  when
connecting the charge hose.

▪ After  adding  the  refrigerant,  do  not  forget  to  close  the

lid  of  the  refrigerant  charging  port.  The  tightening
torque for the lid is 11.5 to 13.9 N•m.

▪ In  order  to  ensure  uniform  refrigerant  distribution,  it

may take the compressor ±10 minutes to start up after
the unit has started operation. This is not a malfunction.

6

Proceed with the manual charge.

INFORMATION

After charging refrigerant:

▪ Record  the  additional  refrigerant  amount  on  the

refrigerant  label  provided  with  the  unit  and  attach  it  to
the backside of the front panel.

▪ Perform 

the 

test 

procedure 

described 

in

"7 Commissioning" on page 21

.

5.6.6

Step 6: To manually charge refrigerant

INFORMATION

The manual refrigerant charge operation will automatically
stop  within  30  minutes.  If  charging  is  not  completed  after
30  minutes,  perform  the  additional  refrigerant  charging
operation again.

INFORMATION

▪ When  a  malfunction  is  detected  during  the  procedure

(e.g., in case of closed stop valve), a malfunction code
will  be  displayed.  In  that  case,  refer  to 

"5.6.7  Error

codes  when  charging  refrigerant"  on  page  16

  and

solve  the  malfunction  accordingly.  Resetting  the
malfunction  can  be  done  by  pushing  BS3.  The
procedure  can  be  restarted  from 

"5.6.6  Step  6:  To

manually charge refrigerant" on page 15

.

▪ Aborting  the  manual  refrigerant  charge  is  possible  by

pushing  BS3.  The  unit  will  stop  and  return  to  idle
condition.

Summary of Contents for RXYTQ8T7YF

Page 1: ...Installation and operation manual VRV IV system air conditioner English Installation and operation manual VRV IV system air conditioner RXYTQ8T7YF RXYTQ10T7YF RXYTQ12T7YF RXYTQ14T7YF RXYTQ16T7YF...

Page 2: ...iring Overview 16 5 7 2 Guidelines when knocking out knockout holes 16 5 7 3 To route and fix the transmission wiring 16 5 7 4 To connect the transmission wiring 17 5 7 5 To finish the transmission wi...

Page 3: ...AL SETTING 40 30 10 20 19 9 29 39 38 28 8 18 17 7 27 37 36 26 6 16 15 5 25 35 34 23 24 4 3 2 1 INSTALLATION MODELNAME No 12 13 14 50 49 48 47 46 45 60 59 58 57 56 64 63 62 61 11 22 21 33 32 31 44 43 4...

Page 4: ...nd in cooling mode at ambient temperatures from 5 C DB to 52 C DB 3 2 System layout NOTICE Design of the system must not be done at temperatures below 15 C e d c c b f a a VRV IV Heat pump outdoor uni...

Page 5: ...200 19 1 200 x 290 22 2 Indoor unit capacity index Piping outer diameter size mm Gas pipe Liquid pipe 290 x 420 28 6 12 7 420 x 640 15 9 640 x 920 34 9 19 1 920 41 3 Example Downstream capacity for E...

Page 6: ...HRQ22M64T 640 KHRQ22M75T Concerning refnet headers choose from the following table in accordance with the total capacity of all the indoor units connected below the refnet header Indoor unit capacity...

Page 7: ...adding the minimum circuit amps of each used unit according to the table above multiply the result by 1 1 and select the next higher recommended fuse capacity Example Combining the RXYTQ30 by using t...

Page 8: ...stallation is on a solid longitudinal foundation steel beam frame or concrete The foundation must be larger than the grey marked area 729 613 929 AB AA a mm Minimum foundation a Anchor point 4 HP AA A...

Page 9: ...abel a attached to the joint comes to the top Do not tilt the joint more than 7 5 see view A Do not install the joint vertically see view B a a A B 7 5 7 5 a Caution label X Not allowed O Allowed Make...

Page 10: ...o close Shaft Valve body Hexagonal wrench Cap valve lid Service port 9 5 5 4 6 6 4 mm 13 5 16 5 11 5 13 9 12 7 8 1 9 9 18 0 22 0 15 9 13 5 16 5 6 mm 23 0 27 0 19 1 27 0 33 0 8 mm 22 5 27 5 25 4 5 3 7...

Page 11: ...ait until the outdoor unit has finished the initialisation to apply setting 2 21 Leak test and vacuum drying Checking the refrigerant piping involves Checking for any leakages in the refrigerant pipin...

Page 12: ...Should you fail to reach the target vacuum within 2 hours or maintain the vacuum for 1 hour the system may contain too much moisture In that case break the vacuum by pressurising with nitrogen gas to...

Page 13: ...e see 5 6 5 To charge refrigerant on page 15 It can be skipped but charging will take longer then A flow chart is available which gives an overview of the possibilities and actions to be taken see 5 6...

Page 14: ...refrigerant charge label Go to test run Step 3b Close valves C and B R Q R Q R Q Continued on next page p p R410A N2 C A B Charging refrigerant Step 5 Proceed with manual charge Step 6 Activate field...

Page 15: ...harge port and charge the remaining additional refrigerant through this port Open all outdoor unit stop valves At this point valve A must remain closed p p R410A a c d b A a Weighing scales b Refriger...

Page 16: ...n knocking out knockout holes To punch a knockout hole hit on it with a hammer After knocking out the holes we recommend removing any burrs and paint the edges and areas around the holes using repair...

Page 17: ...tion The wiring for the other systems must be connected to the F1 F2 Out Out terminals of the PCB in the outdoor unit to which the interconnecting wiring for the indoor units is connected The base uni...

Page 18: ...e push buttons it is possible to Perform special actions testrun etc Perform field settings demand operation low noise etc DIP switches By operating the DIP switches it is possible to DS1 1 COOL HEAT...

Page 19: ...ndoor units When the communication between indoor units and outdoor unit s is established and normal the 7 segment display indication state will be as below default situation when shipped from factory...

Page 20: ...or units 1 13 Shows the total number of connected outdoor units in case of multiple outdoor system 1 17 1 18 1 19 Shows 1 17 The latest malfunction code 1 18 The 2nd last malfunction code 1 19 The 3rd...

Page 21: ...n the installer and user reference guide Installation Check that the unit is properly installed to avoid abnormal noises and vibrations when starting up the unit Field wiring Be sure that the field wi...

Page 22: ...r 2 on page 19 Push BS2 for 5 seconds or more The unit will start test operation Result The test operation is automatically carried out the outdoor unit display will indicate and the indication Test o...

Page 23: ...n on PCB or actuator Discharge temperature too high R21T R22T Stop valve closed Refrigerant shortage Open stop valves Check refrigerant amount recharge unit Compressor casing temperature too high R8T...

Page 24: ...tion Transmission outdoor unit inverter INV2 transmission trouble A1P X20A X28A X40A Check connection INV1 unbalanced power supply voltage Check if power supply is within range INV2 unbalanced power s...

Page 25: ...ered unit amount by monitor mode or wait till initialisation is finished Stop valve closed or wrong during system test run Open stop valves 9 Technical data Latest information can be found in the tech...

Page 26: ...based on cooling operation at 46 C ambient temperature standard conditions INFORMATION Further specifications can be found in the technical engineering data 9 2 Piping diagram Outdoor unit Piping dia...

Page 27: ...L S1PH S2PH HPS R6T R5T R7T R1T R4T R21T R22T R3T HPS n a Compressor M1C b Compressor M2C c Heat exchanger d Fan e Fan motor M1F M2F f Accumulator g Expansion valve main Y1E h Expansion valve subcool...

Page 28: ...e found in the technical engineering data 12 2 Operating the system 12 2 1 About operating the system Operation procedure varies according to the combination of outdoor unit and user interface To prot...

Page 29: ...m temperature is low 20 C 12 3 2 To use the dry program WITHOUT cool heat changeover remote control switch To start 1 Press the operation mode selector button on the user interface several times and s...

Page 30: ...interface Only the master user interface can select heating or cooling mode 13 Maintenance and service NOTICE Never inspect or service the unit by yourself Ask a qualified service person to perform th...

Page 31: ...tify your installer and report the malfunction code If the system does not properly operate except for the above mentioned cases and none of the above mentioned malfunctions is evident investigate the...

Page 32: ...r units combined Indoor unit malfunction Connection malfunction over indoor units or type mismatch Centralised address duplication Malfunction in communication centralised control device indoor unit A...

Page 33: ...topped When another indoor unit is in operation this noise is heard In order to prevent oil and refrigerant from remaining in the system a small amount of refrigerant is kept flowing 14 2 10 Symptom N...

Page 34: ......

Page 35: ......

Page 36: ...4P388987 1 C 0000000F 4P388987 1C 2016 02 Copyright 2015 Daikin...

Reviews: