![background image](http://html1.mh-extra.com/html/daikin/rxysq-p8y1/rxysq-p8y1_technical-data-manual_2459971006.webp)
• Outdoor Unit • VRVIII-S heat pump • RXYSQ-P8Y1
1
2
• VRV Systems • Outdoor Unit
4
2
Specifications
Standard Accessories : Connection pipes; Quantity : 3;
Standard Accessories : Operation manual; Quantity : 1;
Standard Accessories : Installation manual; Quantity : 1;
Compressor
Quantity
1
Model
JT1G-VDLYR
Type
Hermetically sealed scroll compressor
Speed
rpm
6,480
Output
W
2,500
3,000
3,500
Starting method
Direct on line
Crankcase heater
W
33
Operation range
Cooling
Min.~Max.
ºCDB
-5~46
Heating
Min.~Max.
ºCWB
-20~15.5
Refrigerant
Type
R-410A
Charge
kg
4.0
Control
Expansion valve
Circuits
Quantity
1
Refrigerant oil
Type
Daphne FVC68D
Charged volume
l
1.5
Piping connections
Liquid
Type
Flare connection
OD
mm
9.52
Gas
Type
Flare connection (VRV®) / Braze
connection (RA)
Flare connection (VRV®) / Braze
connection (RA)
Braze connection
OD
mm
15.9 (6) / 19.1 (7)
15.9 (6) / 19.1 (7)
19.1
Drain
Quantity
3
OD
mm
26x3
Heat insulation
Both liquid and gas pipes
Piping length
OU -
BP
Total
m
55 (7)
BP - IU Max.
m
15 (7)
Total
m
60 (7)
80 (7)
90 (7)
Total piping length
System Actual
m
300 (6) / 115 (7)
300 (6) / 135 (7)
300 (6) / 145 (7)
Level difference
OU - IU Outdoo
r unit in
highest
position
m
-
Indoor
unit in
highest
position
m
-
Defrost method
Reversed cycle
Defrost control
Sensor for outdoor heat exchanger temperature
Safety devices
Item
01
HPS
02
Fan motor thermal protection
03
Inverter overload protector
04
PC board fuse
PED
Category
Category I
2-2 Electrical Specifications
RXYSQ4P8Y1
RXYSQ5P8Y1
RXYSQ6P8Y1
Power supply
Name
Y1
Phase
3N~
Frequency
Hz
50
Voltage
V
380-415
Voltage range
Min.
%
-10
Max.
%
10
Current
Nominal running
current (RLA) - 50Hz
Cooling
A
5.30
6.77
7.79
2-1 Technical Specifications
RXYSQ4P8Y1
RXYSQ5P8Y1
RXYSQ6P8Y1
Summary of Contents for RXYSQ-P8Y1