3
1
2
• VRV Systems • Outdoor Unit
5
• Outdoor Unit • VRVIII-S heat pump • RXYSQ-P8Y1
2
Specifications
Notes
(1) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m
(2) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m
(3) Sound power level is an absolute value that a sound source generates.
(4) Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
(5) Sound values are measured in a semi-anechoic room.
(6) In case VRV® indoor units are connected
(7) In case RA indoors are connected
(8) RLA is based on following conditions: indoor temp. 27ºCDB, 19ºCWB; outdoor temp. 35ºCDB
(9) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(10) Maximum allowable voltage range variation between phases is 2%.
(11) Select wire size based on the value of MCA
(12) Instead of a fuse, use a circuit breaker
(13) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
(14) MSC means the maximum current during start up of the compressor
(15) EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input
current \> 16A and
≤
75A per phase
(16) Ssc: Short-circuit power
Current - 50Hz
Maximum running current
A
13.5
Starting current (MSC)
A
5.30
6.77
7.79
Zmax
List
No requirements
Minimum circuit amps (MCA)
A
13.5
Maximum fuse amps (MFA)
A
16.0
Full load amps
(FLA)
Fan motor
A
0.3
Fan motor 2
A
0.3
Wiring connections -
50Hz
For power supply
Quantity
5
Remark
Earth wire included
For connection with
indoor
Quantity
2
Remark
F1,F2
Power supply intake
Both indoor and outdoor unit
Field earth leakage breaker
mA
300
2-2 Electrical Specifications
RXYSQ4P8Y1
RXYSQ5P8Y1
RXYSQ6P8Y1