Wiring diagrams
8 - 1 Wiring Diagrams - Three Phase
RXYSQ-P8Y1
Cool/Heat selector
HAP (A2P)
Light emitting diode (service monitor green)
R5T
Thermistor (suction 2)
S1S
Selector switch (fan / cool - heat)
K1M(A1P)
Magnetic contactor
R6T
Thermistor (heat exchanger)
S2S
Selector switch (cool - heat)
K1R
Magnetic relay (Y1S)
R7T
Thermistor (liquid 1)
Connector of option adaptor
K2R
Magnetic relay (Y2S)
R8T
Thermistor (liquid 2)
X37A
(note 4)
Connector
(option adaptor power supply)
K3R
Magnetic relay (Y3S)
R9T
Thermistor (power module)
K4R
Magnetic relay (E1HC)
S1NPH
Pressure sensor (high)
L1~RED
L2-WHT
L3-BLK
N-BLU
K5R, K6R
Magnetic relay
S1PNL
Pressure sensor (low)
A1P
Printed circuit board (main)
L1R
Reactor
S1PH
Pressure switch (high)
A2P
Printed circuit board (inv.)
M1C
Motor (compressor)
V1R
Power module
BS1~BS5
Push button switch (mode, set, return, test, reset) M1F
Motor (fan) (upper)
V2R, V3R
Diode module
C1~C3
Capacitor
M2F
Motor (fan) (lower)
X1M
Terminal strip (power supply)
DS1-1
DS1-2
Dip switch
PS
Switching power supply
X2M
Terminal strip (control) (C/H selector)
Q1DI
Field earth leakage breaker (300mA)
Y1E
Electronic expansion valve (main)
E1HC
Crankcase heater
R1(A1P)
Resistor
Y3E
Electronic expansion valve (subcool)
F1, 3, 4U
(A1P)
Fuse (T 6,3A / 250V)
R1(A2P)
R2(A2P)
Resistor
Y1S
Solenoid valve (4 way valve)
Y2S
Solenoid valve (hot gas)
H1P~H8P
Light emit. diode (serv. monitor-orange)
[H2P] Prepare, test -------------- flickering
Malfunction detection --- light up
R1T
Thermistor (air)
Y3S
Solenoid valve (U/L circuit)
R2T
Thermistor (M1C discharge)
Z1C~Z4C
Noise filter (ferrite core)
R3T
Thermistor (suction 1)
Z1F
Noise filter (with surge absorbed)
HAP (A1P)
Light emitting diode (service monitor green)
R4T
Thermistor (subcool)
Z2F
Noise filter
NOTES
1. This wiring diagram only apllies to the outdoor unit.
2. L: Live, N: Neutral
: Field wiring
3.
: Terminal strip
: Connector
: Movable connector
: Movable connector
: Protective earth (screw)
: Noiseless earth
: Terminal
4. When using the option adapter, refer to the installation manual
5. Refer to the ‘Installation or service manual’ on how to use BS1 ~ BS5 push button switch and DS1-1, DS1-2 dip switch.
6. Do not operate the unit by short-circuiting protection device S1PH.
7. Colors: BLU = BLUE, BRN = BROWN, GRN = GREEN, RED = RED, WHT = WHITE, YLW = YELLOW, ORG = ORANGE, BLK = BLACK.
8. Refer to the installation manual for connection wiring to indoor - outdoor transmission F1-F2.
9. When using the central control system, connect outdoor-outdoor transmission F1-F2.
2TW29226-1B
Position of
compressor
terminal
Wire entrance
outdoor
COOL
AIR CONTROL
(NOTE 8)
INDOOR
(F1) (F2)
(NOTE 9)
OUTDOOR
(F-1) (F2)
FAN
C/H
SELECTOR
TO IN/D UNIT
TO OUT/D UNIT
EL. COMPO ASSY FRONT
VIEW A
( NOTE 4)
HEAT
S2S
S1S