Outdoor Unit Installation

3. 

Flaring the pipe end 

1)  Cut the pipe end with a pipe cutter.
2)  Remove burrs with the cut surface facing  

downward so that the chips do not enter the pipe.

3)  Put the flare nut on the pipe.
4)  Flare the pipe.
5)  Check that the flaring is properly made.

   WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.

4. 

Refrigerant piping

   CAUTION

• Use the flare nut fixed to the main unit to prevent it from cracking and deteriorating from age.
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

Flare nut tightening torque

Liquid side

1/4 inch (6.4mm)

10.4-12.7ft • lbf

(14.2-17.2N • m)

Gas side

1/2 inch (12.7mm)

36.5-44.5ft • lbf

(49.5-60.3N • m)

Valve cap tightening torque

Liquid side

1/4 inch (6.4mm)

15.9-20.2ft • Ibf

(21.6-27.4N • m)

Gas side

1/2 inch (12.7mm)

35.5-44.0ft • Ibf

(48.1-59.7N • m)

Service port cap tightening torque

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration oil to 
the inner surface of the 

flare.

Do not apply refrigeration oil to 

the flare nut to avoid tightening 

with excessive torque.

[Apply oil]

• Align the centers of both flares and tighten the flare 

nuts 3 or 4 turns by hand. Then tighten them fully with 

the torque wrenches. 

7.9-10.8ft • lbf

(10.8-14.7N • m)

(Cut exactly at 

right angles.)

 Remove burrs.

Set exactly at the position shown below.

A

Flaring

Die

Check

Flare’s inner surface 

must be flaw-free.

The pipe end must 

be evenly flared in a 

perfect circle.

Make sure that the 

flare nut is fitted.

A

0-0.020 inch 

(0-0.5mm)

Clutch-type

Flare tool for R410A

0.039-0.059 inch 

(1.0-1.5mm)

Clutch-type (Rigid-type)

0.059-0.079 inch 

(1.5-2.0mm)

Wing-nut type (Imperial-type)

Conventional flare tool

01_EN_3P296778-1.indd   6

10/7/2011   8:44:52 AM

Summary of Contents for RXS15LVJU

Page 1: ...R410A Split series Fran ais Espa ol Manuel dinstallation S rie split R410A Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS15LVJU RXS18LVJU 00_CV_3P296778 1 i...

Page 2: ...gs so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk...

Page 3: ...e to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open...

Page 4: ...more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain f...

Page 5: ...t Min allowable piping length Max allowable piping length 98 4ft 30m 4 92ft 1 5m 65 6ft 20m Liquid pipe Gas pipe O D 1 4 inch 6 4mm O D 1 2 inch 12 7mm 0 21oz ft 20g m Additional refrigerant required...

Page 6: ...ndation drawing fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the f...

Page 7: ...e flare nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 1 2 inch 12 7mm 36 5 44 5ft lbf 49 5 60 3N...

Page 8: ...re gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not sw...

Page 9: ...should be as gentle as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation...

Page 10: ...rewdriver Forced cooling operation switch SW1 Push Wiring WARNING Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire...

Page 11: ...Observe the notes mentioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal board...

Page 12: ...Cut the jumper J6 of the PCB inside J5 J7 J8 J6 GND Top plate PCB Drip proof cover 1 Remove the 3 screws 2 Remove the drip proof cover 3 Cut jumper J6 CAUTION If the outdoor unit is installed where t...

Page 13: ...uires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circui...

Page 14: ...3P296778 1 M11B087 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P296778 1 indd 2 10 17 2011 2 44 16 PM...

Reviews: