Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1)  Remove the valve cap from liquid stop valve and gas stop  

valve.

2)  Carry out forced cooling operation.
3)  After 5 to 10 minutes, close the liquid stop valve with a  

hexagonal wrench.

4)  After 2 to 3 minutes, close the gas stop valve and stop forced  

cooling operation.

Forced cooling operation

 

Using the indoor unit ON/OFF switch

Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)

•  Forced cooling operation will stop automatically after around 15 minutes.  

To stop the operation, press the indoor unit ON/OFF switch.

 

Using the indoor unit’s remote controller

1)  Press “MODE” button and select the cooling mode.
2)  Press “ON/OFF” button to turn on the system.
3)  Press both of “TEMP” button and “MODE” button at the same time.
4)  Press “MODE” button twice. (   will be displayed and the unit will enter forced cooling operation.)

•  Forced cooling operation will stop automatically after around 30 minutes.  

To stop the operation, press “ON/OFF” button.

 

Using the outdoor unit forced cooling operation switch

Forced cooling operation can be performed when the outdoor unit forced cooling operation switch is pressed within 
around 3 minutes after power is supplied.

•  Push on “ 

 ” with a screwdriver. (The operation will start.)

•  Forced cooling operation will stop automatically after around 15 minutes. 

To stop the operation, press the switch (SW1).

1

2

3

Screwdriver

Forced cooling 
operation switch 
(SW1)

Push

Wiring

   WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Be sure to install a ground fault circuit interrupter breaker. (One that can handle higher harmonics.)  

(This unit uses an inverter, which means that it must be used a ground fault circuit interrupter breaker capable handling 
harmonics in order to prevent malfunctioning of the ground fault circuit interrupter breaker itself.)

• Use an all-pole disconnection type breaker with at least 1/8 inch (3mm) between the contact point gaps.
• When carrying out wiring connection, take care not to pull at the conduit.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Do not turn on the safety breaker until all work is completed.

1)  Strip the insulation from the wire (3/4inch (20mm)).
2)  Connect the connection wires between the  

indoor and outdoor units so that the terminal  
numbers match. Tighten the terminal screws  
securely. We recommend a flathead  
screwdriver be used to tighten the screws. 

Gas stop valve

Valve cap

Hexagonal wrench

Close

Liquid stop valve

Service port

1

2

3

1 2 3

GR

L

1

L

2

Safety 

breaker 

20A

Ground fault

circuit interrupter

Ground

Use AWG16 if the connection wire 
length is less than 32.8ft (10m), or 
AWG14 if it is 32.8ft (10m) or more.

Outdoor unit

Indoor 
unit

Power supply
60Hz 208-230V

Use AWG 14 wires.

01_EN_3P296778-1.indd   9

10/7/2011   8:44:53 AM

Summary of Contents for RXS15LVJU

Page 1: ...R410A Split series Fran ais Espa ol Manuel dinstallation S rie split R410A Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS15LVJU RXS18LVJU 00_CV_3P296778 1 i...

Page 2: ...gs so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk...

Page 3: ...e to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open...

Page 4: ...more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain f...

Page 5: ...t Min allowable piping length Max allowable piping length 98 4ft 30m 4 92ft 1 5m 65 6ft 20m Liquid pipe Gas pipe O D 1 4 inch 6 4mm O D 1 2 inch 12 7mm 0 21oz ft 20g m Additional refrigerant required...

Page 6: ...ndation drawing fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the f...

Page 7: ...e flare nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 1 2 inch 12 7mm 36 5 44 5ft lbf 49 5 60 3N...

Page 8: ...re gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not sw...

Page 9: ...should be as gentle as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation...

Page 10: ...rewdriver Forced cooling operation switch SW1 Push Wiring WARNING Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire...

Page 11: ...Observe the notes mentioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal board...

Page 12: ...Cut the jumper J6 of the PCB inside J5 J7 J8 J6 GND Top plate PCB Drip proof cover 1 Remove the 3 screws 2 Remove the drip proof cover 3 Cut jumper J6 CAUTION If the outdoor unit is installed where t...

Page 13: ...uires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circui...

Page 14: ...3P296778 1 M11B087 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P296778 1 indd 2 10 17 2011 2 44 16 PM...

Reviews: