Installation Guidelines 

• Where a wall or other obstacle is in the path of outdoor unit’s inlet or outlet airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.

More than 

3-15/16 (100)

More than 

13-3/4 (350)

Side view

47-1/4

(1200)

or less

More than 

1-15/16 (50)

More than 

1-15/16 (50)

More than 

13-3/4 (350)

Top view

More than 

3-15/16 (100)

Top view

unit: inch (mm)

More than 3-15/16 (100)

More than 13-3/4 (350)

More than 

1-15/16 (50)

Wall facing one side

Walls facing two sides

Walls facing three sides

Precautions on Installation

• Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
• In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare 4 sets of M8 or M10 

foundation bolts, nuts and washers each which are available on the market.)

• It is best to screw in the foundation bolts until their ends are 3/4 inch (20mm) from the foundation surface.

3/4 inch 

(20mm)

Outdoor Unit Installation

1. 

Installing outdoor unit

1)  When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor Unit Installation Drawings”.
2)  If drain work is necessary, follow the procedures below.

2. 

Drain work

1)  Use drain plug for drainage.
2)  If the drain port is covered by a mounting base or floor surface, place  

additional foot bases of at least 1-1/4 inch (30mm) in height under the outdoor  
unit’s feet.

3)  In cold areas, do not use a drain hose with the outdoor unit.  

(Otherwise, drain water may freeze, impairing heating performance.)

Drain port

Bottom frame

Drain plug

Hose (available commercially,
inner dia. 5/8 inch (16mm))

01_EN_3P296778-1.indd   5

10/7/2011   8:44:52 AM

Summary of Contents for RXS15LVJU

Page 1: ...R410A Split series Fran ais Espa ol Manuel dinstallation S rie split R410A Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS15LVJU RXS18LVJU 00_CV_3P296778 1 i...

Page 2: ...gs so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk...

Page 3: ...e to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open...

Page 4: ...more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain f...

Page 5: ...t Min allowable piping length Max allowable piping length 98 4ft 30m 4 92ft 1 5m 65 6ft 20m Liquid pipe Gas pipe O D 1 4 inch 6 4mm O D 1 2 inch 12 7mm 0 21oz ft 20g m Additional refrigerant required...

Page 6: ...ndation drawing fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the f...

Page 7: ...e flare nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 1 2 inch 12 7mm 36 5 44 5ft lbf 49 5 60 3N...

Page 8: ...re gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not sw...

Page 9: ...should be as gentle as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation...

Page 10: ...rewdriver Forced cooling operation switch SW1 Push Wiring WARNING Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire...

Page 11: ...Observe the notes mentioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal board...

Page 12: ...Cut the jumper J6 of the PCB inside J5 J7 J8 J6 GND Top plate PCB Drip proof cover 1 Remove the 3 screws 2 Remove the drip proof cover 3 Cut jumper J6 CAUTION If the outdoor unit is installed where t...

Page 13: ...uires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circui...

Page 14: ...3P296778 1 M11B087 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P296778 1 indd 2 10 17 2011 2 44 16 PM...

Reviews: