Facility Setting
(cooling at low outdoor temperature)
This function is designed for facilities such as equipment or computer rooms. It is never to be used in a
residence or office where people occupy the space.
■
Cutting jumper 6 (J6) on the circuit board will expand the operation range down to 14°F (–10°C). However it will stop if
the outdoor temperature drops below –0.4°F (–18°C) and start back up once the temperature rises again.
1) Remove the 3 screws on the side and remove the top plate of the outdoor unit.
2) Remove the drip proof cover.
3) Cut the jumper (J6) of the PCB inside.
J5 J7 J8 J6
GND
Top plate
PCB
Drip proof cover
1) Remove the
3 screws.
2) Remove the drip
proof cover.
3) Cut jumper J6.
CAUTION
• If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
• Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
• Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used.
A humidifier might cause dew condensation from the indoor unit outlet vent.
• Cutting jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.