Wiring

<Work before wiring>

A protection plate is fixed for protection from the high-voltage section.
Before staring wiring work, dismount the protection plate by removing the 2 screws and dismount the conduit mounting cover by 
removing the 2 screws. 

<Method of mounting conduit>

1)  Pass wires through the conduit and secure them with a lock nut.
2)  After completing the work, reattach the conduit mounting cover and the protection plate to its original position.

1

2

3

1

2

3

Screw

Protection plate

Conduit 
mounting 
plate

Conduit 
1/2 inch (21.3mm)

Lock nut

Power supply
terminal block

Shape wires so 
that the protection 
plate and conduit 

mounting plate fit 

securely.

Observe the notes mentioned following when wiring to the power supply terminal board.
Precautions to be taken for power supply wiring. 

   CAUTION

• When connecting the connection wires to the terminal board 

using a single core wire, be sure to perform curling.  
Problems with the work may cause heat and fires. 

Strip wire end 
to this point.

Excessive strip length 

may cause electrical 

shock or leakage.

Good

Wrong

• If the stranded wires must be used, make sure to use the 

round crimp-style terminal for connection to the power 
supply terminal block. Place the round crimp-style 
terminals on the wires up to the covered part and secure in 
place.

Stranded wire

Round crimp-style

terminal

3)  Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop. 

Stripping wire at terminal block

Good

Wrong

01_EN_3P296778-1.indd   10

10/7/2011   8:44:54 AM

Summary of Contents for RXS15LVJU

Page 1: ...R410A Split series Fran ais Espa ol Manuel dinstallation S rie split R410A Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS15LVJU RXS18LVJU 00_CV_3P296778 1 i...

Page 2: ...gs so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk...

Page 3: ...e to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open...

Page 4: ...more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain f...

Page 5: ...t Min allowable piping length Max allowable piping length 98 4ft 30m 4 92ft 1 5m 65 6ft 20m Liquid pipe Gas pipe O D 1 4 inch 6 4mm O D 1 2 inch 12 7mm 0 21oz ft 20g m Additional refrigerant required...

Page 6: ...ndation drawing fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the f...

Page 7: ...e flare nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 1 2 inch 12 7mm 36 5 44 5ft lbf 49 5 60 3N...

Page 8: ...re gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not sw...

Page 9: ...should be as gentle as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation...

Page 10: ...rewdriver Forced cooling operation switch SW1 Push Wiring WARNING Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire...

Page 11: ...Observe the notes mentioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal board...

Page 12: ...Cut the jumper J6 of the PCB inside J5 J7 J8 J6 GND Top plate PCB Drip proof cover 1 Remove the 3 screws 2 Remove the drip proof cover 3 Cut jumper J6 CAUTION If the outdoor unit is installed where t...

Page 13: ...uires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circui...

Page 14: ...3P296778 1 M11B087 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P296778 1 indd 2 10 17 2011 2 44 16 PM...

Reviews: