background image

12

English

Trial Operation and Testing

1. 

Trial operation and testing

1-1 Measure the supply voltage and make sure that it falls in the specified range.

1-2 Trial operation should be carried out in either cooling or heating mode.

• In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable 

temperature.

1)  Trial operation may be disabled in either mode depending on the room temperature.
2)  After trial operation is complete, set the temperature to a normal level (78°F to 82°F (26°C to 28°C) in cooling mode, 

68°F to 75°F (20°C to 24°C) in heating mode).

3)  For protection, the system disables restart operation for 3 minutes after it is turned off.

1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts, 

such as fin movement, are working properly.

• The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for some 

time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation 

mode when the circuit breaker is opened again.

2. 

Test items

Test items

Symptom

Check

Indoor and outdoor units are installed properly on solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating 
function

Refrigerant gas and liquid pipes and indoor drain hose extension are 
thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly grounded.

Electrical leakage

The specified wires are used for inter-unit wiring.

Inoperative or burn damage

Indoor or outdoor unit’s air inlet or air outlet has clear path of air.  
Stop valves are opened.

Incomplete cooling/heating 
function

Indoor unit properly receives remote control commands.

Inoperative

01_EN_3P296778-1.indd   12

10/7/2011   8:44:54 AM

Summary of Contents for RXS15LVJU

Page 1: ...R410A Split series Fran ais Espa ol Manuel dinstallation S rie split R410A Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXS15LVJU RXS18LVJU 00_CV_3P296778 1 i...

Page 2: ...gs so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk...

Page 3: ...e to install a ground fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open...

Page 4: ...more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain f...

Page 5: ...t Min allowable piping length Max allowable piping length 98 4ft 30m 4 92ft 1 5m 65 6ft 20m Liquid pipe Gas pipe O D 1 4 inch 6 4mm O D 1 2 inch 12 7mm 0 21oz ft 20g m Additional refrigerant required...

Page 6: ...ndation drawing fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the f...

Page 7: ...e flare nuts to prevent damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 1 2 inch 12 7mm 36 5 44 5ft lbf 49 5 60 3N...

Page 8: ...re gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not sw...

Page 9: ...should be as gentle as possible Use a pipe bender for bending 7 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation...

Page 10: ...rewdriver Forced cooling operation switch SW1 Push Wiring WARNING Do not use tapped wires stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire...

Page 11: ...Observe the notes mentioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal board...

Page 12: ...Cut the jumper J6 of the PCB inside J5 J7 J8 J6 GND Top plate PCB Drip proof cover 1 Remove the 3 screws 2 Remove the drip proof cover 3 Cut jumper J6 CAUTION If the outdoor unit is installed where t...

Page 13: ...uires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circui...

Page 14: ...3P296778 1 M11B087 1111 HT Two dimensional bar code is a code for manufacturing 00_CV_3P296778 1 indd 2 10 17 2011 2 44 16 PM...

Reviews: