Si001275
Compressor
Removal Procedure
27
2
Disconnect the
compressor lead wires
and detach the
overload protector.
Be careful so as not to burn
the compressor terminals or
the name plate.
3
Remove the protecting
bushing.
4
Remove the 2 nuts.
5
Heat up the brazed part
of the discharge side
and disconnect.
Step
Procedure
Points
(R18774)
Overload protector
Compressor
lead wire
V (yellow)
U (red)
W (blue)
(R6031)
(R5897)
(R14033)
(R5899)