background image

English

6

5.

Purging air and checking gas leakage.

• When piping work is completed, it is necessary to purge the air and check for gas leakage.

 WARNING

1) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
2) When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
3) R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
4) Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum 

pump or the unit.

• If using additional refrigerant, perform air purging from the refrigerant pipes and 

indoor unit using a vacuum pump, then charge additional refrigerant.

• Use a hexagonal wrench (4mm) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified 

tightening torque.

*1. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists.  

Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.

2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).  

(High-pressure valve subsequently requires no operation.)

3) Do vacuum pumping and make sure that the compound pressure gauge reads –0.1MPa (–76cmHg).

(The vacuum pump should run for at least 10 min.)

4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump. 

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*1.

5) Remove covers from liquid stop valve and gas stop valve.

6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve. 

Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods. 
After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.

(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

Compound 
pressure gauge

Pressure 
meter

High-
pressure 
valve

Low-pressure 
valve

Vacuum pump 
adapter

Vacuum pump

Service port

Gas stop 
valve

Valve caps

Liquid stop valve

Charging 
hoses

Gauge 
manifold

01_EN_3P177302-2.fm  Page 6  Thursday, May 25, 2006  6:21 PM

Summary of Contents for RXR28EV1B

Page 1: ...V1B Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split syste...

Page 2: ...TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EM...

Page 3: ...or fire If any refrigerant has leaked out during the installation work ventilate the room The refrigerant produces a toxic gas if exposed to flames After all installation is complete check to make sur...

Page 4: ...they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Sinc...

Page 5: ...age 8 When laying the humidifying hose inside the wall block the ends of the humidifying hose with tape or the like to prevent water or anything else from entering it until it is connected to the indo...

Page 6: ...undation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If...

Page 7: ...them fully with the torque wrenches Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas 2 To prevent gas leakage apply refrigeration machine oil on...

Page 8: ...gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operati...

Page 9: ...to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the g...

Page 10: ...o the outdoor humidifying duct 2 Apply a binding band to prevent the humidifying hose from coming off 2 Connecting the cut humidifying hoses When installing the cut humidifying hoses follow the instru...

Page 11: ...m the wire 20mm 2 Connect the connection wires between the indoor and outdoor units so that the termi nal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used...

Page 12: ...ooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are ther mally insulated Water leakage Draining line is properly installed Water leakage System is properly ear...

Page 13: ...0605 HT 3P177302 2 M05B201...

Reviews: