Outdoor Unit Installation

6.

Refilling the refrigerant.

Check the type of refrigerant to be used on the machine nameplate.

Precautions when adding R410A
Fill from the liquid pipe in liquid form.

It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon 

attached” displayed on it.)

• Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.

7.

Refrigerant piping work.

7-1 Cautions on pipe handling. 

1)Protect the open end of the pipe against dust and moisture.
2)All pipe bends should be as gentle as possible. Use a pipe bender 

for bending.
(Bending radius should be 30 to 40mm or larger.)

7-2 Selection of copper and heat insulation materials.

When using commercial copper pipes and fittings, observe the following:
1) Insulation material:  Polyethylene foam 

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)

Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.  

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe thermal 

insulation

Liquid pipe thermal 

insulation

O.D. 9.5mm

O.D. 6.4mm

I.D. 12-15mm

I.D. 8-10mm

Thickness 0.8mm

Thickness 10mm Min.

Filling a cylinder with an attached siphon

Stand the cylinder upright when 
filling.

There is a siphon pipe inside, so the 
cylinder need not be upside-down to 
fill with liquid.

Filling other cylinders

Turn the cylinder upside-down 
when filling.

Wall

If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt or 
water out.

Be sure to 
place a cap.

Rain

Piping bundle diagram

Finishing tape

Liquid pipe insulation

Inter-unit wiring

Gas pipe 
insulation

Gas pipe

Humidifying 
hose

C

Drain hose

Liquid pipe

Seal the edge of the 
insulation if there is a 
possibility that the 
condensation from the 
shut-off valve might 
drip onto the indoor 
unit through the gap 
between the insulation 
and the pipe.

01_EN_3P177302-2.fm  Page 7  Thursday, May 25, 2006  6:21 PM

Summary of Contents for RXR28EV1B

Page 1: ...V1B Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split syste...

Page 2: ...TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EM...

Page 3: ...or fire If any refrigerant has leaked out during the installation work ventilate the room The refrigerant produces a toxic gas if exposed to flames After all installation is complete check to make sur...

Page 4: ...they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Sinc...

Page 5: ...age 8 When laying the humidifying hose inside the wall block the ends of the humidifying hose with tape or the like to prevent water or anything else from entering it until it is connected to the indo...

Page 6: ...undation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If...

Page 7: ...them fully with the torque wrenches Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas 2 To prevent gas leakage apply refrigeration machine oil on...

Page 8: ...gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operati...

Page 9: ...to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the g...

Page 10: ...o the outdoor humidifying duct 2 Apply a binding band to prevent the humidifying hose from coming off 2 Connecting the cut humidifying hoses When installing the cut humidifying hoses follow the instru...

Page 11: ...m the wire 20mm 2 Connect the connection wires between the indoor and outdoor units so that the termi nal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used...

Page 12: ...ooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are ther mally insulated Water leakage Draining line is properly installed Water leakage System is properly ear...

Page 13: ...0605 HT 3P177302 2 M05B201...

Reviews: